InspectAPedia®

Dryer vent installation, sloppy © D Friedman at InspectApedia.com Clothes Dryer Exhaust Vent Installation
Dryer vent duct installation specifications

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Clothes dryer exhaust vent installation codes & specifications:

How to install a clothes dryer exhaust vent: choosing materials, routing vent ducting, dryer vent duct connections, dryer vent termination at an exterior wall.

Also we explain and illustrate problems that result from improper dryer vent installation design, materials, routing, and filtering including dryer vent clogging, clothes dryer fire hazards, building moisture and mold problems, and increased clothes dryer operating costs due to poor or blocked dryer vents.

This article series describes good practices for clothes dryer vent installation, lint traps, wall vents, filters, and screens. We include a list of clothes dryer fire safety hazards and other clothes dryer installation or maintenance mistakes that are either unsafe or that interfere with effective, economical dryer operation.

We discuss types of dryer vent ducting and dryer vent doors or opening protection devices.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Clothes Dryer Exhaust Vent Installation: Safe & Effective Installation of Clothes Dryer Exhaust Vent Ducts

Hole in flex duct dryer vent (C) Daniel Friedman

Most clothes dryer exhaust vent installations use 4" diameter vent piping, the minimum-allowed.

But the variety of materials and duct prices can fool you into making a bad or even a dangerous choice. Clothes dryer exhaust duct material choices that you are likely to find at building supply stores include the materials listed below, and illustrated throughout this article.

Article Contents

Choices of Clothes Dryer Exhaust System Duct Material & Size

Flex-duct: plastic & wire flexible dryer vent duct (photo at above-left), a coil of spring wire covered with a thin, usually white, plastic. Although we have observed this material widely used in homes as "dryer vent ducting" it should not be used for that purpose.

Cranor elaborates: "Plastic" dryer duct" sold at various suppliers does not say on the packaging that it can be used for clothes dryer ducts....it specifically says bathroom venting.

Plastic duct is not a UL approved dryer duct material, not code approved and its use will void any dryer manufacturer warranty."

What's wrong with using this material at a clothes dryer? It is not safe, not durable, and not effective.

Mylar plastic dryer vent duct © D Friedman at InspectApedia.com

Here are other clothes dryer vent materials we have encountered:

Metal dryer duct at wall exit point © D Friedman at InspectApedia.com

Advantages of using metal dryer vent vent duct material

Watch out: Use rigid or semi-rigid metal dryer vent material [we recommend rigid metal dryer vent ducting]: Virtually all independent authorities, including the US CPSC, Underwriters Laboratories, and the Association of Home Appliance Manufacturers, and experienced home inspectors such as Cranor all recommend the use of rigid or semi-rigid metal ducting for clothes dryer exhaust venting. [2][4][5][6][7][8]

And we prefer rigid, solid metal dryer vent ducting wherever possible. An acceptable alternative that is nearly as effective is semi-rigid metal duct work, though we have found that that material is easily dented, crushed, or damaged.

Metal ducts, having a smooth interior surface provide these advantages when used on clothes dryer systems:

Clothes Dryer Exhaust Duct Vent Hood Types

Standard clothes dryer vent cover on an exterior wall (C) Daniel Friedman

Above: an angled clothes dryer exhaust vent hood. Two other types: a box hood that is quite similar, and a louvered hood are also provided.

Details are at CLOTHES DRYER WALL VENT SCREENS

Watch out: we have found serious and chronic lint clogging of louvered dryer exhaust vent hoods IF the hood uses multiple louvers that are small in width.

Lint-clogged screen on clothes dryer vent (C) Daniel Friedman

Above: I'm checking a two-louver dryer wall vent hood that is somewhat resistant to lint clogging.

Clothes Dryer Vent Line Installation & Elbows

For optimum clothes dryer venting we use 4" or larger galvanized metal duct sections and elbows, though aluminum is also acceptable in most locations.

Flexible clothes dryer is easy to install, avoids having to mess with elbows in the duct system, and is inexpensive, but that material restricts air flow and may sag, giving you areas that collect water and risk leaking into the building.

Our dryer vent installation photos just below illustrate use of 4" galvanized metal dryer ducts.

Metal dryer duct at wall exit point © D Friedman at InspectApedia.com

Above you can see that we had to use a pair of elbows to lift the dryer vent duct into the building ceiling cavity.

The dryer vent joints are secured with foil tape.

Watch out: some manufacturers recommend against using sheet metal screws to secure dryer duct sections because the screws collect lint. Also if you have ever tried reaching into a dryer exhaust duct to clean it by hand and had your arm ripped open by the SMS screw you may have another objection.

At above right our second dryer vent duct photo illustrates passage of the duct through the rim joist.

Notice that we carefully caulked this opening both inside (shown) and outside the wall (not shown).

Metal dryer duct at wall exit point © D Friedman at InspectApedia.com

This duct section can be inspected and if necessary cleaned by removing the outside vent cover. Photos courtesy of Eric Galow, Galow Homes.

We secure connected dryer vent duct sections using metal foil tape at each vent section. (See the dryer vent duct photos just above).

Watch out: manufacturers typically advise against using screws to secure dryer vent duct sections as the end of the screw protruding into the duct interior increases lint-trapping and may make the vent duct harder to clean.

Specs for using flex duct for dryer venting: If despite our recommendation for metal exhaust duct material you nevertheless are using flexible fan duct, stretch the flexduct tight to keep it as straight and smooth inside as possible. Long sloppy bending flexduct runs significantly reduce the performance of the vent fan.

Connect the flexduct to the fan itself using plastic ties, or second best, duct tape. Keep all connections tight and avoid air leaks.

Banjo or periscope dryer vent connection © D Friedman at InspectApedia.com

Connecting the dryer vent to the back of the clothes dryer: space is usually tight between the clothes dryer and its exhaust vent because homeowners want to push the dryer back as close to the wall as possible.

If you use flexible or even semi-rigid duct for the dryer connection at this location (a most common practice) the duct is likely to be bent and crushed closed, increasing dryer operating time, cost, and fire risk.

Our photo above illustrates how we connected a clothes dryer outlet through a laundry room wall into an adjoining utility room where the duct could rise to its ceiling and outdoor exit destination.

On the other side of the wall in the photo shown above a periscope type connection adapted the dryer outlet to the through-wall vent.

A "banjo-type" or "periscope type" metal dryer vent connector makes the 90 degree bend connection at the back of the clothes dryer where space is limited.

Our photo below illustrates a typical clothes dryer periscope vent that permits the back of the dryer to be placed closer to the wall than would be possible with round dryer vent ducting.

The periscope clothes dryer vent shown is distributed by Whirlpool and depending on size can be purchased for about $20. U.S.D.

Periscope dryer vents are usually telescoping in length and sold in ranges such as 0-18" tall, or longer.

The vent provides better air flow than a partly-squashed flexible duct dryer vent, and it resists crushing, therefore it's safer. The minimum clearance to the rear wall for this type of clothes dryer vent is 2 1/2".

The vent shown can be used on clothes dryers made by Admiral, Amana, Caloric, Crosley, Estate, Inglis, Jenn-Air, KitchenAid, Roper, Vesta, and Whirlpool.

Periscope type clothes dryer vent allows dryer to be placed close to the wall - sold by Whirlpool and other brands.

Maximum clothes dryer duct length & number of bends or elbows:

Keep the vent duct sections as short, straight, and directly routed to the building exterior as you possibly can. Our metal dryer vent installation shown just below has the right idea, though not a very neat installation and not properly sloped.

Dryer vent installation, sloppy © D Friedman at InspectApedia.com Industry standards recommend that the maximum "concealed" rigid metal ducted clothes dryer vent length be no more than 25 feet (IRC; some codes permit 35-feet).

That 25-foot maximum length should be reduced by 2 1/2 feet for each 45 degree bend in the ducting, and by another five feet for each 90 degree bend in the vent duct.

So a clothes dryer vent with three 90 degree bends to come out of the back of the dryer, run up a wall, and then across a ceiling or under a floor to a wall vent would have a maximum length of (25 - (3x5=15)) just ten feet!

An exception to this length reduction for dryer vent elbows may be permitted for large-radius bend dryer vent products such as Dryer-Ell®.

That's because a normal 4-inch 90-degree metal dryer vent elbow bends 90 degrees in a 4-inch radius while the Dryer-Ell product makes its bend over a more gradual 10-inch radius. [Dryer-Ell is at http://dryer-ell.com/ ].

Model codes permit use of large-radius dryer vent elbows:

Section M1502.6 of the 2006 International Residential Code, Section 504.6.4 of the 2009 International Mechanical Code, Section M1502.4 of the 2009 International Residential Code, Section 504.6.4 of the 2012 International Mechanical Code and Section M1502.4 of the 2012 International Residential Code all permit large radius elbows.

However the installation instructions and recommendations from the individual clothes dryer manufacturer are the final authority on how the dryer should be installed.

Some dryer manufacturers permit installations with dryer exhaust venting of much greater lengths [though perhaps combined with a requirement to avoid use of 90 degree turns in the duct system]

Use 45 degree elbows if you can but 90s are ok (C) InspectApedia.com

Note: Fantech notes that

"The 2012 International Residential Code (IRC) is pretty specific when it comes to dryer exhaust venting.

The maximum length for dryer exhaust duct cannot exceed 35 feet from the dryer location to the wall or roof termination. " (Fantech 2012)

Also see CLOTHES DRYER VENT BOOSTER FANS

Slope the clothes dryer vent duct downwards towards its building exit - this will avoid condensation accumulating inside the ductwork and dripping back into the building ceilings or insulation.

It's fine for the dryer vent to rise vertically to enter the building ceiling, but within the ceiling the vent should slope downwards towards its exit point at the building exterior wall.

The same design should be applied to dryer vents that turn down to exit the building below a floor and/or through a basement or crawl space ceiling.

Provide one or more dryer vent duct inspection access points at which you can disconnect and open the dryer duct system for inspection and cleaning.

This is especially critical in long dryer runs through ceilings and walls where the risk of blockage and fire would be increased. There should be no section of dryer exhaust vent ducting that is inaccessible for inspection and cleaning.

Insulation around the dryer vent is not normally necessary if you install straight, well-supported metal ductwork sloping to its exit point at the building wall.

But if ductwork must be routed up and down through space such as an attic, air conditioned interior, or dryer vents routed through a cool crawl space where otherwise the duct will be exposed to cold air the result will be a significant level of condensation within the dryer vent duct system.

For such areas and routing you should consider using insulated solid metal ducting or insulated flex duct to avoid condensation buildup, corrosion or leaks into the structure.

Install a secure, self-closing screened exhaust vent cover  - the vent hood, outside the building at the end of the clothes dryer vent line in order to prevent rodents or birds from entering the ductwork.

Also see CLOTHES DRYER WALL VENT SCREENS

Clothes Dryer Exhaust Vent Routing Options

Recommended clothes dryer venting routing (C) Inspectapedia.com adapted from Whirlpool dryer installation instructions cited in detail in this article.

Get the Clothes Dryer Moisture & Lint Outside of the Building.

Every manufacturer's clothes dryer vent fan installation guide that we reviewed emphasized: make sure that the vent ducting carries moist air all the way outside of the building.

The preferred or most-recommended dryer vent routing is shown above, adapted from Whirlpool dryer vent instructions cited in detail below.

Clothes dryer optional vent routings - adapted from Whirlpool cited in detail in this article at InspectApedia.com

Our sketches shown here, adapted from Whirlpool clothes dryer installation recommendations cited at the end of this article, show typical clothes dryer vent routing options includint a special provision for routing the dryer exhaust outside through a crawl space below a mobile home.

In some areas where winter air is very dry homeowners may choose to temporarily spill dryer vent air directly into the building interior in order to try to raise the indoor humidity level. This approach violates manufacturer instructions and is unsafe.

Do not spill the laundry vent air directly into the building attic or roof cavity, basement, crawl space, or other hidden building interior areas.

Doing so will lead to moisture condensation on building surfaces, wet, damaged, moldy building insulation, wet building framing members, wall, floor or roof sheathing. In these locations spilling laundry dryer vent moisture will certainly encourage mold growth.

And Cranor points out that spilling dryer vent products into the building can be a dangerous carbon monoxide hazard as well, at least for gas-powered clothes dryers.

Even if the dryer exhaust vent does extend to the outdoors, an improperly sloped, damaged, or disconnected dryer vent can leak moisture, lint, dust, and even dangerous carbon monoxide (CO) into the building. Leak stains in building ceilings may be traced to condensate leakage from an overhead clothes dryer vent.

Complete details about clothes dryer exhaust vent installation are provided below in this article at CLOTHES DRYER VENT INSTALLATION DETAILS

Dryer vent duct routing mistakes

Clothes dryer exhaust vents should be directed to the building exterior. Do not vent the clothes dryer indoors nor into an attic, crawl space, or other enclosed area.

Dryer vent spilling into wet crawl space © D Friedman at InspectApedia.com

Vent the dryer duct to outside: Our photo above shows a dryer vent spilling directly below the building first floor into a soaking wet crawl space.

Along with trash, debris, and other water entry sources, this crawl space was a moldy mess that had led to wet building insulation, mold contamination, and damage to the structure.

Clothes Dryers that Vent into the Attic?

Vent fan spilling into attic © D Friedman at InspectApedia.com

Do not vent clothes dryers directly into the attic space: you're only putting more moisture into an area where it is already going to be a problem, inviting mold growth on wood surfaces and hidden mold growth in building insulation.

See MOLD in FIBERGLASS INSULATION

Clothes Dryer Vent Up Through Roof?

Droopy attic ducting of a bath fan (C) Daniel Friedman

Avoid through-roof dryer vent exits: Our photo (left) shows a typical attempt at venting a upper floor clothes dryer through the attic and into a ridge vent - this direction of vent exit may seem convenient but we don't like it much.

In the photo (left) the droopy flex-duct will certainly invite clothes dryer moisture to condense and run back to the home's ceiling rather than exiting at the ridge.

The through-roof vent approach gives us another roof penetration, a possible leak spot, and it almost assures that condensing moisture will drip down the vent duct and into the building ceiling.

Additional roof top dryer vent photos below illustrate a vent that became lint clogged and that was snow-covered (and blocked) in winter.

condensation in vent ducts in an attic (C) Carson Dunlop Associates

Also see CLOTHES DRYER VENT INTO ATTIC?

Clothes Dryers that Vent into the Crawl Space?

Dryer vent duct at crawl space vent © D Friedman at InspectApedia.com

Our second clothes dryer vent exhaust mistake is shown above: the installer hung the vent opening at the crawl space vent screen.

Not only did lint clog the crawl space vent, but most of the damp dryer exhaust air soon was being spilled into the crawl space ceiling.

Clothes dryer vent routing for a trailer or mobile home (C) InspectApedia.com adapted from Whirlpool

Special provisions for dryer venting in mobile homes

Above: a clothes dryer exhaust vent installed in a mobile home can be vented down through the crawl space and outside through the skirting wall, but must never be vented to terminate right in the crawl space.

Exhaust vent must be securely fastened to a noncombustible portion of mobile home and must not terminate beneath the mobile home. Terminate exhaust vent outside. - (Whirlpool 2012) 

Typical Clothes Dryer Vent Routing Summary

Clothse dryer venting options recommended by GE - at InspectApedia.com

Above and below: Do's and Dont's of clothes dryer exhaust venting routing as suggested by GE and cited in DRYER INSTALLATION MANUALS

Clothes dryer exhuast vent details NOT recommended by GE - at Inspectapedia.com

Clothes Dryer Installation & Operation Manuals

Now found at DRYER INSTALLATION & OPERATION MANUALS

Clothes Dryer & Dryer Vent Temperatures

This discussion, now found at CLOTHES DRYER TEMPERATURES gives the various temperatures found inside of clothes dryers, in and at the clothes dryer tumbler or drum, heater, and in the dryer exaust vent during both normal safe operation and during unsafe conditions that risk a dryer fire or building fire.

We include a table of the tempeatures that occur inside of clothes dryers at different places in the equipment and in its venting system and we describe unsafe dryer operating temperatures.

Clothes Dryer Exhaust Vent Installation, Dryer Temperatures, Dryer Fires Research

This reference & research material has moved to CLOTHES DRYER FIRE RESEARCH

...


Continue reading at CLOTHES DRYER VENT CLEARANCES - distances required around clothes dryer exhaust vent terminations or exhaust hoods, or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see APPLIANCE DIAGNOSIS & REPAIR

Or see this

Article Series

Suggested citation for this web page

CLOTHES DRYER VENT INSTALLATION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to APPLIANCE REPAIR

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Questions & Answers on bathroom vent fan and fan ducting installation procedures, codes, standards.

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman