InspectAPedia®

Roof ice dams built a tower of ice from eaves to ground at this Hyde Park NY Restaurant in 2014 © Daniel Friedman Roof Ice Dam Leaks & Attic Moisture
Attic Condensation, Leaks, Mold due to ice dam formation on roofs, Cause & Cure in Buildings

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


This article series describes roof venting problems and solutions:

Ice dams, attic condensation, attic mold, and inspection methods and clues to detect roof venting deficiencies, insulation defects, and attic condensation problems in buildings.

It describes proper roof ventilation placement, amounts, and other details.

These recommendations are based on many years of building inspections, on the observation of the locations of moisture, mold, ice dams, condensation stains, and other clues in buildings, and on the correlation of these clues with the roof venting conditions at those properties, and frequent literature review and professional discussion.

We have also measured changes in airflow, temperature, and moisture before and after installing roof venting.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

How to Stop Roof Ice Dam Leakage & How to Prevent Ice Dam Formation at the Roof Edges & Gutters

Severe ice dams, eaves to ground in Poughkeepsie NYHow to STOP ongoing roof ice dam leaks

Let's start with emergency measures for buildings already in trouble with heavy roof ice dams and leaks into the building attic, walls, or other areas.

[Click to enlarge any image]

These are the useful approaches to curing existing roof ice dam leaks into a building attic, walls or other areas:

  1. Use heat tapes:

    during winter & freezing conditions when weather precludes actual building modifications or repairs to add ventilation or ice and water shield, you can use

    HEAT TAPES & CABLES on Roofs for Ice Dams
    to melt channels in existing ice or to prevent water back-ups between new-forming ice on roof edges and in roof gutters.

    Heat tapes at the roof eaves are not a great permanent fix but it's a useful stop-gap measure if you're having ongoing ice dam leaks into the building.
  2. Fix air & heat leaks:

    winter is a fine time to take a look at the attic for missing insulation, gaps in insulation, or for dark spots on insulation that mark air bypass leaks. Fixing insulation gaps and air leaks drops the attic temperature and thus cuts ice dam formation.
  3. Turn down the heat:

    A neighbor told us that as her dad's currently empty house in New York had a long history of ice dam trouble she was keeping the heat up to hope she would melt ice off of the roof!

    Really? No, she was taking the wrong approach. Making the house warmer means sending more heat into the attic or roof space where the under-roof heat melts snow on the upper roof sections.

    That melting snow water runs beneath the snow cover on the roof just fine, right down the warm roof deck until it hits the cold roof overhang or lower edges. There it freezes solid. The more water we send down the roof to the cold roof edge the bigger the ice dam. Don't do that.

    The neighbor then asked: "OK so should I turn the heat down?" Geez! not knowing the house I was worried that if I told her to do that the pipes might freeze - we'd go from one problem to another.

    See WINTERIZE - HEAT ON PROCEDURE for details on how to turn down the heat without freezing the pipes.

Collapsing building © Daniel Friedman

  1. Rake snow off of the roof ?

    lots of people risk their lives or the lives of others having somebody shovel or rake snow off of the roof when ice dams seem to be a problem.

    Really? Snow raking might be appropriate where unusual conditions of deep snow threaten structural collapse of a building, but that's not a great fix for ice dams unless all of the snow is removed from the roof.

    Otherwise, snow high on the roof still melts (in that hot attic), running down to the eaves where it freezes to form ice dams.

    OK maybe smaller ice dams as we have less melting snow and a somewhat cooler attic due to increased heat loss through the non-snow-coverd area, but we'll continue to see ice dams nevertheless.

    Emergency steps in stopping roof ice dam leakage that included removing snow from the roof are illustrated

    at ICE DAM LEAK EMERGENCY REPAIRS

    Raking snow off of roofs (photo at left) is discussed

    at COLD WEATHER ROOF TROUBLE.
  2. Get Rid of the Ice:

    ok so we've seen all sorts of crazy schemes: socks filled with ice-melt crystals or salt (which is hell on the aluminum gutters), chopping ice (which wrecks the roof shingles) at the roof eaves, and my favorite - squirting a jet of hot water to melt drainage channels in the ice dams to allow backed-up water off of the roof.

    I confess, I've done this. It works, for a few hours. Maybe that's a way to make room for heat tapes.

    See HEAT TAPES & CABLES for ROOF ICE DAMS

How to Prevent Future Roof Ice Dam Leaks

Snow raked off of a high New York roof (C) Daniel FriedmanOK so either by choosing from the steps listed above in this article, or by other desperate measures shown

at ICE DAM LEAK EMERGENCY REPAIRS we've taken emergency measures to stop ice dam leaks.

Now how do we stop ice dam leaks in the future, and how do we fix an existing building or build a new one that won't have ice dam leak troubles.

Do we really want to be raking a high roof like the one shown at left every winter?

Doesn't raking snow risk roof damage or a shorter roof life? Are there falling and electrocution hazards? You bet. Here are some other approaches to avoiding ice dam problems on roofs:

  1. Ventilate the roof properly at soffits (eaves) and ridge.

    We'll say more about this below. If you can't ventilate the roof you'll have to go to a hot roof design and hope that nothing ever punctures the roof covering.

    Over at ROOF ICE DAM CURE: Comparing Two Houses we show the best long term way to avoid ice dam formation and roof ice dam leaks: good ventilation and good insulation and no air leaks into the roof cavity.
  2. Inspect & fix insulation & air bypass leaks.

    Details about air bypass leaks themselves can be read

    at AIR BYPASS LEAKS.

    Readers who want to find and fix un-wanted air bypass leaks should also

    see AIR LEAK DETECTION TOOLS

    and AIR LEAK MINIMIZATION as well

    as AIR SEALING STRATEGIES.
  3. Add insulation 

    in the attic floor or under the roof if the present R-value doesn't match your climate zone.

    Readers who want to understand the significance of air bypass leaks and how this problem is corrected should

    see ENERGY SAVINGS RETROFIT CASE STUDY

    and ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE.
  4. Use Ice & Water Shield:

    even in really careful construction, challenging weather conditions or unusual building conditions (someone left the door to the attic open) can cause so much ice formation on a roof that ice dam leaks occur where they never have before.

    As extra insurance against roof ice dam leaks when re-roofing, use ice and water shield at the building roof eaves, running this impermeable membrane (it even seals around nails) up the roof at least three feet, or in some climates or on problem roofs, up six feet or more.

    Watch out: ice formation in gutters at the roof edges can push water back up underneath ice and water shield if it did not bond perfectly to the roof sheathing, or it may push water up underneath the roof deck itself.

    Extra detailing at the roof edges, including wrapping the ice and water shield down over the fascia may be needed
  5. Install & Use Heat Tapes at Roof Eaves & In Problem Spots:

    Sometimes the most expedient, least costly, and fastest way to stop ice dam leaks is to remove accumulated snow and ice (as much as possible and safely) and then install heat tapes in those areas.

    Particularly for un-vented roofs or roof spots at which adding ventilation and insulation to stop ice dam formation is very costly or difficult, the appeal of ice melting heat tapes becomes overwhelming.

    See HEAT TAPES & CABLES for ROOF ICE DAMS

Why Roof Iced Dams Form & How Water Backs Up & Leaks at Ice Dams

Figure 2-54: Roof Ice Dam Formation (C) J Wiley, S BlissAs explained in Best Practices Guide to Residential Construction, chapter

on BEST ROOFING PRACTICES:

Ice dams form when heat leaking into attics or roof cavities from the building below, or from attic ductwork, melts the bottom layer of snow on the roof.

The melt water runs down the length of the roof to the eaves, where it refreezes, forming a dam and icicles.

In the worst cases, liquid water pools behind the dam and flows under the shingles and into the building (Figure 2-54 shown at left).

Research has indicated that the ice-dam risk is greatest when temperatures range between 15°F and 20°F— when it is warm enough for snow to melt but cold enough for it to refreeze at the eaves.

Also, the greater the depth of snow on the roof, the greater the risk of ice dams due to the insulating value of the snow itself.

Cold Roofs Prevent Ice Dams

So how much roof ventilation do we need to prevent roof ice dams, leaks, and attic moisture, condensation & mold problems?

Ventilation helps prevent ice dams by keeping the roof surface cold enough to limit uneven melting. Tests conducted in 1996 at the U.S. Army Corps of Engineers Cold Regions Research and Engineering Laboratory (CRREL), showed that the traditional 1:150 ventilation rule was sufficient to prevent ice dams on roofs with R-25 or greater ceiling insulation.

The 1:300 rule proved adequate for roofs with R-38 or greater insulation. Since most standard eave and ridge vents sold today meet the higher ventilation rates, most new homes are protected as long as there are no large heat leaks into the attic, or tricky sections of the roof with inadequate ventilation. -- Adapted with permission from Best Practices Guide to Residential Construction.

But just adding outlet vents at a ridge (or worse, at gable ends of a building) or just adding soffit vents alone does not work very well to ventilate attics or under-roof spaces.

We need both air inlet at the building eaves or lower roof edges, and air outlet at the ridge in order to move air up beneath the entire roof surface, keeping the roof deck and attic cool and dry.

See ROOF VENTIILATION INTAKE-OUTLET RATIOS for details about the ratio of soffit intake vent area to ridge outlet vent area.

Attic Condensation and Roof Leaks as a Source of Building Mold - Diagnosis and Cure

Frost on attic roof decking (C) Daniel FriedmanSources of Attic Mold: Roof leaks or, alternatively, high levels of attic moisture due to a combination of inadequate attic (soffit intake and ridge outlet) ventilation combine with building moisture sources (such as a chronic or even a single-event wet basement, plumbing leaks, or a leaky roof from roof failure or from ice dams) are likely to cause excessive moisture or actual wet conditions in an attic.

High attic moisture levels or actual wet attic conditions invite extensive mold growth.

Also see DEW POINT TABLE - CONDENSATION POINT GUIDE

Visible frost may appear on attic roof surfaces if the building is located in a freezing climate and high levels of moisture are trapped in a poorly vented attic or roof cavity (photo, left).

Visible mold may appear on wood surfaces in an attic such as on rafters or roof sheathing.

Hidden mold may be present and may be even more of a problem if it forms in insulation or in the ducts and air handler of an air conditioning or heating/air conditioning system.

Typical building air convection currents tend to move air up and out from lower to upper building levels, so one would not think that much mold would move down from an attic into the living area.

But important exceptions to this can quickly move problem mold from an attic into a living area.

Conditions that Cause Air Movement Upwards into an Attic or Roof Cavity Space

As home inspection expert Roger Hankey has pointed out,

"... attic bypasses are one of the primary causes of ice dams. You effectively discuss insulation and ventilation

at INSULATION INSPECTION & IMPROVEMENT

and at VENTILATION in buildings) but if attic bypasses remain in an insulated and ventilated attic, then the result can be frost and moisture damage to the roof sheathing, and/or spot ice dams." - R. Hankey 01/28/2008.

Because warm air rises up through buildings by natural convection, tending to displace heavier cold air, warm building air leaks and forces its way into roof spaces primarily through small openings leaking from heated space into the roof cavity or attic space.

The pressure difference between a warm interior ceiling and a cooler attic or cathedral ceiling space needs only to be slight for air to move from warm to cool spaces in a building.

Remarkably, the current of rising air in a two story or higher building can be quite adequate to even draw cool, moist, or possibly moldy air from a building's crawl space or basement too.

Conditions moving air and potentially moldy air downwards from an attic or roof space include

Toxic white attic mold (C) Daniel Friedman

Building Exteriors Leaks and Mold vs Attic Ventilation & Moisture Troubles

No mold cleanup project will be successful unless you correct the conditions that caused mold growth in the first place.

An expert inspection and report should find and suggest remedies for site and building exterior conditions that produce mold or for building areas that serve as a mold reservoir or as amplifiers for allergens, mold, mildew, excessive pollen or pet dander.

The basic steps: find all unwanted moisture sources, correct appropriate building, site, landscaping, & construction details. 90% of the wet basements and crawl spaces I see are caused by bad or missing roof gutters and downspouts.

An IAQ investigator who has training and experience in building science, mycology (mold science), and IAQ, or in some cases an experienced ASHI-Certified home inspector or sick building investigator who is who has a similar in-depth understanding of construction failures can be helpful at this step.

...


Continue reading at HEAT TAPES & CABLES for ROOF ICE DAMS or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see ROOF ICE DAM LEAK FAQs - questions and answers about ice dam and leak problems posted originally on this page

Or see these

Roof Ice Dam Articles

Suggested citation for this web page

ROOF ICE DAM LEAKS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING VENTILATION

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Questions & answers or comments about how to diagnose and fix attic moisture, condensation, and mold sources

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman