Mobile ViewENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY AIR CLEANER PURIFIER TYPES AIR FILTER EFFECTIVENESS AIR FILTERS, FIBERGLASS PARTICLES AIR FILTERS for HVAC SYSTEMS AIR HANDLER / BLOWER UNITS AIR LEAK DETECTION TOOLS AIR POLLUTANTS, COMMON INDOOR Air Quality Improvement Strategies AIR LEAK SEALING PROCEDURE AIR SEALING STRATEGIES ALLERGEN TESTS for BUILDINGS ALLERGY TESTS for PEOPLE ANIMAL ALLERGENS / PET DANDER ANIMAL ODORS IN BUILDINGS ASBESTOS-FREE INSULATION MATERIALS ASBESTOS IDENTIFICATION IN BUILDINGS ATTORNEYS and EXPERT WITNESSES BACKDRAFTING HEATING EQUIPMENT BASEMENT MOLD BATHROOM MOLD BIBLIOGAPHY ENVIRONMENTAL HEALTH, MOLD, IAQ BIOGAS PRODUCTION & USE BIOLOGICAL POLLUTANTS BLOWER DOORS & AIR INFILTRATION BLOWER FAN OPERATION & TESTING BOOKSTORE - ENVIRONMENTAL BUILDING SAFETY HAZARDS GUIDE CACTUS FUNGI / MOLD CAR MOLD CONTAMINATION CARPET DUST IDENTIFICATION CARPET MOLD CONTAMINATION CARPETING & INDOOR AIR QUALITY CAT DANDER in BUILDINGS CHIMNEY INSPECTION DIAGNOSIS REPAIR CHINESE DRYWALL HAZARDS COMBUSTION PRODUCTS & IAQ COMBUSTION GASES & PARTICLE HAZARDS CRAWL SPACES CRAWLSPACE MOLD ADVICE CPSC Indoor Air Pollution Book Online Copy DUCT SYSTEM & DUCT DEFECTS FIBERGLASS DUCT, RIGID CONSTRUCTION FIBERGLASS HVAC DUCTS DUST ANALYSIS for FIBERGLASS DUST CONTAMINATION FROM HVAC? DUST SAMPLING PROCEDURE EMF RF FIELD & FREQUENCY DEFINITIONS EMERGENCY RESPONSE, IAQ, GAS, MOLD EMF ELECTROMAGNETIC FIELDS & HUMAN EXPOSURE ENERGY SAVINGS in buildings Fiberboard Insulation Sheathing Mold FIBERGLASS DUCT, RIGID CONSTRUCTION Fiberglass Enviro-Scare FIBERGLASS HAZARDS Fiberglass Insulation Exposure Limits FIBERGLASS PARTICLE CONTAMINATION TEST Recognizing Fiberglass Insulation Recognizing Fiberglass Duct Insulation Lab Identification of Fiberglass Fiberglass Fragment Hazards Fiberglass Detection in Building Air Mold in Fiberglass Insulation Mold on Books, Book Conservation Mold on Fiberboard Insulating Sheathing References, Fiberglass Hazards Vacuuming exposed insulation FIBERGLASS PARTICLE CONTAMINATION TEST FIBERGLASS INSULATION IDENTIFICATION FIBERGLASS INSULATION MOLD CRAWLSPACE MOLD ADVICE INSPECTION of INSULATION for MOLD TEST CHOICES for MOLD in FIBERGLASS TEST PROCEDURE for MOLD in FIBERGLASS WHEN to TEST INSULATION for MOLD WHY DOES MOLD GROW in INSULATION? FIBERGLASS PARTICLE CONTAMINATION TEST Fireplace Inserts Fireplaces & Woodstove Contaminants FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP FLOODS IN BUILDINGS-mold FLOORING MATERIALS, Age, Types FORMALDEHYDE HAZARDS Formaldehyde Gas Hazard Reduction GAS DETECTION & MEASUREMENT GAS EXPOSURE EFFECTS, TOXIC GAS FIRED WATER HEATERS HVAC Systems HOME HEATING SAFETY HUMIDITY CONTROL & TARGETS INDOORS HOUSE DUST ANALYSIS ICE DAM PREVENTION INDOOR AIR QUALITY & HOUSE TIGHTNESS INDOOR AIR QUALITY IMPROVEMENT GUIDE INSULATION, ASBESTOS INSULATION CHOICES Insulation Air & Heat Leaks INSULATION FACT SHEET- DOE INSULATION IDENTIFICATION GUIDE INSULATION INSPECTION & IMPROVEMENT INSULATION LOCATION - WHERE TO PUT IT INSULATION MOLD Mold in Fiberglass Insulation Mold on Books, Book Conservation Mold on Fiberboard Insulating Sheathing MOLD PREVENTION AFTER FLOODING MOLD RESISTANT CONSTRUCTION Mold in Foam Insulation Moldy insulation may look clean Why does mold grow in fiberglass? When to test insulation for mold How to Test for Mold in Insulation References, Fiberglass Hazards Vacuuming exposed insulation INSULATION MOLD RESISTANCE of FOAM INSULATION, UFFI UREA FORMALDEHYDE FOAM LEED Building Designation & IAQ Legionella Legionnaires' Disease Legionella BACTERIA & HVAC Equipment MILDEW REMOVAL & PREVENTION MOISTURE CONTROL in BUILDINGS MOLD: A COMPLETE GUIDE TO MOLD MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD MOLD APPEARANCE - WHAT MOLD LOOKS LIKE MOLD CLEANERS - WHAT TO USE MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD MOLD CONSULTANTS/INSPECTORS MOLD CULTURE TEST KIT VALIDITY MOLD DETECTION & INSPECTION GUIDE MOLD or INDOOR AIR EMERGENCY RESPONSE MOLD EXPERT, WHEN TO HIRE MOLD FAQ's MOLD ODORS, MUSTY SMELLS MOLD PREVENTION GUIDE MOLD RELATED ILLNESS GUIDE MOLD SAFETY WARNINGS MOLD SPRAYS, SEALANTS, PAINTS MOLD STANDARDS MOLD TEST KITS for DIY MOLD TESTS MOLD TESTING METHOD VALIDITY MSDS Material Safety Data Sheets MVOCs & MOLDY MUSTY ODORS MYCOPHOBIA, STAINS MISTAKEN for MOLD MYCOTOXIN EFFECTS of MOLD EXPOSURE Museum Artifact Preservation Nanomaterials Hazards NOISE / SOUND DIAGNOSIS & CURE ODORS GASES SMELLS, DIAGNOSIS & CURE OIL TANKS INSPECT LEAK TEST ABANDON REGS OZONE HAZARDS OZONE for MOLD OR ODORS PAINTS & COATINGS ODORS IN BUILDINGS PARTICLE SIZES & IAQ Particulates & Allergens Indoors Pesticide Exposure Hazards PET ALLERGEN REMEDIES Pet Dander PLASTIC CONTAINERS, TANKS, TYPES PLASTIC HEATER VENT PLASTIC ODORS-SCREENS, SIDING PLUMBING SYSTEM ODORS Pollen Photos PVC - VINYL BUILDING PRODUCTS RADON HAZARD TESTS & MITIGATION Radon Enviro-Scare ROT, FUNGUS, TERMITES SAFETY HAZARDS GUIDE SAFETY HAZARDS & INSPECTIONS SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR SEWER GAS ODORS SICK HOUSE IAQ QUESTIONNAIRE SIDING VINYL SMELL PATCH TEST to Track Down Odors SOUND CONTROL in BUILDINGS STAIN DIAGNOSIS on BUILDING EXTERIORS STAIN DIAGNOSIS on BUILDING INTERIORS SULPHUR & SEWER GAS SMELL SOURCES THERMAL TRACKING & HEAT LOSS UFFI UREA FORMALDEHYDE FOAM INSULATION URETHANE FOAM Deterioration, Outgassing VAPOR BARRIERS & AIR SEALING at BAND JOISTS VAPOR BARRIERS & CONDENSATION in BUILDINGS VAPOR BARRIERS & HOUSEWRAP VAPOR CONDENSATION & BUILDING SHEATHING VENTILATION in BUILDINGS VINYL CHLORIDE HEALTH INFO VINYL Siding or PLASTIC Window ODORS in buildings Volatile Organic Compounds VOCs WATER ODORS, CAUSE CURE WATER TESTS, CONTAMINANTS, TREATMENT Well Pollution World Trade Center Collapse Dust Photos More Information |
Fiberglass insulation mold contamination test details: this document discusses choices of test methods to screen for toxic or allergenic mold contamination in fiberglass building insulation in residential and light-commercial buildings. Mold is often found in basement fiberglass insulation, crawl space fiberglass insulation, fiberglass wall insulation, heating or cooling duct fiberglass insulation, and attic or roof insulation in buildings which have either been wet or have been exposed to high levels of mold from other sources. InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website. How to Test Building Insulation for Mold Contamination
More details about just how fiberglass mold tests are conducted in the field are found at TEST PROCEDURE for MOLD in FIBERGLASS. This website discusses health hazards associated with moldy fiberglass in buildings, with focus on fiberglass insulation, fiberglass fragments, fiberglass in heating and air conditioning duct work, and invisible but toxic mold growth in fiberglass which has been wet, exposed to high humidity, or exposed to other moldy conditions. Readers of this document on mold hazards in fiberglass insulation should see How to Test for Mold in Insulation and also read INSULATION MOLD on how to locate and test for moldy insulation in buildings, and for a technical discussion of use of vacuum sampling methods for inspecting building insulation, see Vacuuming exposed insulation. To avoid further mold contamination also see MOLD RESISTANT CONSTRUCTION and MOLD PREVENTION AFTER FLOODING. See Attic Moisture or Mold Sources for a discussion of common sources of moisture in attics that can cause moldy insulation, and similarly, see BASEMENT LEAKS, INSPECT FOR for the same problem in basements. Readers ducting cool air through a crawl space should also see CRAWLSPACE MOLD ADVICE. Question: How should we sample fiberglass insulation for mold when investigating a building?
Sometimes I see spots on the insulation and know that there is obvious mold, but I have long suspected (based on smell and moisture readings) that some mold might not be visible to the eye. Is it just that it is in early growth stage so the colonies are too small to see? And again, how do you verify that this is the case – by samples submitted to the lab? I was on the site searching for information on mold in insulated ducts. - Vickie Swenson, CRMI Minnesota Mold Inspection (612) 508-2742 Our photo of clean-looking insulation in a basement ceiling (above left) does not provide evidence that insulation testing was necessary for that building. But a case history of occupant complaints, a wet basement, and previous storage of moldy materials in the basement that had been removed at the time of our inspection led us to test and confirm that this insulation was severely contaminated with Penicillium sp. mold. Answer: Detailed Description of Methods for Testing Building Insulation for Mold
There are several similar ways to test insulation that does not already give visual evidence of a mold problem. Air Sampling Cassettes for Insulation Mold TestWe use an air sampling cassette such as an Air-o-Cel or Allergenco unit with a vacuum pump set to move air at the proper flow rate for the cassette (typically 10 lpm). The sampler is held 1-4 inches away from the insulation and then with the pump running we poke or agitate the suspect insulation to stir a particle release. The sample interval needs to be short - often just 5-20 seconds in duration since otherwise you risk overloading the cassette with fiberglass particles. At ACCURACY OF VARIOUS MOLD TEST METHODS we include photos of particle traces on microscope slides that can help you recognize when a dust sample is overloaded and thus hard to analyze in the lab. Our photo (above left) shows a more complicated version of this test about to start. In this case we were using two air sampling pumps and two different brands of sampling cassettes in order to compare their behavior during dust sampling. In the foreground you can just make out a special timer-switch that we used to turn on and off both pumps simultaneously. If you are in doubt or inexperienced, try making three sample cassettes of 5, 10, and 20 second durations, agitating the insulation about the same degree in each case and keeping about the same distance. The time and distance are not critical as long as we make clear that this is a qualitative test for the presence or absence of high levels of mold or other particles in the insulation, not a quantitative test. Burkard Personal Air Sampler and Prepared Slide for Insulation Mold TestA second method for testing fiberglass insulation that we have used with good results was to run a Burkard personal air sampler with a prepared collection slide mounted in the device for a 15-second interval, holding the sampler one to six inches away from the insulation during agitation of the insulation itself. You can simply use a pencil to poke the insulation during sampling. As with the air sampling cassette approach above, make several test samples at different sampling durations to be sure you have a good sample that is not overloaded. Alternative, low-cost Air Pumps for Building Insulation Mold Testing
Watch out: the airflow rate of portable battery operated pumps such as shown here varies widely from device to device as well as depending on battery condition. For field use in testing insulation, we tested ten low-cost portable pumps in our forensic laboratory, selecting a subset that consistently delivered 10-15 LPM with fresh batteries . Constructing a Clean Test Chamber to Screen Insulation for MoldIn the laboratory, if we receive a bulk sample of suspect insulation, in addition to inspecting the insulation itself in the stereo microscope and high power transmitted light forensic microscope, we sometimes use a third sampling method that is most suitable for a variety of suspect, perhaps dirty and loose materials. We construct a test chamber using a cardboard box lined with a new clean plastic garbage bag. The bag lines the box, the sample is placed into the box, the box is sealed. We cut an opening sufficient to admit or affix our air sampling cassette, then we agitate the box for 30 seconds before pulling a vacuum sample from the box itself. This method also can reduce overloading the sample with fiberglass particles. Quantitative Analysis of Insulation Samples for Mold ContaminationIt is possible to perform quantitative analysis of insulation or other fibrous materials or dust samples for mold contamination using a wash and filter method that collects most particles from the insulation sample into a liquid for further processing and particle counting. We do not agree that the apparent accuracy of this method is real, and we suspect that except for controlled technical studies it is not appropriate.
Therefore a quantitative analysis of mold spores per cubic inch, meter or other volume of fiberglass insulation may be very precise (lots of decimal places) but inaccurate as an estimator of size of the problem mold reservoir. Should All Building Insulation be Tested for Mold?No. We do not recommend testing all insulation for mold. The decision to test insulation for mold needs to be made based on a careful building inspection and case history, including visual evidence of leaks or the presence of exposed fiberglass over an area known to be or have been subject to a large mold contamination problem or a mold remediation project. See WHEN to TEST INSULATION for MOLD Questions & Answers regarding this articleQuestions & answers about methods for testing for the presence of mold contaminants in fiberglass or other building insulation products. Ask a Question or Search InspectAPediaHTML Comment Box is loading comments...
Recommend / Share this Article
... Technical Reviewers & References
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. INSULATION MOLD BASEMENT MOLD includes examples of moldy fiberglass insulation found in basements
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
Fiberglass in buildings: hazards, testing, cleanup, prevention: references & productsFor more information about fiberglass as an indoor air quality concern see:
|