Water pump short cycling diagnostic FAQs:
This article provides answers to frequently-asked questions about how to diagnose short-cycling problems with a water pump or well pump.
If the well pump runs too often or cycles on and off rapidly these diagnostic questions should help troubleshoot the problem.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions and answers about troubleshooting and fixing a well or water pump that keeps turning on and off rapidly were posted originally at SHORT CYCLING WATER PUMP - home - be sure to read the procedures and repairs discussed there.
On 2018-10-02 by Nick
Thank you! A photo of my pump with a GE motor is shown here.
On 2018-10-01 4 by (mod) - squealing noise at the pump is a failing bearing.
Nick
I suspect that the squealing noise at the pump is a failing bearing.
I hate hate and dislike suggesting that there are multiple problems at once - (Occan's razor says the simplest explanation is the most-likely)
but still
I also suspect that the pressure control sensor port might be debris clogged - causing it to fail to cut in and out when it's supposed-to.
A burst tank bladder will cause the tank to become waterlogged or for other reasons will cause short on-off cycling of the pump but not the other symptoms you cite.
On 2018-10-01 by Nick
I have a 1/2 hp GE 5KC36HN2934AX well pump with a SQUARE D Pumptrol 20/40 low pressure cut off switch.
There should be 18psi in the pressure tank WM-9. I haven’t checked. For some reason the cut in switch is kicking in at 30psi and cutting out at 40psi.
Also there is a very faint squeal while running and the guage is jumping up and down until it hits 40 psi and stops. Could the bladder in the bag have a leak and the bearing be going in the pump?
On 2018-09-24 by (mod) - pump shuts off for 15 minutes
Di
I generally stay away from guessing Ed problem causes that involve to false at the same time, but this sounds as if there may be a leaky foot valve or check valve or water running somewhere in the building, combined with a inadequate water in your well
On 2018-09-23 4 by DiAnn
Pump kicKS on for about 30 seconds and shuts off and then come back on about 15 minutes later and won't pressure up over 10 pounds we have replaced the pump and tank
On 2018-08-21 by (mod) -
at the live link
Continue reading at SHORT CYCLING WATER PUMP - home
On 2018-08-21 by Amanda
We are having a terrible time trying to figure out what is going on with our well pump.
We have gone through 3 to 4 pressure switches put in a new well pump and out pressure switch keeps kicking on and off every 1/2 sec. We run our pump during the day but have to shut it off at night to keep from going through another pressure switch.
The pressure switch we normally use is a 20/40 but even after shutting off the pump and water supply the pressure switch still cuts in and out 1/2sec till we manually stop it. We don't know what else to do or replace. Can you help?
On 2018-07-15 1 by Fred Hart
I replaced a water logged well pressure tank that last 5 yrs...after replacing the tank and a new pressure switch set to 40/60 with pressure tank at 38 psi - turned on the pump and it filled the tank and shut off at 60 psi, then a few seconds 3-5 the pressure switch started short cycling on and off.
If I turned on the water the pump ran continuously and maintained 55-60 psi on the pressure gauge. Turn off the water and the within a few seconds it builds pressure to 60 psi shuts off, 5 seconds later it starts clicking on and off.
I checked the air line, check valve and tank pressure and all appear to be fine. This well set up has worked great for 5 years only after replacing the 50 gallon water pressure tank with a new 85 water pressure tank I now have this short cycling problem....thoughts?
thanks
On 2018-07-13 18:40:19.073471 by (mod) -
36 secs. after 5-6 minutes is an argument for loss of air charge in the tank. The tank pre-charge pressure you cite however is right for a 30 psi cut-in.
On 2018-07-13 17:48:54.362945 by KenV
Well maybe a little longer than ten seconds but not the 5-6 minutes it was taking. Timed it and takes 36 seconds.
The holding cisterns are black poly tanks for potable water. I have two; one is 1100 gal, the other 600 gal. I have them T'd into the suction side of my pump with valves to shut off the flow from either one with a backflow in front of the valves.
Checked my pressure tank which is a horizontal Water Worker 20 gal actual (40 gal equivalent) and with the system empty and no pressure in the lines the tank bladder is sitting at 28psi. This is 2 psi below my cut in switch setting.
On 2018-07-13 15:12:24.874827 by (mod) -
Ken
I INFER from our discussion that while your water source is an open cistern, your water pressure is delivered by a combination of pump (drawing from the cistern) and a pressure tank (floated on the water line common with the water pump).
On a typical residential pump and pressure tank water system, regardless of where the water originated, if a pump gets from CUT-IN to CUT OUT pressure in just 10 seconds, then the water pressure tank has lost its air charge. That's part of the definition and explanation of short cycling given in the article SHORT CYCLING WATER PUMP.
Silt and debris in the water supply can indeed clog the pressure control switch for a water pump. But that clogging will usually result in the pump's failure to turn on or off when it should in response to use of and a drop in water pressure in the system.
I can't quite figure out how a clogged switch sensor would cause the switch to turn off too fast.
But you can watch for such a weird situation by watching the pressure on the system as water is turned on and off. If pressure on a reliable gauge drops below the cut-in and the switch doesn't cut on when it should, that'd be an indicator of clogging. (or something else like damaged relay parts).
Wind-blown dust could certainly get into an open-top cistern or water storage tank where it might foul water, contaminate it (manure-contaminated dust around cattle, for example).
In contrast (and for other readers), windblown dust would have no easy way to get into a water pressure tank- a pressure tank is not open to the atmosphere.
On 2018-07-13 by KenV
OK DanJoe I replaced my filters and pump cycles for about 10 seconds to bring pressure back to 50psi.
I replaced the filters when I installed the new pump so I didn't think they would clog that quickly. But I am in West Texas where the wind blows all the time and I suppose dirt and dust gets in my tanks since they have an air breather cap on them (although the breather has a screen, primarily to keep mosquitoes out.)
This is our ranch house and ground water is contaminated due to oil well production over the last 50 years.
Too far away from the county water line to get municipal water so Stan the Water man delivers it to us. All is now working and I guess I will have to replace the filters on a more regular interval.
They are installed on the suction side to keep dirt and dust from clogging my pressure switch orifice.
On 2018-07-07 by (mod) - Pentair 1HP SNE-L pump specifications
Ken the specs on the Pentair 1HP SNE-L pump give it a lift capability of 25 ft. As long as your Cistern storing water is above the pump level, lift should not be an issue. That's why it makes sense to look for a blockage somewhere. Do keep me posted.
Specs for the Pentair 1HP SNE-L 1 HP 115/230 shallow well pump shown below
Shallow Well Jet Pump (Suction lift less than 25 ft) with Max Operating Pressure at 67 psi / 154 ft Total Dynamic Head
1 hp motor that can operate on either 115 or 230 volts, with factory set 30/50 Pressure Switch
Self-priming after the priming chamber has been filled with water.
Close-grained cast iron body. Drain port provided for easy winterizing.
Specifically designed for water systems & sprinkling for residential homes, farms and cottages
On 2018-07-07 14:01:40.513929 by KenV
I will check my filters and see if those are causing the problem. New pump went from 45 seconds to hit 50 PSI to now taking 4 minutes. It is a Pentair 1HP SNE-L 1 HP 115/230 shallow well pump.
On 2018-07-06 20:28:10.223588 by (mod) -
That data sounds quite reasonable.
But something's odd. Any pump and pressure tank combination ought to be able to get you to 50 psi with water supply from a cistern, completely independent from the water level in the cistern itself, unless the pump is not the right one for the application.
On 2018-07-06 16:37:09.274305 by KenV
The pump is brand new. It has a cut in @30 and cutout @50 psi switch built in. I have a WaterWorks pressure tank attached with air bladder set to 28 PSI.
On 2018-07-06 14:56:14.274910 by (mod) -
Ken
I don't think so. Is your pump combined with a pressure tank or are you using a pressure-sensitve pump with no pressure tank ? - as we often do with cistern systems like yours.
I'd look for a damaged pump impeller or debris clogging.
The weight of water in the cistern or its down-pressure on a bottom outlet does decrease as water is used. That's why in many cistern systems we elevate the tank above the building's roof.
But the pump ought to have a capacity well beyond that difference in pressure.
At WATER PRESSURE MEASUREMENT https://inspectapedia.com/water/Water_Pressure_Measure.php we explain the weight or pressure of water in a vertical column such as in a cistern, pipe, or well.
On 2018-07-06 14:00:51.780448 by KenV
I have a cistern system that is supplied by delivered, hauled water.
I replaced the pump a couple of months ago with a stronger pump and higher pressure switch and water pressure to the house improved. 2 months later my pump runs twice as long to bring pressure switch back to 50 PSI and cut off.
Water tank capacity is much lower now due to consumption over two months. Could weight of the water decreasing cause less suction side pressure? Any suggestions?
On 2018-06-30 18:45:10.836222 by (mod) -
Jenni
That's an interesting complaint and one I've not heard before.
I would station someone at the pump and/or pressure control switch to watch what happens when you shut off barn water.
Does the pressure on the gauge continue to fall?
Does the pump refuse to re-start?
If so I suspect
- a sticking check valve at the pump or in the well - replace the valve(s)
- a pump that doesn't respond reliably to changes in water pressure - debris clogging - change the switch
- or of course something else we've yet to discover
Keep us posted. What you find will help others.
On 2018-06-30 18:32:49.463780 by Jenni
If I turn on the water at the barn too fast we lose all water pressure at the house. We have to close the main line, reset pressure tank, let it build up pressure than reopen line.
The pressure tank trips its circuit, I think. We can take multiple showers at a time, run washer alliances at same time and or sprinkler, without problem.
Makes no difference if water is not being used at the house. If I turn water on too fast we lose water at the house. Been that way for years.
Pressure Tank is Gould V140 installed in 1988. Ink about well pump. Well is 50 yards from house, across flat ground. Drives me crazy. The water pressure at the house is not as good as it used to be, as well..
Thank you,
Jenni
On 2018-05-31 01:33:57.381802 by (mod) -
Sean
WHen the pump runs at regular intervals for "no reason" (no water is being used in the building) then you would look for a leak somewhere - in the building (eliminate that by turning off water into the building) or in the piping between the building and the bottom of the pipe in the well.
But you've identified a different problem: an unsafe electrical wiring or control serving the pump. You should TURN OFF the power to the system and ask for help from your electrician.
She will perhaps check for damaged pump wiring or a problem in the pump or control itself.
Yes the problem could be at wet twist-on connectors on wiring in the well - DO NOT try fixing that with power on - you are likely to be shocked or killed.
You wouldn't reach into the well to fix such wiring, you'd pull the whole assembly.
On 2018-05-31 00:46:40.424812 by Sean Fagan
Well is 165 feet deep according to county records. Well is approximately 100 feet deep (sting and plumb bob so it's approximate at best).
New pressure switch 40/60. Tank drained and aired up to 38 lbs. We have had no problems over the 4 years owning this home until now. The pump, when using water hoses out side, has begun "short cycling" (?).
On a consistent basis it runs for 15 seconds then turns off for 105 seconds. I've metered the wires in, at the well casing, and the demand power stays at 240 until the pressure is satisfied. The pump will continually run for 15 seconds and off for 105 seconds until the switch turns off. We have not noticed any issues with just the in house use.
It's only since the I opened the outside lines this summer. One problem I did see, there is are two wire nuts about 18 inches down inside the well casing.
While metering the voltage and timing the cycles, for a few hours, one of these lines shorted against the case a few times causing a loud pop and tripping the 220 breaker.
I have yet been able to figure out how to get down in there to properly repair them. This has been an incredible system, any advice would be greatly appreciated.
On 2018-05-19 01:25:34.875397 by (mod) -
yes there's a problem. If you use the ARTICLE INDEX at the end of this page you can find out article on
Intermittent well pump cycling
Where you will find the diagnostic procedure for the case you described
On 2018-05-18 22:47:15.488042 by Colleen
A second residence is using my pressure tank. It is going off and on when water in the homes are not being used. Is there a problem
On 2017-12-30 by (mod) - pump turns on and off rapidly and then stops until i reset it
Paul,
I suspect your pump is short-cycling until it overheats and is turned off completely by a thermal protection switch in the pump motor.
See the diagnosis and repair steps at SHORT CYCLING WATER PUMP - and let me know what questions remain
On 2017-12-30 by Paul
I just replaced my pressure switch in my crawl space. It turns on and off rapidly and then stops until i reset it
On 2017-11-30 23:21:56.464561 by (mod) -
Sabrina,
I don't suspect a bad pump to start, from the description you give. More likely the short cycling is because by one of the problems discussed in the article SHORT CYCLING WATER PUMP.
On 2017-11-30 19:13:42.788827 by Sabrina
My pump kicks up and down 6 or more times to fill my commode. Is my pump going bad?
On 2017-08-19 15:03:54.767192 by (mod) -
Johnny
Watch the pressure gauge: the pump should turn on when pressure drops below the CUT IN - typically 20 or 30 psi. If it is not turning on at that point and pressure drops further, then even though there's a new gauge there may be a blockage or clog that prevents it from properly sensing the water pressure - such as a debris clog in the pressure tube that conducts water pressure to the switch bottom.
On 2017-08-19 03:31:16.485656 by Johnny Chapman
I put a new pressure switch on and new tank today and water pumps good and strong for 3 to 5 min then stops for 45 seconds then nacj on strong then off i need help
On 2017-07-10 02:55:55.539127 by (mod) -
Perhaps water tank is isolated from the rest of the plumbing system
On 2017-07-10 01:52:33.831901 by Harv
Well is short cycling pressure tank is good what else could it be ?
On 2017-06-20 01:12:18.345633 by Williàm
The control box for the water well is clicking rapidly. What could be the causes
On 2017-06-19 03:09:42.002759 by Kristy
My pump was short cycling so I had the pressure tank replaced by my plumber. All was fixed for a couple weeks and now it's short cycling again but intermittently. If I flush the toilet or run just cold water it might short cycle once and then work normal, but if I run the hot water at all, even when mixed with cold like for a shower, then it does it quite a bit more. It also short cycles when no faucets are used but we have a known drip in the kitchen sink.
Once in a while when the faucet is turned on the water will come to a stop as if the well had run dry but after about 30 sec the pump kicks back on and flow is back to normal. My plumber already came back out to inspect the pressure tank and it's working normally but he didn't have time to inspect much further at the time. I have noticed that when taking a shower when it starts to short cycle the water will run noticeably cooler for a couple seconds. Would the problem be more likely to be my pump or my hot water heater? Both are only about 5-6 years old
On 2017-05-23 23:04:12.333708 by (mod) -
Tony,
You might want to scan through the article SHORT CYCLING WATER PUMP as it summarizes the causes of well pump short cycling, or if you prefer a more concise explanation we have a table summarizing the causes and curse of this problem at
WATER PUMP SHORT CYCLING DIAGNOSIS TABLE
https://inspectapedia.com/water/Water_Pump_Short_Cycle_Table.php
On 2017-05-23 19:26:26.823043 by Tony
I have a water well and my 40/60 switch is turning on every minute and a half it is a new switch
On 2017-05-03 21:36:59.016049 by (mod) -
Robert,
That constant clicking on and off usually tells us that a pump is short cycling, and the clicking is the pump control relay.
On 2017-05-03 21:36:24.071121 by (mod) -
Nina
Your'e right that the pressure tank is keeping the pump from cycling on and off so rapidly as to wear it our or overheat its motor. Thanks for your comments.
On 2017-05-03 11:45:39.404889 by Robert
I use my well pump for my garden I'm getting low pressure at the tank in the house about 5 psi.
when i pulled the cover off the manhole in the yard, that the submersible pump is located in i hear a constant clicking on and off. i just changed the pump 4 years ago and hardly ever use it.
Why do you think i have such low pressure? and what is the clicking ?
On 2017-05-02 17:00:27.183657 by Anonymous
@Nina M.,
While the tank holds a reservoir of water the main purpose is to conserve your pump. If the upper is only going to 38 you just need to adjust the upper limit nut on the Pressure switch (should be on the right). Run the water until the pump comes on again and check the pressure again.
This is best done in small increments say 1/4 turns (depending upon your switch). If you are talking about the pressure read from your tank
. I am not sure whether air pressure and water pressure would be the same. I am inclined to think so, but I don't know. Mine has a pressure gauge on the pressure switch, reading from my tank would require a tire pressure gauge.
On 2017-04-08 19:29:59.963736 by (mod) -
Anon
The arrow always points in the direction of normal water flow.
On 2017-04-07 23:57:31.659097 by Anonymous
Which way should arrow loint on a water heater inlet check valve
On 2017-03-24 18:44:28.310893 by (mod) -
Nina
Searching (in the search box just above) InspecApedia for "adjust pressure control switch" finds WATER PRESSURE CONTROL SWITCH ADJUSTMENTS at https://inspectapedia.com/water/Pressure_Switch_Nut_Adjust.php
Please take a look at that procedure and let me know how that works for you.
On 2017-03-24 18:00:49.344893 by Nina M.
We just replaced an older 20 gallon water tank with a 32 gallon water tank in a home we just purchased.
We are still using the jet pump (shallow well) and pressure switch (Square D single post switch located at pump). At the current adjustment, the pump kicks on at 28 psi and we deflated the empty tank to 26 psi. The issue is that the pump kicks off at 35 psi (not 48 like its supposed to), and we feel like the tank is not at its full capacity.
On 2018-10-18 by (mod) - sometimes we lose prime, pump kicks on and off
interesting question.
I would fix the problem causing loss of prime and replace the pump switch.
On 2018-10-16 by Jessica
We keep having a problem with our pump kickong on and off. Sometimes we can go weeks without and issue.
Normally when we lose water pressure, we have to go prime the pump by holding the pressure switch half way between on and off until the pump kicks on by itself. Sometimes we have no water at all.
I have noticed lately we seem to have to go down to the wellhouse and prime the pump more often when it is raining. Is it possible that the rain is affecting the pressure switch?
We just replace the pump and the pressure switch last year. Any ideas? Cause I am tired of not having water.
On 2017-05-06 16:57:33.390491 by (mod) -
Tammie,
I suspect that there may be one or several problems going on producing the symptoms that you described. Short cycling of the pump, that is pump turning on and off too frequently, occurs when the water pressure tank has lost its air charge - we call this a waterlogged pressure tank.
you can use the search box just above to search this website for
WATER TANK AIR, HOW TO ADD
If your water softener is regenerating very frequently, and if no one has adjusted its controls, then it's possible that your building has a water leak somewhere that you haven't noticed and you are actually consuming more water.
If your water softener is one of the more sophisticated models that monitors water usage that would cause it to go through a regeneration cycle more often.
The relation between these two events might be that an increase in water usage would speed the loss of air charge from my older traditional steel water pressure tank.
On 2017-05-03 23:47:20.021231 by Tammie Moore
My well pump started short cycling several weeks ago at the same time my water conditioner started regenerating much more often. Could these two issues be connected?
On 2017-04-10 14:19:59.201102 by Anonymous
Well pump will kick on then stop.
On 2017-01-05 02:52:16.456928 by (mod) -
Very interesting, and I agree a bit unusual. In a normal well pump short cycling problem case, the faster you run the water the shorter it will be the pump on off-cycle period.
Therefore I would look for something else. After all your toilet tank fill rate is surely much less than the flow rate when someone is running water into a bathtub.
Perhaps there is a partly clogged water filter that is causing short cycling when the flow rate is slow.
Another possibility is simply that you are noticing the short cycle rate at the end of a pump on cycle. So check again to be sure that if you run water at other fixtures the pump never short Cycles.
On 2017-01-05 02:45:54.513396 by Kate
I believe that i have a short cycling issue but it only seems evident when the toilet tank is filling... i have had the kids run the tub and the kitchen sink and don't get tge same 'on/off' repeat that happens after flushing i just counted 7 cycles for one flush???
On 2016-09-13 16:59:18.097347 by (mod) -
Tracey
Like the Poughkeepsie police told Anna M when she complained that the trains running along the Hudson River were blowing their horns too loud, "Well that's one I've never heard before!"
I can but guess that when you are running hot water, maybe with cold on too, or not, that water is running at a faster GPM flow rate and the pump has to cycle more often.
On 2016-09-13 00:46:04.613671 by Tracey
Hi, Our pressure pump cycles only when the hot water tap is on. Cold water is fine. I can see your tips for blocked pipes and valves not fully turned on. Any other reasons why only hot water would be affected? We have a storage tank for the hot water. Thanks, Tracey
On 2016-05-03 20:19:36.835266 by Stephanie
My well pump pressure switch yesterday started clicking on and off the second any water is turned on in the the house. When water is turned on the pressure switch turns on and off rapidly thee entire time. Is my pressure switch needing to be replaced? My pressure gauge is reading 55 and the switch that's on there is a 40/60
Mark said: Ok so I have a few problems here. First off my pump is short cycling drastically as in I flush my toilet and within 3-4 seconds I hear the pump kick on. Second, when it kicks on it only stays on for a few seconds before turning off then it only stays off for a couple more seconds before turning back on.
And recently about once a day or once every couple days the pump wont come on at all and I have to go down and tap the pressure control switch housing for it to come on.
By the time I realize that, we have pretty much lost all pressure in the house due to normal use.
I haven't quite nailed down any tying reasons or times when this happens like my wife doing laundry or something along those lines. When the pump is working we have plenty of pressure, almost too much (water sprays out hard and makes a mess when doing dishes - "lol").
I have looked through this site and have found a bunch of useful information but am overwhelmed and don't have a clue where to start. Any guidance in this matter would be greatly appreciated. - Mark
(Jan 27, 2013) Hunter said: We have a cistern filled by city water and a submersible pump which pumps to a bladder tank, which supplies the house with pressured water. The water flow from faucets has began to pulse so inspected the pump setup outside and observed the pump shorty cycling.
I purchased and installed a new pressure switch thinking it would be a cheap,easy repair, but afterwards, the pump continued to switch on and off, every second. Does this sound like something is clogged?
(Apr 2, 2014) firstclasslimo said: My pump keeps cycling every 1/2 second for about 10 to 15 pulses( on/off/on/off etc.)when it reaches its cut out set at 58lbs psi.with a differential set at aprox. 63 to 65 psi. I can't find a happy medium to shut this thing off.
When it does shut off, pressure is stable with no loss,that is IF all faucets are closed: but if shower or faucet is running;the pump won't shut off.
I have a new pressure tank with bladder, new pressure switch, new pressure gauge(0/100 range).What do I do? Not sure if i have any valves like a check valve or foot valve etc.installed.
Should I ? This is not a new system it used to work fine then started acting up,so i replaced pressure switch as contacts were carboned bad. Didn't fix. Now I can't get thing set right.
Mark and Hunter:
You are describing a classic well pump rapid short cycling problem. Eventually that condition can actually damage the well pump, resulting in less water pressure and flow than previously.
You should be able to obtain satisfactory water pressure with the factory settings of your pressure control switch, typically 20/40 or 30/50 cut-in/cut-out.
Mark I suspect that the reason you sometimes lose all water pressure under these conditions is that the rapid on-off cycling of the water pump is contributing to an overheating pump motor. Many electric motors include an internal thermal overload switch. When the motor is too hot, the switch turns off the motor.
Later when the motor cools down on its own, the thermal reset switch resets and the pump will run again.
The rapid on-off short cycling well pump may also have led to burning on the contacts of the pressure control switch. That's why sometimes you have to tap the switch to get the pump to run. There could be other pressure control switch problems such as clogging of its pressure sensor due to debris in the water line.
Firstclass
My best advice about diagnosing short cycling is in the articles above. I'm not sure just what's going on in the case you describe but I've seen similar problems with a blocked or dirty water filter, mostly-closed water shutoff valve, or a dirt-clogged pressure control switch sensor.
The stable pressure with pump off argues against a leaky foot valve or piping leak. I don't rule out a sticky check valve or foot valve intake but I'd start with the other items I listed first.
...
Continue reading at SHORT CYCLING WATER PUMP - topic home, the home page for this water pump topic, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WATER PUMP SHORT CYCLING FAQs-5 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.