InspectAPedia®

Photograph of  fire retardant identifying markings when newPerformance of FRT Plywood Roofs
History of FRT plywood use, problems, litigation, standards

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Properties of FRT Plywood & inspection tips:

This document summarizes the history of the development and use of fire-resistant plywood roof sheathing in the U.S. and explains the issue of structural damage to roof sheathing where fire retardant plywood roof sheathing, or FRT plywood was used on buildings.

Bottom line: FRT-treated material can degrade seriously due simply to high attic temperatures. Special inspection and testing methods are available. The cost to remove and replace FRT plywood roof sheathing was significant. In addition, FRT plywood roofed buildings apparently did not receive the fire-spread resistance that was intended.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Requirements & Specifications for Fire Retardant Plywood Treatment for Roof Sheathing

FRT Plywood success © Daniel Friedman at InspectApedia.comFRT or flame resistant plywood is (or was) required by building codes for certain structures such as on either side of the fire wall between building units in multiple-living unit structures (apartments, condos, townhouses).

In the U.S. including in your state of New Jersey FRT plywood roof sheathing products began to be widely used during the late 1970s and early 1980s (Barbel 1992), mostly in homes east of the Mississippi, and was used in construction up to 1988 (Kryakos 1994) or possibly a bit later.

FRT deterioration problems were first "discovered" in New Jersey around 1987 and were found throughout the U.S. wherever FRT plywood was used in roof construction.

The FRT deterioration problem was widely investigated by experts as you'll see in citations given at the end of this article, and was addressed by ASTM and other standards associations in North America.

FRT plywood was intended to deteriorate in response to a fire at around 400F by charring to retard flame spread.

But in actual field experience it was found that the deterioration of FRT plywood occurs in response to the heat at temperatures as low as 150F, commonly-experienced by roof sheathing from sun exposure and attic or roof-cavity temperatures was sufficient to so-weaken the plywood that someone walking on the roof could easily step right through the material. (Peterson 1990)

The effectiveness of the fire-resistant roof sheathing also was called into question.

Our photo (left) shows the success of FRT plywood in preventing fire spread from one portion of a flaming building to the next.

[Click any image to see an enlarged, detailed version]

As a substitute for vertical through-roof firewalls on multiple-dwelling buildings, the advent of FRT-plywood permitted omission of those more costly fire-walls that had to be built up extending through roof design.

The omission of that vertical through-roof extension simplified building roof construction thus reducing building cost as well as re-roofing costs.

Watch out: when inspecting a building for the presence of FRT plywood, look first at the roof sheathing from the attic or under-roof space.

If you suspect or confirm that FRT plywood is in place on the roof, do not walk on that roof area as weakened plywood roof sheathing could give way, resulting in both roof damage and severe injury.

Where will Fire Retardant Treated Plywood be found on buildings?

On entry into the attic space of a multiple-dwelling structure such as attached town homes or condominiums, look first for the fire-wall that should have been built between the abutting units. In proper modern construction that firewall should extend from the foundation up through the occupied space and up through the attic space to at least the roof surface.

In that design, typically FRT plywood roof decking was used for four feet on either side of the firewall between building sections, and the firewall terminated just below the roof decking. You can see that design in the photo below.

The concrete block wall on the left of the photo is the fire-wall, and you can see that the plywood roof sheathing adjacent to the fire-wall looks different (like plywood) than the remaining roof sheathing (that is OSB in the right portion of the photo).

In more recent construction as well as in retrofit jobs intended to improve building fire safety you may see a double layer of fire-resistant drywall installed for as much as four feet against the roof sheathing on either side of the party wall or fire-wall between adjacent living units.

Problems with FRT Plywood Degradation

FRT plywood at fire wall in condominium © Daniel Friedman at InspectApedia.com

But on older buildings where FRT plywood was used, attic heat and age was found to lead to deteriorated roof decks even where no actual fire had ever occurred.

Apparently the fire resistive treatment, intended to lead to a "surface charring" of the plywood to slow flame spread, also led to surface oxidation and deterioration. Often structural repairs will be required.

While FRT plywood seemed as if it was going to be a terrific product, it appears that high attic temperatures in some buildings caused early deterioration of the material.

In some cases the plywood became so soft that someone walking on the roof could simply step right through it. The material, as it was formulated in its problematic form, is no longer used in new construction but may still be found on some buildings.

How fire spread is controlled where FRT plywood was or is not used

Alternative products to using FRT plywood as roof sheathing for the roof section covering the area of abutment of multiple living units have included

Where these products and designs were used FRT plywood may have not been required.

Premature Degradation of Fire-Retardant-Treated (FRT) Plywood Used in Roof Decks

The following is adapted with permission from an original Fire-Retardant-Treated (FRT) Plywood article in Professional Roofing by Tom Bollnow, Professional Roofing, May 1999 p.62.

Q: Have there been any significant efforts made to eliminate premature degradation of fire-retardant-treated (FRT) plywood used as roof decks?

A. During the late 1980s, there was an outbreak of structural roof deck failures directly related to degradation of FRT plywood used as roof sheathing.

Because the potential for FRT ply- wood degradation still exists, roofing professionals should be knowledgeable about FRT plywood properties so the likelihood of degradation occurring can be reduced.

FRT plywood is produced by pressure treating plywood with fire retardant chemicals. During the mid 1980s, the search for lower hygroscopic (i.e., less moisture-absorbing) chemical compounds to treat plywood resulted in a change from ammonium sulfates that cause fastener corrosion to ammonium phosphate salts.

Ammonium phosphate salts with additional treatments using buffers, such as Borax, and organic and less acidic chemicals were developed to decrease fastener corrosion and raise the threshold temperatures of fire-retardant materials.

FRT plywood's structural strength changes from 10 percent to 20 percent after an initial pressure treatment procedure.

The drying process follows the pressure treatment procedure and is critical to achieving maximum product performance. Problems result if the kiln drying process is accelerated. Air drying causes fewer problems, but it is more time-consuming.

Products should be marked "KDAT" if kiln dried after treatment or "ADAT" if air dried after treatment.

3 Categories of Fire Retardant Treated Plywood

FRT plywood treatments are divided into three categories: Exterior, Interior Type A and Interior Type B.

A roof deck typically will be interior Type A because it is not exposed directly to outside elements.

Type B treatments can cause excessive moisture to accumulate in wood, allowing chemicals to react with steel fasteners and connectors.

Building code authorities, such as the Building Officials and Code Administrators (BOCA) International Inc., have specific requirements for treatment processes and labeling.

For example, plywood must be manufactured according to American Wood Preservers Association (AWPA) standards, and the treatment process must be evaluated by BOCA Evaluation Services, National Evaluation Services or an AWPA-approved, independent agency.

Fire Retardant Treated Plywood Identifying Labels

In addition, each plywood piece must be labeled properly with its performance rating and design-strength adjustment values. FRT plywood must be used according to manufacturers' recommendations. It must be kept dry and used strictly within the parameters of design-load values.

Below left: fire retardant plywood identifying stamp. [Click to enlarge any image]

Fire retardant plywood identifying stamp © Daniel Friedman at InspectApedia.com

How Fire Retardant Treated Plywood Works

Open flames' elevated temperatures activate fire-retardant chemicals that produce. low-level acids (i.e., acid hydrolysis) in FRT plywood.

The acids lower the temperature at which thermal degradation occurs, increase the amount of surface char and reduce the production of flammable volatiles (i.e., by-product gases that contribute to flame spread).

The results are a reduction of the flame spread across a surface and capacity to support combustion. When a flame is removed from FRT plywood's surface, the plywood will char but not burst into flames.

Chemicals that produce low-level acids causing fire-retardant effects also cause premature FRT plywood degradation at lower temperatures. Untreated plywood experiences no major problems at temperatures up to 200 F (93 Q. Roofing professionals should note that achieving fire retardancy at the expense of structural integrity is not desirable.

Acid hydrolysis and degradation can occur at lower elevated temperatures of about 130 F (54 C to 180 F (82 Q. Temperatures at the interface surface between a roof covering and deck can reach 200 F (93 X with 150 F (66 C commonly found.

As a result, degradation can occur at temperatures that are below open flame temperatures.

Construction Alternatives Can Eliminate the Need for FRT Plywood

Roofing professionals should note that there are construction alternatives available that can eliminate the use of FRT plywood. But local codes (e.g., fire, building) first must be referenced to be sure the alternative construction is in compliance.

These options include fully sprinkled interior systems; noncombustible decks; %-inch- (16-mm-) thick water- and fire-resistant gypsum board beneath untreated plywood; and fire walls that extend through a roof system on a multi tenant building (e.g., an apartment complex).

Factors Reducing the Deterioration of FRT Plywood

If FRT plywood is installed new or encountered during a recover situation, the use of light-colored shingles, a radiant-reflecting roof covering (e.g., white single-ply) or improved ventilation may diminish potential degradation.

These materials may lower temperatures at a roof deck's surface. Roofing professionals should use caution and precise documentation when confronted with FRT plywood roof decks to avoid repercussions if failures occur.

-- Original Source: Page 62 Professional Roofing May 1999. Photograph, adaptation, edits and additions by Daniel Friedman.

Current Uses of Fire-Retardant-Treated (FRT) Plywood

Fire resistant treated plywood prevented fire spread © Daniel Friedman at InspectApedia.com

Fire retardant treated FRT plywood, while it is still a combustible material, has been chemically treated to provide a lower flame-spread rate than un-treated plywood used in building construction.

Our second photo of a contained spread of fire (left) illustrates the object of using this fire resistant roof sheathing.

The plywood industry states that the flame-spread rate of FRT plywood is at least as low as gypsum wallboard (although without specifying which fire-rated wallboard was used for comparison).

Current Definition of FRT Plywood

In the Uniform Building Code, Fire-Retardant-Treated Wood is defined as

any wood product impregnated with chemicals by a pressure process or other means during manufacture, and which, when tested in accordance with UBC Standard 8-1 for a period of 30 minutes, shall have a flame spread of not over 25 and show no evidence of progressive combustion

Identification of and Current Applications of Modern FRT Plywood

In a "how to" article on equipment room fire safety design discussing FRT plywood backer boards for electrical panels, thanks to engineer Ronald Belleza de los Santos, datacom provides this FRT identification detail:

A Fire-Retardant-Treated backboard will be designated with a fire-rated stamp “branded” or “stamped” along the edge or center of the plywood—“UL FR-S Plywood 1780 R-7003.” Marine-grade plywood does NOT qualify even though it is saline “treated”—as it will have a different UL number.

Fire resistant or fireproof buildings and FRT wood use

According to the APA, and in accordance with the International Building Code (IBC), noncombustible buildings Types I and II (usually built of steel and concrete), allow fire-retardant-treated plywood and heavy timber construction in limited uses.

In buildings type IIIA and IV (less fire resistant than Types I and II), interior walls, floors, and roofs may be built of conventional, untreated wood. Non-combustible exterior walls (required for building types IIIA and IV) are required however. The IBC permits FRT wood for these exterior walls as a design option.

Conventional Wood Frame Buildings and FRT wood use

IBC building type V (conventional wood frame buildings) have the lowest fire resistance and are the least costly to construct. Type V buildings may be constructed using conventional un-treated wood throughout the structure. However the sue of fire sprinkler systems, fire spacings (set-backs), and fire-resistant-rated walls, floors, and roofs, are required to obtain larger interior spaces.

American Plywood Association Information about Fire Retardant Treated FRT Plywood

For a detailed, industry-provided and current description of Fire Retardant Treated FRT Plywood, see Fire-Retardant-Treated (FRT) Plywood, American Plywood Association (APA), representing the engineered wood industry, publication NO. K320, January 2009.

This document includes the types of construction where FRT plywood is used, specifies the proper type of fasteners used for FRT plywood, describes the burn-through resistance and design capacities of FRT wood, provides the FRT plywood treating process and test standards, outlines code-approved applications for FRT Plywood, and explains how to identify fire-retardant treated plywood. -- thanks to Arlene Puentes for assistance with this material.

Reader Question: when were building fire walls first required in homes?

My house was built with no wall separation ( firewall) in the attic! When did the Victorians start to use them? The sash windows upstairs has two bars up and down making six panes of glass in all but four downstairs! Chimney pots are yellow with one bar top and bottom. I would be much grateful for any help dating the house! - A.C. 6/29/14

Reply:

Firewalls are a modern building safety feature used in multiple occupancy dwellings.
E.g. see historical citations given in the references below.

Fire Retardant Plywood History, Research, Failures

...


Continue reading at FIRE RATINGS for ROOF SURFACES or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see WOOD ROOF COATINGS & FIRE RATINGS

Or see ARTICLE INDEX to BUILDING FIRE SAFETY

Or see ROOF VENTILATION, FIRE RESISTANT

Or see these

Building Sheathing & Lumber Articles

Suggested citation for this web page

FIRE RETARDANT PLYWOOD at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING STRUCTURES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman