InspectAPedia®

Seepage pit or drywell design sketchGuide to Seepage Pits for Septic System Effluent Disposal

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


This document explains what a drywell or seepage pit is, gives safety and maintenance advice for drywells / seepage pits, and defines the criteria for drywell failure. We also explain a useful difference between a drywell (accepts only graywater) and a seepage pit (accepts septic effluent). We warn readers that while installation of a drywell to receive graywater at a property may be a good idea, the use of drywells may be a warning about the capacity and remaining life of the septic system.

This article series explains septic system and drywell or seepage pit or cesspool inspection procedures, defects in onsite waste disposal systems, septic tank problems, septic drainfield problems, checklists of system components and things to ask. Drywell & seepage pit maintenance and pumping schedules.

Seepage pit design specifications: this article discusses the design & construction of septic seepage pits for septic wastewater treatment to perform the functions of septic effluent treatment and disposal in onsite wastewater treatment systems, conventionally called "septic systems". A seepage pit is designed to receive clarified effluent from a septic tank, or if the pit receives only gray water (GREYWATER SYSTEMS) then it's called a drywell.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Guide Seepage Pits: definitions, construction, testing, uses, warnings

Photograph of  a seepage pit

Seepage pits: a "seepage pit" may be used as a septic effluent absorption system such as shown in the sketch at the top of the page and also immediately above.

In this application, instead of receiving only graywater from sinks, laundry, shower, etc., the seepage pit is receiving not just graywater but also blackwater-effluent or septic effluent which flows out of a septic tank.

Unlike the drywell described just above, in this design waste, including black water and gray water, leaves the building through a main drain which enters a septic tank. The tank retains solids and grease/floating scum, allowing clarified effluent to enter the seepage pit for disposal into the soil.

Distinctions among cesspool, cistern, drywell & seepage pit:

Photograph of  a seepage pit collection at the factory Seepage pits come in a variety of capacities, sizes, shapes, and can be safe (against collapse) when a modern factory-built unit is shown, such as those in this photo.

Watch out: We do not consider the use of traditional seepage pits a complete and satisfactory onsite septic effluent wastewater disposal system design, though where space is limited or for other problem site reasons it may have been the choice of the septic system installer.

Disposal of septic effluent deep below ground in a seepage pit (typically four to six feet deep and placed another two or more feet below grade level) means that little or no aerobic bacteria will be present.

Limiting the bacterial action to anaerobic may mean that the biomat that forms around the seepage pit will not adequately treat the effluent. The system may then be discharging contaminants into groundwater and the environment.

Fortunately there are alternative onsite wastewater disposal alternative designs which can handle limited or even zero-space sites, so a simple seepage pit as a destination for blackwater effluent is no longer the only choice for limited-space sites.

More Reading about Seepage Pits for Septic Effluent Disposal

(h) Seepage Pits used for septic system effluent disposal in "New York State Septic System Design Regulations 75-A.8 Subsurface treatment - disposal of septic effluent - design specifications for septic systems" includes design specifications for seepage pits used to receive septic effluent, including tables of dimensions required for different household loads.

Drywell and Seepage Pit Safety and Septic System Capacity Warnings

Drywell & Seepage Pit Safety

Drywell & Seepage Pit Capacity and Testing Limitations

Tips for Extending Seepage Pit Life Life

Some experts recommend installing a filter on water entering the seepage pit. Particularly for a seepage pit used to receive water not just from a septic tank receiving black water but also graywater from a clothes washing machine, installing a lint filter between the washing machine and the seepage pit can extend the life of the drywell by reducing the moment of soil-clogging particles of lint and debris into the system.

Intermittent dosing systems such as are used for some alternative septic system designs, can also be adapted to graywater systems. In simple terms, this means that multiple drywells are used, and graywater is routed intermittently among them, giving the unused drywell time to recover. A simple valve system on the graywater drain line can serve to route greywater (graywater) to alternating drywells.

Seepage Pits - Seepage Pits used for septic system effluent disposal

Repeating an important distinction we made above, a cesspool is not a seepage pit, and vice versa, though their construction may be similar. Cesspools receive black water (sewage including solids) directly. Seepage pits receive only clarified septic effluent ( no large solids).

(1) General notes about seepage pit septic system components

A seepage pit, sometimes called a leaching pit, leaching pool, or incorrectly a cesspool, is a covered pit with an open-jointed or perforated lining through which septic tank effluent seeps into the surrounding soil.

[DF NOTE: the term drywell might be used for a seepage pit disposing of septic effluent in this case; by contrast, a cesspool holds both solid waste and septic effluent. I use the term "seepage pit" to refer to a pit used to dispose of septic effluent which originated as blackwater, the solids having been retained in the septic tank. I use the term "drywell" to refer to a pit used to dispose of graywater (greywater) which originated in sinks, laundry facilities, or showers. While their uses and implications of their presence at a property are quite different, the actual construction details of a seepage pit or a drywell are about the same.

(2) Site Requirements for septic seepage pits

(i) If soil and site conditions are adequate for absorption trenches, seepage pits shall not be used.

(ii) A minimum three foot vertical separation must exist between the bottom of any pit and the high groundwater level, bedrock, or other impervious layer.

(3) Design Criteria for seepage pits used to dispose of septic effluent

(i) The required "effective seepage pit area" is obtained from Tables 6 and 7 which are shown below.

(ii) No allowance for infiltration area is made for the bottom area of a pit or the surface area of impervious soil layers (percolation rate slower than 60 minutes/inch).

(iii) The effective diameter of a pit includes the diameter of the lining plus the added diameter provided by the annular ring of aggregate. Any area surrounding the liner with rock smaller than 2 1/2 inches in size shall not be included as part of the effective diameter.

(iv) Effective depth is measured from the invert of the seepage pit inlet to the floor of the pit, with the thickness of impervious layers deducted.

Site Distance Requirements for Seepage Pits

SKETCH of a typical aerobic treatment unit tank, aerator, chamber

This sketch (from New York's Wastewater Regulations) shows the recommended site clearances between a seepage pit (or cesspool or drywell) and other building and site features.

A more detailed list of site clearances to septic system components is listed at "More Reading" just below. Notice that seepage pits not only need to be at a sufficient distance from the building, from wells, from property lines, but also if multiple seepage pits are installed, they should be adequately separated from one another.

Absorption Area Requirements for Seepage Pits

Table 6 shown here gives the required soil absorption area for seepage pits as a function of soil percolation rate and anticipated daily wastewater flow in gallons.

[Click to see an enlarged, detailed version of this or any other image or table found at InspectApedia.com]

TABLE 6 - SEEPAGE PITS - REQUIRED ABSORPTIVE AREA (IN SQUARE FEET) FOR HOUSEHOLD SYSTEMS

Seepage Pit Size Requirements to Obtain Necessary Absorption Area

Table 7 given below shows the size of seepage pit necessary in order to provide the required soil absorption area for seepage pits. First use the preceding table to determine the necessary seepage pit absorption area, then use this table (below) to determine the necessary seepage pit size to provide that absorption area.

TABLE 7 - SEEPAGE PITS (CYLINDRICAL) - DIMENSIONS FOR REQUIRED ABSORPTIVE AREA (IN SQUARE FEET)

Seepage Pit Construction Details: Linings, Separation, Strength, Connections

Seepage pit USDA DJFThe schematic of a seepage pit (left, courtesy USDA) shows typical construction of a site built seepage pit using brick, block, or pre-cast concrete rings with open joints, surrounded by stone to improve soil absorption.

NYS: (v) Seepage pit linings may be pre cast concrete, cast-in-place concrete, or built in place with unmortared hollow cinder or concrete blocks. Concrete shall have a minimum compressive strength of 2,500 psi and 3,000 psi is recommended.

Material with comparable structural strength, determined in accordance with commonly accepted sewage construction standards, principles or practices, may be allowed on an individual basis to prevent unreasonable hardship, provided public health is not prejudiced.

(vi) The separation between the outside edges of seepage pits shall be three times the effective diameter of the largest pit. This separation is measured as the undisturbed soil between pit excavations.

(vii) Pits shall be designed with sufficient structural stability to withstand lateral soil forces as well as vertical loads.

(4) Construction of seepage pits for septic effluent disposal

(i) Laterals leading to each seepage pit must be at least four inches in diameter with a minimum slope of 1/8 inch per foot.

(ii) Seepage pits shall not be connected in series. A distribution box shall be required where more than one seepage pit is installed.

(iii) The pit excavation is to be raked to minimize sidewall smearing that may occur and reduce infiltration capacity. If groundwater is encountered, the pit shall be backfilled with the original soil to a level at least three feet higher than maximum groundwater and adjustments made in the pit dimensions.

(iv) The linings are placed upon a concrete block, poured concrete, or pre cast footing and surrounded by a six inch minimum annular ring of large aggregate (2 1/12 - 4 inches in size).

(v) The rock is covered to prevent soil from filling the void spaces. Building paper, a four inch thick layer of hay or straw may be used.

(vi) The seepage pit cover shall be structurally sound and capable of supporting 300 pounds per square foot at the weakest point. Covers may be pre cast concrete or cast-in-place and shall be reinforced. A manhole with an opening of at least 20 inches in the shortest dimension shall be provided.

Septic Seepage Pit, Drywell, or Cesspool Collapses

Photo of seepage pit collapse when driven over by a dump truck

A seepage pit, drywell, or cesspool can be collapsed as shown in this photo, where a seepage pit receiving septic effluent was driven over by a heavy dump truck.

Watch out: Seepage pit, cesspool, or drywell collapses are dangerous and can be fatal if someone falls into the collapsing opening.

Falling into a cesspool, seepage pit, or drywell can easily be fatal, and quickly. We investigated a tragic case in which an adult fell into a cesspool that then collapsed over him, burying him alive.

In general, while there are heavy duty septic system components and covers for pits and tanks, you should not permit traffic to drive over septic equipment nor on septic fields.

See SEPTIC & CESSPOOL SAFETY.

Seepage Pit Life Expectancy & Maintenance

Reader Question: What product can I by that will eat the grit and dirt off the walls of the seepage pit, clean the pores so that the liquids will drain out in the earth, and so that I do not have to pump out all the time?

I live in the Hollywood Hills CA. I have a septic tank inlet and outlet and a seepage pit. My seepage pit & septic I have to have to pump out every 4 months versus 2 years, for the liquids are not seeping out and the pores are clogged with grit, dirt and I would say toilet paper. What product can I by that will eat the grit and dirt off the walls of the seepage pit, clean the pores so that the liquids will drain out in the earth, and so that I do not have to pump out all the time? - S.B.

Reply: Sounds As If You Need a New Seepage Pit

A competent onsite inspection by an expert usually finds additional clues that help accurately diagnose a septic system or seepage pit problem.

That said, we do not recommend septic seepage pit additives or cleaners for septic effluent seepage pits (see SEPTIC TREATMENTS & CHEMICALS) - using at least some of these products risks contamination of your environment, groundwater, or nearby wells, and depending on local laws septic treatment chemicals may be illegal as well.

Septic seepage pit rejuvenation methods like agitating or hydrojetting can sometimes temporarily give some relief and cause drainage at least from the bottom of the pit, but depending on how the seepage pit has been constructed these methods can be very dangerous. The risk is a pit collapse, someone can fall in - a fatality that has actually happened more than once.

In sum if the seepage pit no longer drains into the surrounding soils, you need a new one. You can extend the connection to the new seepage pit from an outlet from the old seepage pit provided the old pit is not in danger of collapse.

Septic tee troubles (C) D Friedman J WatersOtherwise the old pit needs to be abandoned: pumped out and filled-in with soil and rock to be safe.

Your observation of toilet paper in the seepage pit suggests that solids are not being retained in the septic tank where they belong.

If solids are flowing into the seepage pit from the septic tank, that will explain its short life and costly frequent pumping.

The cause could be damaged or missing baffles in the septic tank - something that can be repaired when your new seepage pit is installed.

Our photo (above-left) shows a damaged septic tank baffle that was allowing solid waste to flow out of the septic tank into the absorption system. Details of septic tank tee replacement (baffle replacement) are at SEPTIC TANK TEES.

When your new effluent seepage pit is being installed, look into installing a filter at the outlet from your septic tank; in fact check that the septic tank baffles are intact.

Beyond their design specifications provided here, seepage pits & drywells are also discussed and are contrasted with cesspools at DRYWELL DESIGN & USES or onsite gray water disposal - What are Drywells, What Drywell Maintenance is Needed? How do Drywells Fail?

A cesspool is not a seepage pit, and vice versa, though their construction may be similar. Cesspools receive black water (sewage) directly.

Key Drywell & Cesspool Articles

...


Continue reading at DRYWELL / SEEPAGE PIT SPECIFICATIONS or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see CESSPOOL FAILURE CRITERIA

Suggested citation for this web page

SEEPAGE PITS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to SEPTIC SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Questions & answers or comments about designing, installing, using & mainteaining seepage pits for sewage or septic effluent disposal

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman