Mobile ViewBUILDING SAFETY HAZARDS GUIDE PLUMBING SYSTEM INSPECT DIAGNOSE REPAIR SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR AEROBIC SEPTIC SYSTEMS ALTERNATING BED SEPTIC SYSTEMS BACKUP PREVENTION, SEWER LINE BIOLOGICAL POLLUTANTS CESSPOOLS CESSPOOL SAFETY WARNINGS CHECK VALVES, WATER SUPPLY CHEMICALS & TREATMENTS for SEPTICS CHLORINE IN DRINKING WATER CISTERNS CLOGGED DRAIN DIAGNOSIS & REPAIR FIRST SIGNS of DRAIN CLOGGING DRAIN vs SEPTIC BLOCKED DRAIN? BLOCKED DRAIN REPAIR METHODS Plumbing Trap Clog Repair Drain Cleaner Chemicals Toilet Plunger Method Plumbing Snake Drain De-Clog Kinetic Water Ram™ Opens Drains DRAIN DRAINFIELD DIAGNOSTIC TABLE BLOCKED DRAIN REPAIR METHODS PLUMBING DRAIN NOISE DIAGNOSIS PLUMBING DRAIN NOISE REPAIR DEFINITIONS OF SEPTIC SYSTEM TERMS DIFFICULT SEPTIC SITES DISTRIBUTION-BOX INSPECTION, SEPTIC DRAINFIELD FAILURE DIAGNOSIS DRIVING or PARKING OVER SEPTIC COMPONENTS? DRYWELL DESIGN & USES FILTERS SEPTIC & GREYWATER FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP FLOODED SEPTIC SYSTEMS, REPAIR GARBAGE DISPOSAL vs SEPTICS GRAVELLESS SEPTIC SYSTEMS GRAVITY/SIPHON DOSING SYSTEMS GREYWATER SYSTEMS HOME BUYERS GUIDE to SEPTIC SYSTEMS HOME SELLERS GUIDE TO SEPTIC INSPECT LAGOON SEPTIC SYSTEMS LEACHFIELD FAILURE DIAGNOSIS MEDIA FILTER SEPTIC SYSTEMS MOUND SEPTIC SYSTEMS ODORS GASES SMELLS, DIAGNOSIS & CURE ODOR DIAGNOSIS CHECKLIST ODORLESS CHEMICALS / GASES: CHECK FOR? ODORS, PLUMBING SYSTEM ODORS, SEPTIC or SEWER ODORS, SULPHUR SMELL SOURCES OUTHOUSES & LATRINES PLANTS & TREES OVER SEPTIC SYSTEMS PRESSURE DOSING SEPTIC SYSTEMS RAISED BED SEPTIC SYSTEMS SAND BED SEPTIC SYSTEMS SEEPAGE PITS SEPTIC & CESSPOOL SAFETY SEPTIC AUTHORITIES, DESIGN REGS SEPTIC BACKUP PREVENTION SEPTIC BACKUPS During Heavy System Use SEWER BACKUP PREVENTION SEPTIC BACKUP REPAIR SEPTIC BOOK, ONLINE SEPTIC BOOKSTORE SEPTIC BIOMATS SEPTIC CLEARANCE DISTANCES SEPTIC CODES & REFERENCES SEPTIC CONSULTANTS SEPTIC DRAINFIELD FAILURE DIAGNOSIS SEPTIC DRAINFIELD INSPECTION & TEST SEPTIC DRAINFIELD LIFE SEPTIC DRAINFIELD LOCATION SEPTIC DRAINFIELD RESTORERS? SEPTIC DRAWINGS SEPTIC DYE TEST PROCEDURE SEPTIC FAILURE LAWSUIT SEPTIC FAILURE SIGNS SEPTIC FIELD INSPECTION SEPTIC FILTERS SEPTIC FLOOD RESPONSE SEPTIC HOLDING TANKS SEPTIC INSPECTION & TEST GUIDE SEPTIC SYSTEM INSPECTION CLASS SEPTIC LIFE EXPECTANCY SEPTIC LIFE MAXIMIZING STEPS SEPTIC METHANE GAS SEPTIC ODORS SEPTIC PUMPS SEPTIC PUMPING REPAIR SEPTIC REFERENCES SEPTIC & CESSPOOL SAFETY SEPTIC SUPPLIES & PARTS SEPTIC SYSTEM DEFINITIONS SEPTIC SYSTEM DESIGN ALTERNATIVES SEPTIC SYSTEM DESIGN BASICS SEPTIC SYSTEM DESIGN MANUAL - Online SEPTIC SYSTEMS, HOME BUYERS GUIDE to SEPTIC SYSTEM INSPECTION & TEST GUIDE SEPTIC SYSTEMS ONLINE BOOK SEPTIC SYSTEM ODORS SEPTIC SYSTEM SAFETY WARNINGS SEPTIC SYSTEM TYPES, MASTER LIST SEPTIC TANKS SEPTIC TANK BAFFLES SEPTIC TANK COVERS SEPTIC TANK, HOW TO FIND SEPTIC TANK GRASS or SNOWMELT SEPTIC TANK INSPECTION PROCEDURE SEPTIC TANK PUMPING PROCEDURE SEPTIC TANK PUMPING SCHEDULE SEPTIC TANK SAFETY SEPTIC TANK SIZE SEPTIC TANK TEES SEPTIC TESTS: DYE & LOADING TESTS SEPTIC TREATMENTS & CHEMICALS SEWAGE & SEPTIC CONTAMINANTS SEWAGE BACKUP, WHAT TO DO SEWAGE BACKUP TEST & CLEANUP SEWAGE BACKUP PREVENTION SEWAGE CONTAMINATION in BUILDINGS SEWAGE CONTAMINANTS in FRUIT / VEGETABLES SEWAGE EJECTOR / GRINDER PUMPS SEWAGE NITROGEN CONTAMINANTS NITROGEN CONTAMINATION NITROGEN REFERENCES SEWAGE PATHOGENS in SEPTIC SLUDGE Components Entering a Septic Tank Components of Raw Sewage Components of Septic Tank Effluent Settled septic tank sludge Floating septic tank scum Gases in the septic tank SEWAGE PUMPS SEWAGE PUMP CLOG DAMAGE SEWER BACKUP PREVENTION SEWER GAS ODORS SEWER LINE REPLACEMENT SMELL PATCH TEST to Track Down Odors SULPHUR & SEWER GAS SMELL SOURCES SINKHOLES, WARNING SIGNS SOAKAWAY BED FAILURE DIAGNOSIS TOILETS, INSPECT, INSTALL, REPAIR TOILET ALTERNATIVES TOILET REPAIR GUIDE TOILET TYPES Toilet Types, Flush Methods TOILETS, DON'T FLUSH LIST TRAPS on PLUMBING FIXTURES TREATMENTS & CHEMICALS, SEPTIC VIDEO GUIDES: Septic Videos WASHING MACHINES & SEPTIC SYSTEMS WATER SOFTENERS & CONDITIONERS WATER SUPPLY & DRAIN PIPING CLOGGED DRAIN DIAGNOSIS & REPAIR FIRST SIGNS of DRAIN CLOGGING DRAIN vs SEPTIC BLOCKED DRAIN? BLOCKED DRAIN REPAIR METHODS DRAIN DRAINFIELD DIAGNOSTIC TABLE BLOCKED DRAIN REPAIR METHODS PLUMBING DRAIN NOISE DIAGNOSIS PLUMBING DRAIN NOISE REPAIR WASTEWATER TREATMENT BASICS WATER, WELLS, WATER TANKS: TESTING GUIDE WATER PURIFIERS WATER QUALITY TESTS, CONTAMINANTS, TREATMENT WATER QUANTITY IMPROVEMENT WATER QUANTITY USAGE GUIDE WATER, WELLS, WATER TANKS: TESTING GUIDE WETLAND SEPTIC SYSTEMS WINTERIZE A BUILDING More Information |
This article explains how to deal with and test for sewage backup contamination, sewage contamination testing, inspection, and cleanup- remediation in residential and commercial buildings. If you have had sewage back up and spill out of toilets into the building, cleanup is needed and you may face bacterial hazards. InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.If you have had a sewage backup or burst house drain pipe in your building this document offers some advice on how to test for sewage contamination, bacterial and viral hazards, and links to sewage spill cleanup and bacterial hazard information regarding sewage and septic spill contamination. We explain why and how testing for sewage contamination is performed and we discuss the urgency of proper cleanup following a sewage backup or spill in a building. At SEWAGE & SEPTIC CONTAMINANTS we list the pathogens and contaminants commonly found in sewage and in sewage backup waters. In this article series we explain the causes of sewer or septic backups into buildings, the health hazards, testing, and cleanup of sewage backups, and the cure or prevention of future sewage or septic backup problems. If your building has had a septic or sewage system backup into the structure see SEWAGE BACKUP, WHAT TO DO and also see SEWAGE BACKUP PREVENTION. At SEWAGE BACKUP TEST & CLEANUP we discuss how to test for bacterial or other pathogens in a building - tests that may be useful after a sewage spill cleanup in order to assure that the building is acceptably clean. The photo above shows what dirt and sewage sludge may look like in a basement after a sewer line backup. See BLOCKED DRAIN REPAIR METHODS to try clearing your blocked drain before going to more drastic measures. © Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website. Testing For Bacterial Contamination and Cleaning Up Sewage Backups in Buildings
The photo at left shows evidence of raw sewage overflow in the crawl space under a home. Although a new waste line was installed (the white pipe at the top of the photograph) no cleanup has been performed. Both a one-time event and recurrent sewage leaks into a building would be a concern, particularly if prompt and competent cleaning were not performed. If recurrent sewage contamination has occurred more extensive building cleaning and treatment are likely to be required. One reason that experts recommend very prompt treatment following a sewage backup in a building is the wish to avoid transmission of bacterial contamination to other building areas. Examples of sewage bacteria and virus transmission might be by movement of people from contaminated areas to other building areas (tracking contaminated soil), and air movement of aerosolized particles or contaminated dust through the building by natural convection, heating and air conditioning equipment, or other sources of air and dust movement. Testing for Sewage or Septic ContaminationWhile sewage may contain many pathogens harmful to building occupants, testing for this problem usually focuses on indicator organisms including total coliform, fecal coliform, Escherichia coli (E. coli), and Enterococcus as these species are expected in human sewage waste. They are potentially harmful themselves as well as serving as an indicator of sewage contamination. Typical sampling methods to test for sewage contamination in buildings include use of sterile swabs on sample surfaces both in the suspected area and as a control in other building areas where low or no contamination is expected. Bulk samples of debris or building materials may also be collected, such as drywall suspected of having been wet with a sewage backup. Samples are sent to a qualified laboratory for culture and examination for these bacteria. Since there are a variety of tests for bacteria and for possible sewage contamination, specification of the definitive lab test for sewage contamination is important where health concerns are at stake. Be sure to review the test choices with your laboratory before ordering a specific test as test accuracy and cost vary widely. Questions & Answers regarding this articleQuestions & answers about testing for sewage contamination in buildings Ask a Question or Search InspectAPediaHTML Comment Box is loading comments...
Recommend / Share this Article
... Technical Reviewers & References
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
Septic & Sewage Pathogens and Contaminants, References & Research Articles
|