Water pressure gauge questions & answers:
Frequently-asked questions and answers about installing, using, repairing, replacing water pressure gauges on building water systems, pumps, tanks and other water equipment.
This article series describes the location, use, and operation water tank pressure gauges, how to read, use, repair or replace water pressure gauges.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions and replies were posted originally at WATER TANK PRESSURE GAUGE
[Click to enlarge any image]
On 2020-08-22 by (mod)
The pressure control needs to be near the pressure tank or pump but it doesn't have to be at the tank if it's already connected on the pump itself.
On 2020-08-22 by Heather
Our well pump (about 4 years old) has a pressure switch on it. We are now putting in a new tank and every piece of info we can find talks about putting a pressure switch on the tank T-fitting. Do we need to do that, if we already have the one on the pump?
Does the existing one on the pump take the place of the one that is always shown on the tank T-fitting? Or do we need to remove the one on the pump (plug it) and add one to the T-fitting? Thanks!
On 2019-04-13 - by (mod) -
Lee
I suspect your pressure gauge is "stuck" perhaps because the tiny orifice through which water pressure is allowed to enter the gauge is clogged with rust or debris. You could try just replacing the gauge.
Diagnostics for a gauge that is not working are
at WATER TANK PRESSURE GAUGE
and detail
at WATER PRESSURE GAUGE ACCURACY
On 2019-04-10 by Lee b
Replaced well tank pressure gauge and it is still always reading 30psi. Kicks on and off like normal but the gauge never moves.
On 2019-03-27 - by (mod) -
Dawn:
Repair of a leaky drain valve or "spigot" on a water pressure tank is a basic and standard task that some homeowners can perform but if you're not one of them, then yes you need a plumber.
To avoid making a flooded mess one needs to turn off water and drain the pressure tank so that the drain valve can be either disassembled and its bad washer or packing replaced, OR the entire valve is simply replaced with a new one (they're not expensive).
On 2019-03-27 by Dawn
Water is dripping from the spigot near the pressure gauge on my water tank. Water pressure in the house is fine. Do I need a plumber?
On 2017-11-16 - by (mod) -
MIke
when you have to keep replacing the same part I agree that something's wrong. What's happening? If the valve is leaking (which I'm guessing is the case) then the problem may not be the valve but rather an over-pressure (and unsafe) condition in the water tank, perhaps because of a debris clogged pressure control switch. That same debris can also clog a pressure gauge.
No replacing a pressure gauge won't fix any operating problem on a water system. The gauge is passive: it just tells us what pressure it's seeing. It doesn't talk to the controls, it doesn't do anything except tell us the pressure.
On 2017-11-15 by MikeE
I've replaced relief valve on well tank 3 times. It still leaks. I noticed pressure gauge is stuck on 30-40 psi. Is bad gauge causing valve to go bad? Would replacing pressure gauge fix the problem?
On 2017-11-09 - by (mod) -
From your note I can only guess since I have incomplete information, but there may be two problems here.
First, short cycling well pumps are usually caused by a pressure tank that has lost its air charge or has a too-small air charge.
W. If a pump does not turn on at all and if you don't suspect a problem with the pressure control switch, it's possible that you said a pressure tank air charge at a pressure above the pumps cut in pressure number.
Those two possibilities, of course, are two completely different issues with a water pressure tank.
Only one of them will be correct at a given time
On 2017-11-08 by Mike
My well ran dry and since has lost pressure, is short cycling and the pressure gauge is at a constant 32psi. When I primed the pump the gauge read 0 and I watched it pressurize up to 32 but that was the only time it has moved. Any idea what the problem could be. Before this happened I had decent pressure but now I can't take a shower! please help.
On 2017-08-05 - by (mod) -
Sorry Vikalo, our security code doesn't permit a reader to post links or ads. However we welcome content criticism, suggestions, contributions, and those contributors are always acknowledged and linked-to.
Editor
On 2020-08-22 by Heather
Our well pump (about 4 years old) has a pressure switch on it. We are now putting in a new tank and every piece of info we can find talks about putting a pressure switch on the tank T-fitting. Do we need to do that, if we already have the one on the pump?
Does the existing one on the pump take the place of the one that is always shown on the tank T-fitting? Or do we need to remove the one on the pump (plug it) and add one to the T-fitting? Thanks!
On 2019-04-13 - by (mod) -
Lee
I suspect your pressure gauge is "stuck" perhaps because the tiny orifice through which water pressure is allowed to enter the gauge is clogged with rust or debris. You could try just replacing the gauge.
Diagnostics for a gauge that is not working are at WATER TANK PRESSURE GAUGE https://inspectapedia.com/water/Water_Pressure_Gauge.php
and detail at WATER PRESSURE GAUGE ACCURACY https://inspectapedia.com/water/Pressure_Gauge_Accuracy.php
On 2019-04-10 by Lee b
Replaced well tank pressure gauge and it is still always reading 30psi. Kicks on and off like normal but the gauge never moves.
On 2019-03-27 - by (mod) -
Dawn:
Repair of a leaky drain valve or "spigot" on a water pressure tank is a basic and standard task that some homeowners can perform but if you're not one of them, then yes you need a plumber.
To avoid making a flooded mess one needs to turn off water and drain the pressure tank so that the drain valve can be either disassembled and its bad washer or packing replaced, OR the entire valve is simply replaced with a new one (they're not expensive).
On 2019-03-27 by Dawn
Water is dripping from the spigot near the pressure gauge on my water tank. Water pressure in the house is fine. Do I need a plumber?
On 2017-11-16 - by (mod) -
MIke
when you have to keep replacing the same part I agree that something's wrong. What's happening? If the valve is leaking (which I'm guessing is the case) then the problem may not be the valve but rather an over-pressure (and unsafe) condition in the water tank, perhaps because of a debris clogged pressure control switch. That same debris can also clog a pressure gauge.
No replacing a pressure gauge won't fix any operating problem on a water system. The gauge is passive: it just tells us what pressure it's seeing. It doesn't talk to the controls, it doesn't do anything except tell us the pressure.
On 2017-11-16 - by (mod) -
MIke
when you have to keep replacing the same part I agree that something's wrong. What's happening? If the valve is leaking (which I'm guessing is the case) then the problem may not be the valve but rather an over-pressure (and unsafe) condition in the water tank, perhaps because of a debris clogged pressure control switch. That same debris can also clog a pressure gauge.
No replacing a pressure gauge won't fix any operating problem on a water system. The gauge is passive: it just tells us what pressure it's seeing. It doesn't talk to the controls, it doesn't do anything except tell us the pressure.
On 2017-11-15 by MikeE
I've replaced relief valve on well tank 3 times. It still leaks. I noticed pressure gauge is stuck on 30-40 psi. Is bad gauge causing valve to go bad? Would replacing pressure gauge fix the problem?
On 2017-11-09 - by (mod) -
From your note I can only guess since I have incomplete information, but there may be two problems here.
First, short cycling well pumps are usually caused by a pressure tank that has lost its air charge or has a too-small air charge.
W. If a pump does not turn on at all and if you don't suspect a problem with the pressure control switch, it's possible that you said a pressure tank air charge at a pressure above the pumps cut in pressure number.
Those two possibilities, of course, are two completely different issues with a water pressure tank.
Only one of them will be correct at a given time
On 2017-11-08 by Mike
My well ran dry and since has lost pressure, is short cycling and the pressure gauge is at a constant 32psi. When I primed the pump the gauge read 0 and I watched it pressurize up to 32 but that was the only time it has moved. Any idea what the problem could be. Before this happened I had decent pressure but now I can't take a shower! please help.
On 2017-08-05 - by (mod) -
Sorry Vikalo, our security code doesn't permit a reader to post links or ads. However we welcome content criticism, suggestions, contributions, and those contributors are always acknowledged and linked-to.
Editor
On 2018-09-06 by (mod) - found mineral scale obstructing water pressure gauge pipe
Thanks for the follow up, that will help other readers. I'm glad to hear that you were successful.
On 2018-09-06 by Steve
Me back again.
Found problem When I took of the pressure guage ,there was a calcium obstruction in the pipe
Gave it a litle tap with an awn and it came clean. It was mazing how much pressure was still there even with the tank drained.
Make sure you have the power off (I did) ,there was quite a jet of water that came up once the obstruction was moved.
On 2018-09-06 by (mod) -
Steve
Two common explanations
One is clogging the sensor port on a gauge or on a small diameter pipe bringing pressure
Two, the gauge is mounted on a pressure tank and water is not entering the tank.
On 2018-09-06 by Steve
I just replaced my pressure guage and for some reason not getting any reading.Yes the pump has been turned back on and pressure built up .
I also blew out the port to make sure it was clear of any build up.I did check the guage with an air line and the guage worked . Faulty guage ?
On 2018-05-30 by (mod) -
Yep. and Yes, excepting some odd cases such as a shut-off valve or obstruction between the pressure tank and the rest of the building water piping system where you're taking the measurement.
On 2018-05-30 by John
Is it correct to say that the pressure gauge that is part of the system and an external gauge applied to the air valve on the pressure tank should read the same pressure? If they do differ, is that an indication that one or both gauges are faulty or is there some other possible cause?
On 2018-04-21 by (mod) -
Pressure gauges typically use a membrane or a thinwalled brass tube as pressure sensor. That device can develop a leak, sending water into the gauge body where water shows up visibly in the gauge glass - and usually the gauge begins to leak.
On 2018-04-20 by Gary
What might cause water to go in an AVC pressure guage?
We just replaced our AVC and got a new pressure guage, turned power to the pump on and as it was building pressure water was going in pressure site.
On 2018-03-05 by Rick
I have a bladder type tank for my well. No water is coming out of the faucets. I checked the air pressure gauge on the T and it reads 0. I checked the pressure at the valve on top of the tank and it reads 40. Any ideas.
On 2018-02-12 by (mod) -
sounds like there is a pipe leak - I'd follow the water pipes
On 2018-02-10 by Barbara Gillet
Our water Froze and then thawed but our water guage keeps spinning and seems like spurts of air is coming out with the water when we turn on the tap; and the flush keeps making a noisewe have a well and the pump is under the mobile, keeps freezing up
On 2018-01-18 by (mod) -
Tanis
You are probably hearing the pressure switch relay click in and out. If it's doing that rapidly your pump is short cycling. search InspecApedia.com using the search box above to find WATER PUMP SHORT CYCLING to read the diagnosis and repair steps needed.
On 2018-01-18 by Tanis
Our pressure tank/gauge making this snap sound like it’s not filling or when the waters running it just constantly snaps. Not sure if we need a new gauge?
On 2017-12-15 by (mod) -
re-posting
Callum Palmer said:
Considering how important the pressure gauge is on most water pumps it really is important to learn how to repair them. I particularly like that the article also goes over how to replace a damaged one with a new one. After all, it might not be worth trying to repair a broken one if you can just go out and buy a replacement.
On 2017-08-21 by (mod) -
Nelle,
I'm not sure what little motor you are discussing.
But IF you are discussing a water pump, you want to look at
WATER PUMP WONT STOP RUNNING - at https://inspectapedia.com/plumbing/Pump_Runs_On.php because a water pump that never shuts off, even when you stop running water, is in trouble.
On 2017-08-21 by Nelle
I was in the area near the well water tank in my basement and I could hear that the small motor that the water pressure gauge is attached to sermed to be running all day as I checked at least 3-4 times. This morning it must be running normal as I've run two loads of wash and family members took showers showers.
How long does thst little motor usually run? I don't know if I should have it checked out by a plumber. The water tank and gauge and little motor are about 4 years old.
On 2017-05-30 by (mod) -
Mary,
If you have normal water pressure, then only the gauge has failed and it needs to be replaced. It's a standard part widely available from plumbing supply houses and building suppliers.
On 2017-05-30 by Mary Collette Brandt
The gauge that is attached to my well water tank is reading below zero where do I begin to check is it the gauge that's broken or does this mean I need a whole new water tank system for my well
On 2017-04-17 by (mod) -
If the actual water flow is not falling to zero at the same time I suspect that gauge is debris clogged or broken and needs replacement.
OR if at the same time your pump cycles on and off rapidly the pressure tank is waterlogged and has lost its air charge.
On 2017-04-17 11:41:37.393708 by Cindy
Q? I have a top sidemount pressure gauge. When water is running, I look at gauge. Garage reads 0, it turns on. Pressure goes to 30. Then quickly drops to 0 again and repeat same cycle. Q? Is the problem w the gauge? Or something electric?
On 2017-04-09 by (mod) -
I would check for a pressure control switch that's sticking - not responding to the drop in water pressure due to clogging
On 2017-04-09 by Gary
my water well has great pressure when you first turn water on bout 8 seconds later it becomes a small stream the pressure gauge shows 60lbs i have changed out the filter system the gavanized pipes were bout completly full of crud.
On 2017-03-14 by (mod) -
Simplest is to connect the gauge to a laundry or outdoor spigot or hose connection - also in my OPINION - safest.
An inline water pressure gauge is very nice - I like being able to see pressure at any time - but unless the gauge is installed on a loop or riser that can be isolated from the active water piping there is a risk that the gauge itself fails when nobody is around - flooding the building and causing an expensive mess.
So either use a temporary gauge or install an isolating valve on a riser before the gauge.
On 2017-03-14 by Thomas Atanasio
Am I better off using an "in-line" water pressure gauge on my cold water line or should I just use one and attach it to a hose outlet to read my water pressure periodically???
On 2017-02-18 by (mod) - a running toilet does indeed consume water - see that at your water meter
Sure, Barry, as a running toilet is going to use water by periodically re-filling its flush tank.On 2017-02-18 23:30:43.576317 by barry
the water gauge im talking about is the one that gives your reading on water compsumptions
if the flapper valve on toilet is lose and after flushing the toilet and it keeps running would it affect your water gadge. my water bill seemed higher then normal..?
or what would make it go so high?
On 2017-01-13 by (mod)
Sorry Cathy I don't understand what knob, what release
. If you simply mean you're connecting a garden hose to an outdoor hose spigot (hose "bibb" in fancier talk) and then you open the spigot and no water flows, then if there is water elsewhere in the building there's probably a shutoff that's closed preventing water from moving to that outdoor spigot.
The pressure gauge "move up"? where, on what, measured how?
On 2017-01-12 by Cathy smith
When i turn the blue knob to release water from my wellto a hose shouldnt the preasure guage move upOn 2016-12-21 by (mod)
No indeed, Anon.On 2016-12-21 by Anonymous
Does a pressure gauge for a bladder well tank suppose to have liquid in itOn 2016-10-28 by (mod)
Phyllis, for some detailed diagnosis and repair advice please use the Search InspectApedia website box just above and find WATER PRESSURE COMES and GOESOn 2016-10-26 by phyllis
Im having problems with my water. Its not at its full pressure it comes and goes. Ive changed the pressure switch and that didnt change nothing. My pressure gauge is not working either. Is my pump going bad? Im getting water but I dont know what to doOn 2016-10-20 by (mod)
I don't know but I suspect the new gauge was either defective or more likely was damaged during installation. For example, installing a gauge by holding on to and twisting the gauge body instead of using a wrench on the gauge base can cause damage.On 2016-10-20 by Darren
I just had a pressure gauge replaced because the old one had filled with water. About 3 days after the new one was installed (by a plumber) it filled with water. Could you tell me what is causing this? thanks for any help.On 2016-07-31 by (mod)
If the tank is heavy then it probably contains water but cannot drain.On 2016-07-31 by Denny
The part that is really confusing me is no water in tank or lineOn 2016-07-3 by (mod)
I'm confused. If the water pressure is at 70 psi then I'd expect to see that same pressure in the pressure tank as anywhere else. Perhaps debris has clogged one of your pressure gauges and/or the pressure switch?On 2016-07-31 by Denny
No water in house. Water in well got below the pump. Now it is back to normal level. However I cannot get the switch at the tank to prime or run. I have power to the switch. No water in tank. My pressure gauge is at 70 psi.
And the air pressure in the tank bladder is 30 psi. Seems like I may have more than one problem. It was working fine prior to the water level dropping. New tank, gauge 3 years ago.
On 2016-07-10 by (mod)
RichardOn 2016-07-08 by richard field
concerned about my water pump. I use the shower and pump comes on and off a few times which increases the water power but after 3 minutes water flow gradually weakens while pump is on, I close the shower faucet but pump continues running for up to +20 minutes.
What and where do you think the problem is? There is 2 metres water in well but 18 months ago there was 5 metres!
On 2016-06-16 by (mod)
It's possible that both gauge and pressure switch are debris clogged and need replacement; Check first that the pump is capable of reaching the cut-off pressure set on the switch.On 2016-06-16 by Bill
My Pump draws water from the lake but pressure gauge doesn't seem to be functioning and pump will not automatically turn off. notOn 2016-06-04 by (mod)
Joann the pressure gauge needs to be replaced.On 2016-06-04 by joann rosen
water visible on dial of pressure gauge, does that mean it is broken, can it be repaired, the dial is not registering more than a couple of psiOn 2016-05-08 by (mod)
Doesn't soudnd good, Mike.
I trust you turned everything off. Nothing should be coming out of the pressure gauge; if air or water is leaking out of the gauge it's broken and needs replacement. It may be that the pressure tank has become waterlogged from loss of air in the pressure tank; that in turn can cause rapid on-off cycling of a water pump that can damage the pump or that can cause it to turn off.
On 2016-05-06 by Mike Carey
My pressure gage that goes into my water tank reads zero and air is blowing out the bottom of the gauge hardly any water pressure in houseOn 2016-04-21 by (mod)
RayOn 2016-04-20 by RAY HATFIELD
MY WATER PRESSURE GAUGE DOES NOT READ AT ALL UNTIL MY PUMP KICKS OFF AT 60PSI. WHEN IT STARTS TO FALL IT GOES TO ABOUT 40LBS AND THEN DROPS TO 0 AND STAYS THERE UNTIL THE PUMP KICKS ON AGAIN. IS THE GAUGE DEFECTIVE, BECAUSE ITS DONE THAT SINCE I INSTALLED IT NEW, ORE IS MY PRESSURE SWITCH DEFECTIVE.On 2016-02-07 by (mod)
I suspect a failing relay.On 2016-02-07 by Anonymous
hot water heating system is working but a buzzing noise from pump relay what does it mean and what is a safe pressure reading?On 2016-02-07 by Anonymous
hot water heating system with working but a buzzing noise from pump relay what does it mean and what is a safe pressure reading?On 2016-01-29 by darryl
When a water tank has become waterlogged,how do you correct this problem?On 2016-01-24 by (mod)
RandyOn 2016-01-19 by Randy
Just noticed the gauge on my holding tank which is set at 40/60 seems fine until it goes on once it hits 60 it shuts off and slowly drops to 50 and holds until water is in use.So of course I'm lacking pressure whould this be a bad gauge?On 2015-12-01 by (mod)
Christine:On 2015-12-01 by Christine
My water tank pressure gauge is leaking. There is a slow drip from the gauge and humidity behind the glass. What should I do? I just ordered a new gauge. Do I need to exchange it? Can I just screw the current on e on tighter? If I remove it, will water spout out? Thank you.On 2015-10-23 by (mod)
YOu posted this question elsewhere; Please try just one post per question as we have trouble keeping up with the volume. Look for a problem with the well flow rate.On 2015-10-22 by janet scrimager
high my well pump wouldn't shut off- so we decreased the pressure switch from 20/40 to 23/10 and it's working but not enough water I'm afraid should we replace pressure switch- we treated the well and flushed it out- help.On 2015-10-16 by (mod)
Please see your question and our reply atOn 2015-10-16 by kenneth
My well pump won't turn off the gauge always reads zero but we have great water pressure if I turn the pump off we continue to have good pressure for awhile until it runs out what would be my problem here . Your help is appreciated.On 2015-09-26 by (mod)
Typically that means that your system has pipes with a reduced diameter or clogs
. The initial force is the pressure provided by your water supply when no water is running. But when you open the faucet the pressure drops off immediately to a slower flow rate because the volume of water that can be pushed through the piping at that same initial pressure is reduced.
See CLOGGED SUPPLY PIPES, DIAGNOSIS - at https://InspectAPedia.com/water/Clogged_Water_Pipe_Diagnosis.php
On 2015-09-26 12:05:45.989466 by Anonymous
Hi: Our water comes on forcefully for a second and then reduces to a smaller stream, would this be the pressure gauge or something else. Thank you for your reply.On 2015-06-22 by Anonymous
My pump short cycles about every five seconds. I added air to the pressure tank to about 30 psi. The pump still short cycles every five seconds but goes about 15 seconds when the toilet is flushed. Do I need to add more air to the pressure talk or is my bladder bad in thr tank?On 2015-05-25 by Anonymous
My pressure guage is reading about 90 on a 30-50 setup...It drops to about 80 when water comes on
What should my guage be set on when coming on and off...I'm stumped ...I cut the power off to it because my spicket outlet was leaking and it had to be replaced...I cut power back on , .It still pumms water but I'm just worried about the guage reading so high...Thanks for any help or explanation....Dale
On 2015-05-23 by David
My pressure switch will not cut on and pressure gauge reads zero. Put new switch on and it worked for a couple of days and now its doing the same thing again. Would a bad pressure gauge cause it not to read correctly and not kick in?On 2015-04-27 by (mod)
LincolnOn 2015-04-27 by Lincoln
I need to know where to put my pressure gauge I have a new one on the tank it cut off at 60 then drops to 40 stays there until I cut the water on, it drops all the way to zero before the pump comes back on.
I may need to replace the pressure switch so while I'm at it do I need to move the gauge or add one?
(Nov 24, 2012) Ken said:
Hi i would like to ask how come my pressure gauge is stuck at 0 and the pressure switch is not turning off, the water is filling up my tank and i removed the guage water is coming out of it.. I tested my pump with a bucket, it goes up to 90 psi but when i put it in my tank it pumps water, but the pressure gauge won't move even a bit.
I remove it there is very strong air coming out of it.. i tried blowing into the pipe connecting the gauge and the tank, but its clean..
i've already closed all the valve drained my tank, and refilled it. i tried testing my tank and it does pump water, i tried changing the pressure gauge and tried it at the shop its also working. Can u guys help me out?
Ken
Check for debris clogging at the pressure switch bottom sensor port as well as at the gauge. Replace the gauge.
5/26/14 robert said:
What does the float do in a water pressure tank
Robert
The "float" in a water pressure tank is probably referring to the small float that actuates an air volume control on a water tank that does not use an internal bladder.
For details see
AIR VOLUME CONTROLS, WATER TANK
where we discuss the US Gauge & Similar Type 310WJ, Type 300SL, or Type 6 Rectangular Air Volume Controls = Excess Air Vents
Separately at GRAVITY OPERATED WATER TANKS & Open Water Tanks Indoors we describe open water tanks that also use an internal float. The tanks in this group include rooftop water storage tanks and indoor gravity-operated water tanks - these are not pressurized vessels.
(June 25, 2014) Jerry said:
The pressure gauge has water inside. There is dripping from a spout. What's wrong?
(July 18, 2014) Chuck said:
There is water and condensation sitting inside my pond pump's pressure gauge. Is this a problem?
(Dec 24, 2014) Rick Ciotti said:
Recently our plumber installed a new Well Rite tank, pressure switch and dial pressure gauge.Today I checked the water pressure and noticed that the dial face appears to be almost filled with water. I contacted the company that installed this system and they said this is oil in the gauge and is normal.The gauge appears to be reading correctly. Is this BS?
Sounds like two different problems.
When there is water or "condensation" inside the pressure gauge, the pressure gauge needs to be replaced as it's got an internal leak.
Dripping from a spout (meaning faucet at a plumbing fixture) is fixed by repairing a bad faucet valve washer or replacing the valve. On occasion abnormally high building pressure - say over 70 psi - can also contribute to frequent faucet leaks.
Chuck,
I would replace the gauge because the leak not only affects its accuracy but because corrosion could cause it to burst, flooding the area.
Rick the gauge is defective and should be replaced. The risk, besides improper pressure readings is a burst gauge and leaks.
9 Aug 2014 Andrew said:
Hi I recently replaced our submersible water pump (DAB Pulsar 40/50 M), because of a faulty electrical component in the pump. I looked around to see if I could get it repaired but the cost was excessive compared the a new one. (It was over 10 years old).
There is a float switch attached to the pump which works in conjunction with a pressure switch and gauge mounted on top of the pressurized cold water cylinder. The system is set to a max pressure of 3 bar. When the pressure drops to about 1.5 bar the pump automatically recharges the water cylinder.
After I replaced the pump everything was working fine again, until recently.
I started getting erratic re-filling of the tank. The pressure would drop and the pump wouldn't cut in to recharge the cylinder. 5 minutes later the system would recharge. There is plenty of water in the well, so naturally I thought it was the switch or gauge.
I've just replaced both.
The problem now is that when the pump is switched on the system recharges but the gauge is not registering any pressure and the switch doesn't turn the pump off. If I let it run I'm sure it would explode.
Andrew
If your water supply contains silt, iron, debris or the like, I suspect that the gauge pressure port is clogged and possibly there is similar clogging of the pressure sensing port of the pressure control switch. Try replacing the gauge, and cleaning or replacing any clogged small-diameter piping - same for the pressure switch. Keep us posted.
(Aug 11, 2014) Andrew said:
Hi. Thanks for your replies. Since I last posted, (see below), I'm now getting a reading of pressure gauge but it's very slow to react therefore I can only conclude that there is still some sort of debris still clogging the pressure port in the gauge or control switch. (Thanks to DanJoeFriedman & Chuck for your diagnosis).
I've checked the bladder in the tank and it's not split or burst - No water coming out of the air filler on top of the tank when pressed.
I guess I'll take everything apart again give it a dam good clean and cross my fingers. I'll let you know how I get on. Thanks once again.
Every thing is now back together and working 100%. There was a small piece of rust residue in the neck of the water cylinder. I made sure that this inside if the pipe was completely clean, reinstalled the pressure switch and gauge and recharged the system. Job done..... Thanks for your advice. Great website ;-)
Reply:
Thanks for the follow-up Andrew - we'll keep this blocked line / gauge report around as it will assist other readers. DF
(Aug 18, 2014) Tom said:
When my pressure gauge reaches 30 psi I can hear the click to indicate my pump in the well has kicked on but nothing happens. Only after the pressure continues to fall or I turn the water on and off a few times does the pressure begin to climb back to 50 psi. Any ideas?
Tom
If the pressure switch "clicks" to turn on the pump that should be turning on the pump motor.
If your pump is a submersible one that uses a separate pump relay operated by the pressure switch, the problem could be there - like a bad relay, bad start capacitor, bad wiring connection to the pump, or unfortunately possibly the pump itself could have failed.
(Aug 23, 2014) Andrew said:
Tom - I had a similar problem with our submersible pump. After more than 10 years of reliable use the system didn't recharge when the pressure dropped below the set psi. I discovered, after speaking to DAB that the problem was likely to be an electrical capacitor within the pump that basically kick starts the motor and gets it turning.
I investigated the cost of replacing this part. The price of the part was only 20 Euros but the labour to strip down the pump was well over 200 Euros and the specialist wouldn't guarantee the repair. The best option was to buy new. There must be a scrap value in the old pump. It's all stainless steel.
Andrew
It may be time to scrap the pump, but first here's something to check.
Depending on where your pump is located (e.g. if it's above ground you've got a chance),
Take a look at the hard-start capacitor kit discussion, including wiring details, found at
inspectapedia.com/electric/Starting_Capacitors.php
You'll see that in some cases you can leave an old defunct capacitor in place and simply add the new one to the circuit.
Whether or not that will work for you is questionable as your pump is a submersible unit, but I'd give the pump company to call to ask about that option. Often when a pump motor is failing it's seizing and a new capacitor won't fix the problem.
But if the problem were really the pump motor's own capacitor of if the motor has some life left in it, the add-on cap trick might work for a time.
(Aug 25, 2014) Andrew said:
Thanks for the comment Dan. The pump is submersible DAB Pulsar 40/50M and is a sealed unit. I tried to take a look inside but it was just impossible to take it apart without some sort of serious puller.
It's a shame because I'm sure it still has some life left in it. I contacted a registered agent to obtain a price to replace the capacitor but I decided it was more cost effective to purchase a new unit.
A case of built in obsolescence.... I hadn't thought about installing an external capacitor. Interesting idea. Thanks.
Andrew if you can spin the pump motor it may not be seized. At InspectApedia (How to test electric motors) we give some diagnostics that can help figure out what's wrong: motor vs. mechanical parts.
In general if we think a motor might run, an external start capacitor is a cheap fix to try. But in this case I'm doubtful we can attach an external start cap to a submersible pump - though it'd be interesting to look for one intended for that application.
Before going to a lot of trouble I'd try an above-ground test.
(Nov 19, 2014) Michelle said:
October 2012 tank sprung a leak and was replaced with a Well X Trol - although there was room to install upright in crawlspace the guy installed on its side.
May 2013 tank starts short cycling every 10 minutes. Well guy comes out and assumes tank is fine because it's new so he pulls well up to check for leaks.
No leaks found. He then checks tank and finds that the bladder is shot. Tank was replaced with another Well X Trol and this one was installed upright. It took a few weeks to get consistently clear water in the house.
The toilet tanks got rusty and contained sediment and the water faucets would sporadically spit out rust colored water.
A few months later my water softener quit, when we replaced it we found the filter screen where water is drawn in was caked w/sediment.
Soon after my washing machine quit filling so I checked the filter/screen and found it too was caked with sediment. I then checked all the filter/screens on faucets and found they had a lot of debris.
For the past several months I've heard the water tank cut in at strange times. There are 2 people in the household so not much water is used. I will hear tank cut in and then an hour or so later it will cut in again. We've been gone for an entire weekend (no one in the house at all for 3 days) and come back to hear it running.
I sat by the tank for 10 minutes the other morning and watched the gauge very slowly drop from 45 to 30 and then cut in and jump to 60 and then ever so slowly drop again all the while no water is being run.
Strangely, I am NOT noticing an actual water pressure issue, showers and water faucets run consistent pressure. Any thoughts on where we should start?
Ok Michelle. no worries.
But watch out, many pressure tanks are not designed to work installed on their side.
(Nov 21, 2014) Michelle said:
Thank you for the comment, Dan! You are correct, the one that was installed on it's side started short cycling 6 months post-installation and the well guy (a different one than the one that installed it) found the bladder was shot.
The replacement tank was installed upright and there's been no issues.
As for my current short cycling problem, I called a company who checked things out and isolated the issue to a leak between the house and the well. Fortunately it was at the base of the well. They fixed the leak and replaced my pitless adapter with a pitless unit. Everything is running great.
hanks again! I've been learning a lot reading through your website.
Thanks for the feedback Michelle, it will surely help other readers. I'm glad our data was useful. We welcome questions, comments, suggestions, criticism.
(Jan 5, 2015) Justin R. said:
Hi, My BII pressure gauge indicator on my home well pressure tank looks like it went bad. Everything else looks to be OK at the moment. Right now, I am looking to replace the gauge indicator. I was reading the "how to guide" above and had some concerns about what to do to fix this without calling a professional.
I will be buying the exact replacement part but the order of how to fix it confuses me.
1. I will turn off the power to the well.
2. drain the water from the tank out the bottom.
3. prep the new gauge for install with teflon tape.
4. remove the old gauge.
5. replace with the new one. 6. turn power back on and refill the tank with water.
Is there anything I am missing or anything that I should be aware of or avoid. I don't want to screw the system up. Will I be allowing air into the system by doing this and if so what do I do?
Justin,
Just how much trouble you need to go to depends on just where the pressure gauge is mounted.
Basically you need to turn off the pump, remove water pressure from the system, and if you don't want to get wet, drain water from the system or from the pressure tank to allow removal of the old gauge and installation of the new one.
Your 6 steps are just what I'd do. IF you're not going to mind a little splashing or water leakage, you can do this repair just removing pressure from the system but without having to drain all of the water out. Just don't panic when you remove the old gauge and install the new one when some water squirts out of the mounting tapping.
It helps to have an assistant to stand by to hand you the new prepped gauge.
I would take some care to avoid getting electrical components wet - protect them as needed. And mop up any spills so as not to be standing in water when turning the system back on.
And don't panic about squirting water such that you screw the new gauge in crookedly - if you cross-thread the receiving tapping you'll have created a bigger repair.
Take some photos of your procedure and send them along to me if you can - use the email at our CONACT link found at page top or bottom.
Good luck - let us know how you did.
26 Feb 2015 Larry said:
My pressure gauge seems to be acting irradical; it will slowly and steadily go down to 30; kick the pump on but here is the weird thing.
It only takes a couple seconds to get it back to 50 where it cuts the pump off?
I know it usually takes nearly 30 to 45 seconds to fill the tank and get to the 50 shut off point.
Am I wrong in thinking the pressure gauge is bad or is there a leak somewhere. When I shut the water line off to the house the gauge normalizes and stays pretty static at 49ish.
Larry
Often a debris clogged opening on the pressure gauge blocks its ability to consistently sense water pressure. Try replacing the gauge.
...
Continue reading at WATER TANK PRESSURE GAUGE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WATER TANK PRESSURE GAUGE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.