InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US




Mobile View
MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT

AIR CLEANER PURIFIER TYPES
AIR FILTERS for HVAC SYSTEMS
AIR POLLUTANTS, COMMON INDOOR
AIR QUALITY IMPROVEMENT STRATEGIES
ALLERGEN TESTS for BUILDINGS
ANIMAL ALLERGENS / PET DANDER
ANIMAL ODORS IN BUILDINGSS
ATTORNEYS and EXPERT WITNESSES

BASEMENT MOLD
BATHROOM MOLD
BIBLIOGAPHY ENVIRONMENTAL HEALTH, MOLD, IAQ
BIOLOGICAL POLLUTANTS

CAR MOLD CONTAMINATION
CARPET DUST IDENTIFICATION
CARPET MOLD CONTAMINATION
CAT DANDER in BUILDINGS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATION or SWEATING PIPES, TANKS
CPSC Indoor Air Pollution Book Online Copy

DUCT SYSTEM & DUCT DEFECTS

EMERGENCY RESPONSE, IAQ, GAS, MOLD

FIBERGLASS HAZARDS
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN BUILDINGS-mold
FORMALDEHYDE HAZARDS

GAS EXPOSURE EFFECTS, TOXIC

HUMIDITY CONTROL & TARGETS INDOORS
HOUSE DUST ANALYSIS

INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSULATION MOLD

MILDEW REMOVAL & PREVENTION
MOISTURE CONTROL in BUILDINGS
MOLD GROWTH on SURFACES, TABLE OF
MYCOPHOBIA, STAINS MISTAKEN for MOLD

NOISE / SOUND DIAGNOSIS & CURE

ODORS GASES SMELLS, DIAGNOSIS & CURES
OZONE HAZARDS
OZONE for MOLD OR ODORS

RADON HAZARD TESTS & MITIGATION

SAFETY HAZARDS GUIDE
SICK HOUSE IAQ QUESTIONNAIRE
SMELL PATCH TEST to Track Down Odors
STAIN DIAGNOSIS on BUILDING INTERIORS

VENTILATION in BUILDINGS

More Information

Apartment buildings may look crisp outside but individual rental apartments may be discovered by their tenants to have suffered leak damage and extensive hidden mold - here we give some basic advice Health Risks to Tenants in Moldy in Rental Homes, Apartments, Offices
     

  • Possible health risks to tenants in moldy apartments, homes, or offices, How to handle mold health risk & safety concerns in rental property, apartments, rental homes, offices, Mold exposure health risk advice for rental tenants, Mold healt risk to tenants - advice for landlords, When do potential health risks & management inaction suggest that you call your health department about a moldy apartment?
  • RENTERS & TENANTS: MOLD ADVICE - home
    • Possible Mold Causes
    • Action Advice for Tenants
    • Rental Apartment Mold Safety Advice
    • Health Risk for Tenants
    • Possible Hidden Mold
    • Building Manager's Guide to Mold
    • What Can Tenant Do
    • Health Department Assistance
  • Questions & answers about heath risks in moldy apartments, offices, rental spaces
  • References

Click to Show or Hide Related Topics

  • MOLD: A COMPLETE GUIDE - home
  • ACCEPTABLE MOLD LEVEL
  • ACCURACY OF VARIOUS MOLD TEST METHODS
  • ACTION GUIDE - WHAT TO DO ABOUT INDOOR MOLD
  • AIR TEST FOR MOLD: ACCURACY
  • CARPET MOLD CONTAMINATION
  • CRAWLSPACE MOLD ADVICE
  • DISASTERS: BUILDING INSPECTION & REPAIR - home
  • DRYWALL MOLD
  • DUST SAMPLING PROCEDURE
  • EMERGENCY RESPONSE, IAQ, GAS, MOLD
  • HIDDEN MOLD, HOW TO FIND
  • INDOOR AIR QUALITY IMPROVEMENT GUIDE
  • INSULATION MOLD
  • MILDEW in BUILDINGS ?
  • MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
  • MOLD AGE - Old is the Mold?
  • MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
  • MOLD APPEARANCE on VARIOUS SURFACES
  • MOLD APPEARANCE - STUFF THAT IS NOT MOLD
  • MOLD CLEANERS - WHAT TO USE
  • MOLD CLEANUP, DO IT YOURSELF
  • MOLD CLEANUP GUIDE to GET RID OF MOLD
  • MOLD CLEARANCE INSPECTIONS
  • MOLD EXPERT, WHEN TO HIRE
  • MOLD EXPOSURE STANDARDS
  • MOLD PRODUCTS, INEFFECTIVE
  • MOLD RELATED ILLNESS SYMPTOMS
  • MOLD SPRAYS, SEALANTS, PAINTS
  • MOLD TEST vs. PROBLEM DIAGNOSIS
  • MOLD TEST KITS
  • MOLD TEST METHOD ACCURACY
  • MOLD TEST REASONS
  • MOLD TESTING METHOD VALIDITY
  • MOLD TESTING SERVICES
  • MVOCs & MOLDY MUSTY ODORS
  • MYCOTOXIN EFFECTS of MOLD EXPOSURE
  • OZONE for MOLD OR ODORS
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

This document discusses possible mold-related health risks in moldy apartments or rental homes. We note that certain individals may be at much higher risk of serious health consequences when exposed to toxic or allergenic molds, increasing the health risk to those individuals and the liability risks for landlords.

An easy-to-print PDF version of this article is here.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Health Risks for Tenants in Rental Apartments - Compromised immune system increases vulnerability to mold-related illness

The fact that a building occupant's immune system is compromised places that person at extra risk and means that s/he and the contents of their apartment need to be protected carefully.

People at extra risk of health problems if exposed to moldy dust and demolition debris include elderly, infants, immune-compromised, asthmatics, people suffering from COPD or other respiratory illness, and possibly others.

While chronic exposure to high levels of toxic or allergenic mold can make even some healthy people become sensitized as well, the people I just listed should be particularly careful about exposure.

This article continues by discussing the risk of hidden mold reservoirs. Don't assume that the mold you see is the only, or even the most important problem in your rental space.


Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Use the search box below to ask a question or to search the InspectApedia.com website.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • Should you See a Doctor for Mold Symptom Treatment?
  • Mold Related Illness: Index of Symptoms

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • Environmental Health & Investigation Bibliography - our technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • Adkins and Adkins Dictionary of Roman Religion discusses Robigus, the Roman god of crop protection and the legendary progenitor of wheat rust fungus.
  • Kansas State University, department of plant pathology, extension plant pathology web page on wheat rust fungus: see http://www.oznet.ksu.edu/path-ext/factSheets/Wheat/Wheat%20Leaf%20Rust.asp
  • "A Brief Guide to Mold, Moisture, and Your Home", U.S. Environmental Protection Agency US EPA - includes basic advice for building owners, occupants, and mold cleanup operations. See http://www.epa.gov/mold/moldguide.htm
  • US EPA - Mold Remediation in Schools and Commercial Building [Copy on file at /sickhouse/EPA_Mold_Remediation_in_Schools.pdf ] - US EPA
  • US EPA - Una Breva Guia a Moho - Hongo [Copy on file as /sickhouse/EPA_Moho_Guia_sp.pdf - en Espanol

Allergies, Allergens, Allergy Testing in Buildings - References & Products

  • Air Conditioning System Blower Fans & Filters Cascading for Optimum Indoor Air Quality
  • Allergen Tests in Buildings advice about how to test, what to look for, in evaluating the level of dog, cat, or other animal allergens in a building
  • "IgG Food Allergy Testing by ELISA/EIA, What do they really tell us?" Sheryl B. Miller, MT (ASCP), PhD, Clinical Laboratory Director, Bastyr University Natural Health Clinic - ELISA testing accuracy: Here is an example of Miller's critique of ELISA http://www.betterhealthusa.com/public/282.cfm - Townsend Letter for Doctors and Patients
    The critique included in that article raises compelling questions about IgG testing assays, which prompts our interest in actually screening for the presence of high levels of particles that could carry allergens - dog dander or cat dander in the case at hand.
    http://www.tldp.com/issue/174/IgG%20Food%20Allergy.html contains similar criticism in another venue but interestingly by the same author, Sheryl Miller. Sheryl Miller, MT (ASCP), PhD, is an Immunologist and Associate Professor of Basic and Medical Sciences at Bastyr University in Bothell, Washington. She is also the Laboratory Director of the Bastyr Natural Health Clinic Laboratory.
  • Allergens: Testing for the level of exposure to animal allergens is discussed at http://www.animalhealthchannel.com/animalallergy/diagnosis.shtml (lab animal exposure study is interesting because it involves a higher exposure level in some cases
  • Allergens: WebMD discusses allergy tests for humans at webmd.com/allergies/allergy-tests
  • Animal Allergens: Dog, Cat, and Other Animal Dander - Cleanup & Prevention Information for Asthmatics and regarding Indoor Air Quality.
  • Atlas of Mold Related Illness Symptoms & Complaints - long list of both documented, studied mold related illness, and complaints ascribed to mold contamination or allergens in buildings
  • Cat Dander: how to inspect and test a building for past or current presence of cats, cat hair, cat dander, and cat allergens
  • Clinical Atlas of Mold Toxicity - An Online Description of Toxic, Pathogenic, Allergenic Fungi, Fungal Diseases
  • Fiberglass Insulation Contains Mold© 2005 comments about a field study in process, & more about health hazards from fiberglass insulation
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • Mold Action Guide detailed guide on finding, removing, and preventing indoor mold contamination
  • Odors, Odor Detection, Smells, & Gases how to find and identify sources of noxious or toxic odors and gases
  • Other environmental risks, Our much longer list: Asbestos, carbon monoxide, electromagnetic fields, etc.
  • Ozone: The Use of Ozone Indoors for Control of Odors and Mold Removal in Buildings: A Summary of Hazards and False Claims.
  • Pollen Allergens: identification, plant pollen and indoor air quality
  • Products to Reduce Mold & Allergy Problems to reduce indoor mold or allergen levels: air cleaners, air purifiers, dust mite covers, vacuum cleaners, crawl space vents
  • Recognizing Allergens: What various indoor allergens look like - identification photos to help identify pollen, dust mites, animal dander, toxic or allergenic mold - Common Mold and other Allergens, Irritants, Remedies & Advice
  • Rodent control issues, including dander, fecal, and urine contamination of Buildings and Building insulation are discussed at our
  • Sewage and Septic backup contamination in Buildings: inspection, testing, remediation, & references to expert sources
  • Action Guide: What to do about mold, mildew, and other indoor allergens
  • ...

Mold Contamination Testing, Cleanup, Prevention: references & products

  • GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminantsThe Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
  • Aerobiology, Building Science, Microscopy, & Laboratory References, an extensive technical bibliography
  • Allergens: what they look like in buildings
  • Associations: Sick House, Sick Building, SBS - Air Quality, Government, Private Associations and Information Resources
  • Atlas of Clinical Fungi, 2nd Ed., GS deHoog, J Guarro, J Gene, & MJ Figueras, Centraalbureau voor Schimmelcultures, Universitat Rovira I Virgili, 2000, ISBN 90-70351-43-9 (you can buy this book at Amazon) - The Atlas of Clinical Fungi is also available on CD ROM
  • Atlas of Mold Related Illness: Index of Symptoms and health, physical, neurological, psychological, and other complaint which people suspect may be mold or building-related.
  • Atlas of Indoor Mold, Online Clinical Mold Atlas, Toxins, Pathogens, Allergens and Other Indoor Particles - Medical Health Effects of Mold (separate online document)
  • Black Mold that is Harmless Photos of recognizable, usually harmless black mold on wood, bluestain, ceratocystis, ophistoma
  • Building Floods: quick steps after a building flood or plumbing leak can prevent costly mold contamination
  • Classes of Mold: what types of cosmetic, allergenic, or toxic mold are a problem? Can mold be cleaned-up successfully?
  • Clinical Mold References - Detailed bibliography of mold reference texts
  • "A Brief Guide to Mold, Moisture, and Your Home", U.S. Environmental Protection Agency US EPA - includes basic advice for building owners, occupants, and mold cleanup operations. See http://www.epa.gov/mold/moldguide.htm
  • "Disease Prevention Program for Certain Vegetable Crops," David B. Langston, Jr., Extension Plant Pathologist - Vegetables, University of Georgia (PDF document) original source: www.reeis.usda.gov/web/crisprojectpages/209797.html
  • "Disease Prevention in Home Vegetable Gardens," Patricia Donald, Department of Plant Microbiology and Pathology, Lewis Jett
    Department of Horticulture, University of Missouri Extension - extension.missouri.edu/publications/DisplayPub.aspx?P=G6202
  • "Management of Powdery Mildew, Leveillula taurica, in Greenhouse Peppers," Ministry of Agriculture and Lands, British Columbia - Original source: www.agf.gov.bc.ca/cropprot/peppermildew.htm
  • Environmental Health & Investigation Bibliography - our own technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • Fiberglass: Mold in Fiberglass Insulation© 2005 comments about a field study in process, & more about health hazards from fiberglass insulation - DJF
  • Fifth Kingdom, Bryce Kendrick, ISBN13: 9781585100224, is available from the InspectAPedia online bookstore - we recommend the CD-ROM version of this book. This 3rd/edition is a compact but comprehensive encyclopedia of all things mycological. Every aspect of the fungi, from aflatoxin to zppspores, with an accessible blend of verve and wit. The 24 chapters are filled with up-to-date information of classification, yeast, lichens, spore dispersal, allergies, ecology, genetics, plant pathology, predatory fungi, biological control, mutualistic symbioses with animals and plants, fungi as food, food spoilage and mycotoxins.
  • Fungi, Identifying Filamentous, A Clinical Laboratory Handbook, Guy St-Germain, Richard Summerbell, Star Publishing, 1996, ISBN 0-89863-177-7 (English) (buy at Amazon)
  • Looking for Mold Procedure: what mold is often found where in buildings - simple technical presentation
  • Meruliporia: the house eating fungus or "poria"
  • Mold Action Guide: Step-by-Step Instructions, What to do about mold, mildew, and other indoor allergens
  • MOLD APPEARANCE - WHAT MOLD LOOKS LIKE Photos of what mold looks like in buildings
  • MOLD APPEARANCE - STUFF THAT IS NOT MOLD Photos of NOT-mold material that is sometimes mistaken for mold
  • MOLD ATLAS & PARTICLES INDEX, Pathogens, Allergens and Other Indoor Particles - Medical Health Effects of Mold (separate online document)
  • MOLD BY MICROSCOPE Mold under the microscope - photo identification of the most common indoor molds found in buildings
  • Mold FAQs Answers to Most Questions about Indoor Mold, Mold Related Illness, Mold Cleanup, Mold Prevention
  • US EPA: Mold Remediation in Schools and Commercial Building [Copy on file at /sickhouse/EPA_Mold_Remediation_in_Schools.pdf ] - US EPA
  • Mold spores in the Home - a Photo ID Library for detection and identification of mold allergens
  • Mold Test Kits - How to Collect and Send Your Own Mold Sample to our mold testing lab or to any mold lab you wish
  • Most Common Indoor Molds Found in Buildings, A Table of
  • Mycology, Fundamentals of Diagnostic, Fran Fisher, Norma B. Cook, W.B. Saunders Co. 1998, ISBN 0-7216-5006-6 (buy this book at Amazon)
  • Ozone Warnings - Use of Ozone as a "mold" remedy is ineffective and may be dangerous.
  • Rot concerns in buildings-some building mold such as Meruliporia incrassata "Poria" risks serious rot and hidden structural damage
  • US EPA: Una Breva Guia a Moho - Hongo [Copy on file as /sickhouse/EPA_Moho_Guia_sp.pdf - en Espanol