|
|
How to Inspect the Soil Absorption System or Septic Drainfield for Evidence of Septic System Failure - Clogging Failures
|
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
How to spot drainfield clogging failures: this septic system inspecting testing and maintenance article describes septic drainfield (soakaway bed, leach field, drainage trench) clogging failures among the types of septic system failure in the drain field, leach field, seepage bed, or similar component. We list the causes of each type of septic component failure, and list the septic component failure criteria or in other words what conditions are defined as failure?
Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.
DISPOSAL CLOGGING FAILURES - Septic Effluent Disposal and Septic Drainfield Clogging Failures
How can you distinguish between a blocked pipe, a septic tank that
needs pumping, and a clogged drainfield that needs replacement? This is an important question as it distinguishes between relatively
low cost maintenance or repair task and a costly septic leach field replacement.
We also discuss what can be planted over and near a septic drainfield and what should be avoided.
Readers should see DISPOSAL CLOGGING FAILURES, also see SEPTIC DRAINFIELD RESTORERS? where we describe the use of chemicals, treatments, septic tank additives, to try to restore failed or failing sluggish septic drainfields or leaching beds or soakaway beds.
There is an important distinction between septic effluent disposal and septic effluent treatment. Traditionally people figured that if they could flush toilets and use sinks and showers without seeing septic effluent again outside on the ground surface, the septic system was "working fine". Really this describes successful effluent disposal - getting rid of the liquid waste. And when effluent disposal failures occur, people are forced to repair or replace the septic system or drainfield.
Successful septic effluent treatment (as opposed to disposal) means that the effluent being released to the environment (as ground water for example) is sufficiently sanitary as to avoid contaminating nearby wells, rivers, streams, lakes, etc. with pathogens or chemicals from the wastewater. We explain this point further at DISPOSAL vs TREATMENT.
In simplest terms, there are two visible septic effluent or onsite wastewater disposal failures:
- Toilets or other fixtures back up into the house - but
first see Diagnosing Clogged Drains then return here using your browser's 'BACK' button.
- Effluent or sewage appears at the surface of the yard, or the neighbor's yard! Wet spots can be caused by more than a septic failure. You might need to use a SEPTIC DYE TEST PROCEDURE if you can't diagnose this condition by simply running or not running water into building drains.
- Septic odors may also indicate a system failure or an imminent failure. But such odors
may also be produced by defects in the plumbing vent system or other site conditions. Beware, sewer gas contains
methane and is explosive if it reaches a dangerous concentration inside a building.
Typical causes of apparent septic drainfield failure range from things that are easy and cheap to repair, to a need for complete system replacement:
- Clogged building drain or septic system effluent distribution pipes - see CLOGGED DRAIN DIAGNOSIS & REPAIR
- Broken drain pipes or septic effluent distribution piping anywhere in the system, starting between the building and the septic tank or even inside the building. SEPTIC TANK, HOW TO FIND and related articles can help trace piping.
- Damaged septic tank - if the tank baffles are damaged it's easy to replace them, and not costly, but you may have already sent sewage solids out into the drainfield, reducing its future life. See SEPTIC TANK INSPECTION PROCEDURE and SEPTIC TANK BAFFLES and SEPTIC TANK TEES
- Tipped septic effluent distribution box - find and inspect and fix the D-box and you may be back in business. Often a tipped D-box is sending all of the septic wastewater down just a portion of the drainfield, overloading it and causing an apparent failure. See SEPTIC D-BOX INSPECTION.
- Clogged/broken leachfield or drainfield soil absorption piping - find, diagnose, and repair the pipe and you're back in business - see CLOGGED DRAIN DIAGNOSIS & REPAIR
- Clogged drainfield or soakaway field absorption soils around the drainfield piping or trenches, (often by salts, grease & solids, or by an over-aged too-thick biomat) - people try magic bullets, additives, restorers, but despite testimonials and advertising by companies selling these restorers, we have had few reports of lasting, effective success. You may need a new septic drainfield, or you may be able to switch to an alternating drainfield or set of trenches to rest and recover the sluggish section. See SEPTIC DRAINFIELD LIFE. See SEPTIC DRAINFIELD RESTORERS.
Also see septic drainfield clogging at DISPOSAL CLOGGING FAILURES.
Drainfield soils can become clogged or drainfield pipes can be broken and crushed by driving equipment over the drainfield - see Driving or Parking over Septic Components.
- Water-saturated drainfield soil absorption area - you may need to replace the entire drainfield, switch to an alternating bed or set or septic fields, or it may be possible to direct surface and subsurface water from other sources away from the drainfield area.See SEPTIC DRAINFIELD LIFE. See SEPTIC DRAINFIELD RESTORERS. Also see DISPOSAL CLOGGING FAILURES.
List of Articles Describing Causes & Detection of Septic System Failures
DISPOSAL CLOGGING FAILURES
Frequently Asked Questions (FAQs)
...
Ask a Question or Search InspectApedia
Questions & answers or comments about diagnosing and repairing clogged drainfields or soakaway beds or leaching beds or leachfields
Ask a Question or Enter Search Terms in the InspectApedia search box just below.
Technical Reviewers & References
Related Topics, found near the top of this page suggest articles closely related to this one.
- Septic Tank/Soil-Absorption Systems: How to Operate & Maintain [ copy on file as /septic/Septic_Operation_USDA.pdf ] - , Equipment Tips, U.S. Department of Agriculture, 8271 1302, 7100 Engineering, 2300 Recreation, September 1982, web search 08/28/2010, original source: http://www.fs.fed.us/t-d/pubs/pdfimage/82711302.pdf.
- Septic System Drainfield Absorption System Biomat Formation - what leads to drain field clogging and expensive drainfield repairs
- Table of Required Septic & Well Clearances: Distances Between Septic System & Wells, Streams, Trees, etc.
- Ten Steps to Keeping a Septic System Working, suggestions from the U.S. EPA, edits and additions by DJF
- Pennsylvania State Fact Sheets relating to domestic wastewater treatment systems include
- Pennsylvania State Wastewater Treatment Fact Sheet SW-161, Septic System Failure: Diagnosis and Treatment
- Pennsylvania State Wastewater Treatment Fact Sheet SW-162, The Soil Media and the Percolation Test
- Pennsylvania State Wastewater Treatment Fact Sheet SW-l64, Mound Systems for Wastewater Treatment
- Pennsylvania State Wastewater Treatment Fact Sheet SW-165, Septic Tank-Soil Absorption Systems
- Document Sources used for this web page include but are not limited to: Agricultural Fact Sheet #SW-161 "Septic Tank Pumping," by Paul D. Robillard and
Kelli S. Martin. Penn State College of Agriculture - Cooperative Extension, edited and annotated by
Dan Friedman (Thanks: to Bob Mackey for proofreading the original source material.)
- ...
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.
|
- Inspecting Septic Systems: Online Book, Inspection, Test, Diagnosis, Repair, & Maintenance: our Online Septic Book: Septic Testing, Loading & Dye Tests, Septic Tank Pumping, Clearances, details of onsite waste disposal system inspection, testing, repair procedures.
- Advanced Onsite Wastewater Systems Technologies, Anish R. Jantrania, Mark A. Gross. Anish Jantrania, Ph.D., P.E., M.B.A., is a Consulting Engineer, in Mechanicsville VA, 804-550-0389 (2006). Outstanding technical reference especially on alternative septic system design alternatives. Written for designers and engineers, this book is not at all easy going for homeowners but is a text I recommend for professionals--DF.
- Builder's Guide to Wells and Septic Systems, Woodson, R. Dodge: $ 24.95; MCGRAW HILL B; TP;
Quoting from Amazon's description: For the homebuilder, one mistake in estimating or installing wells and septic systems can cost thousands of dollars. This comprehensive guide filled with case studies can prevent that. Master plumber R. Dodge Woodson packs this reader-friendly guide with guidance and information, including details on new techniques and materials that can economize and expedite jobs and advice on how to avoid mistakes in both estimating and construction. Chapters cover virtually every aspect of wells and septic systems, including on-site evaluations; site limitations; bidding; soil studies, septic designs, and code-related issues; drilled and dug wells, gravel and pipe, chamber-type, and gravity septic systems; pump stations; common problems with well installation; and remedies for poor septic situations. Woodson also discusses ways to increase profits by avoiding cost overruns.
- Country Plumbing: Living with a Septic System, Hartigan, Gerry: $ 9.95; ALAN C HOOD & TP;
Quoting an Amazon reviewer's comment, with which we agree--DF:This book is informative as far as it goes and might be most useful for someone with an older system. But it was written in the early 1980s. A lot has changed since then. In particular, the book doesn't cover any of the newer systems that are used more and more nowadays in some parts of the country -- sand mounds, aeration systems, lagoons, etc.
Design Manuals for Septic Systems
-
US EPA Onsite Wastewater Treatment Systems Manual [online copy, free] Top Reference: US EPA's Design Manual for Onsite Wastewater Treatment and Disposal, 1980, available from the US EPA, the US GPO Superintendent of Documents (Pueblo CO), and from the National Small Flows Clearinghouse. Original source http://www.epa.gov/ORD/NRMRL/Pubs/625R00008/625R00008.htm Onsite wastewater treatment and disposal systems,
Richard J Otis, published by the US EPA. Although it's more than 20 years old, this book remains a useful reference for septic system designers.
U.S. Environmental Protection Agency, Office of Water Program Operations; Office of Research and Development, Municipal Environmental Research Laboratory; (1980)
- Eco John® Innovative Toilet Solutions, Global Inventive Industries, Fountain Valley CA, PDF, product brochure
- "International Private Sewage Disposal Code," 1995, BOCA-708-799-2300, ICBO-310-699-0541, SBCCI 205-591-1853, available from those code associations.
- "Manual of Policy, Procedures, and Guidelines for Onsite Sewage Systems," Ontario Reg. 374/81, Part VII of the Environmental
Protection Act (Canada), ISBN 0-7743-7303-2, Ministry of the Environment,135 St. Clair Ave. West, Toronto Ontario M4V 1P5 Canada $24. CDN.
- Manual of Septic Tank Practice, US Public Health Service's 1959.
Onsite Wastewater Disposal Books
- Onsite Wastewater Disposal, R. J. Perkins;
Quoting from Amazon: This practical book, co-published with the National Environmental Health Association,
describes the step-by-step procedures needed to avoid common pitfalls in septic system technology.
Valuable in matching the septic system to the site-specific conditions, this useful book will help you install a reliable system in
both suitable and difficult environments. Septic tank installers, planners, state and local regulators, civil and sanitary engineers,
consulting engineers, architects, homeowners, academics, and land developers will find this publication valuable.
- Onsite Wastewater Treatment Systems, Bennette D. Burks, Mary Margaret Minnis, Hogarth House 1994 - one of the best septic system books around, suffering a bit from small fonts and a weak index. While it contains some material more technical than needed by homeowners, Burks/Minnis book on onsite wastewater treatment systems a very useful reference for both property owners and septic system designers.
- Septic Tank/Soil-Absorption Systems: How to Operate & Maintain [ copy on file as /septic/Septic_Operation_USDA.pdf ] - , Equipment Tips, U.S. Department of Agriculture, 8271 1302, 7100 Engineering, 2300 Recreation, September 1982, web search 08/28/2010, original source: http://www.fs.fed.us/t-d/pubs/pdfimage/82711302.pdf
- Soil Percolation Tests soil perc testing guide and instructions
- Percolation Testing Manual, CNMI Division of Environmental Quality, PO Box 501304, Saipan, MP 96950
- Planting Over Septic System Component", Daniel Friedman (author/editor, InspectAPedia.com), The Innovator, Winter/Spring 2008, BCOSSA, British Columbia OnSite Sewage Association, 201-3542 Blansard St., Victoria BC V8X 1W3 Canada
- Save the Septic System - Do Not Flush These Items Down the Toilet, Daniel Friedman, InspectAPedia.com - PDF document, printable
- Septic System Owner's Manual, Lloyd Kahn, Blair Allen, Julie Jones, Shelter Publications, 2000 $14.95 U.S. - easy to understand, well illustrated, one of the best practical references around on septic design basics including some advanced systems; a little short on safety and maintenance. Both new and used (low priced copies are available, and we think the authors are working on an updated edition--DF.
Quoting from one of several Amazon reviews: The basics of septic systems, from underground systems and failures to what the owner can do to promote and maintain a healthy system, is revealed in an excellent guide essential for any who reside on a septic system. Rural residents receive a primer on not only the basics; but how to conduct period inspections and what to do when things go wrong. History also figures into the fine coverage.
- Test Pit Preparation for Onsite Sewage Evaluations, State of Oregon Department of Environmental Quality, Portland OR, 800 452-4011. PDF document. We recommend this excellent document that offers detail about soil perc tests, deep hole tests, safety, and septic design. Readers should also see Soil Percolation Tests and for testing an existing septic system, also see Dye Tests
- Grass is Always Greener Over the Septic Tank, Bombeck, Erma: $ 5.99; FAWCETT; MM;
This septic system classic whose title helps avoid intimidating readers new to septic systems, is available new or used at very low prices.
It's more entertainment than a serious "how to" book on septic systems design, maintenance, or repair. Not recommended -- DF.
- US EPA Onsite Wastewater Treatment Systems Manual Top Reference: US EPA's Design Manual for Onsite Wastewater Treatment and Disposal, 1980, available from the US EPA, the US GPO Superintendent of Documents (Pueblo CO), and from the National Small Flows Clearinghouse. Original source http://www.epa.gov/ORD/NRMRL/Pubs/625R00008/625R00008.htm
- Water Wells and Septic Systems Handbook, R. Dodge Woodson. This book is in the upper price range, but is worth the cost for serious septic installers and designers.
Quoting Amazon: Each year, thousands upon thousands of Americans install water wells and septic systems on their properties. But with a maze of codes governing their use along with a host of design requirements that ensure their functionality where can someone turn for comprehensive, one-stop guidance? Enter the Water Wells and Septic Systems Handbook from McGraw-Hill.
Written in language any property owner can understand yet detailed enough for professionals and technical students this easy-to-use volume delivers the latest techniques and code requirements for designing, building, rehabilitating, and maintaining private water wells and septic systems. Bolstered by a wealth of informative charts, tables, and illustrations, this book delivers: * Current construction, maintenance, and repair methods
* New International Private Sewage Disposal Code
* Up-to-date standards from the American Water Works Association
- Wells and Septic Systems, Alth, Max and Charlet, Rev. by S. Blackwell Duncan, $ 18.95; Tab Books 1992. We have found this text very useful for conventional well and septic systems design and maintenance --DF.
Quoting an Amazon description:Here's all the information you need to build a well or septic system yourself - and save a lot of time, money, and frustration. S. Blackwell Duncan has thoroughly revised and updated this second edition of Wells and Septic Systems to conform to current codes and requirements. He also has expanded this national bestseller to include new material on well and septic installation, water storage and distribution, water treatment, ecological considerations, and septic systems for problem building sites.
- The NSFC Products List has an excellent list of design manuals/modules available from their website or by telephone 800-624-8301
- Submissions welcome. send us a suggested document link or request an exchange of website links
- ...
|