Winterizing a building: how to freeze proof a building when heat will be turned off:
This article explains with a step by step guide just how to winterize or freeze proof a building when the building's heating system is going to be turned off completely.
We discuss turning off water supply, draining piping and plumbing fixtures, turning off and if necessary winterizing a heating system, and other steps to avoid freeze damage or water, leaks, and mold damage to buildings that are being left in a "shut down" condition.
The articles at this website will answer most questions about freeze protection for piping and other building plumbing and heating system components: how to winterize a building to avoid frozen pipes, and how to thaw frozen water supply & drain piping, wells, & water tanks.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
[Click to enlarge any image] Sketch above courtesy of Carson Dunlop Associates.
Is the building heat going to be left "on" or "off" - the answer determines the extent of freeze-proofing needed.
If you have decided to shut down the building's heating system, some steps to protect the building from freeze damage are simple (you don't worry about figuring out the thermostat set-temperature nor about finding "cold spots" where pipes may freeze).
Incidentally, don't make this common mistake: never leave a garden hose attached to your outdoor faucet in winter as water in the hose may add to the risk that the faucet will be freeze damaged. See details about outdoor faucets, hose bibbs, sillcocks
at FAUCETS, OUTDOOR HOSE BIBBS and
at SILLCOCK INSTALLATION & REPAIR.
But other critical steps need to be performed if you are going to avoid frozen pipes and future leaks and water damage in a building to be winterized with the heat left off (such as an empty summer cabin, vacation home, or an unoccupied residence.)
See details at WINTERIZE WATER SOFTENER & WATER TREATMENT EQUIPMENT.
This article explains water softener shut-down procedure, explain why we use the water softener bypass valve, and how that can reduce the risk of freeze damaged pipes, leaks, and even indoor mold growth.
A separate article WATER SOFTENER / TREATMENT TURN-ON provides details on returning a shut-down water softener to operation after it has been shut down.
Empty or remove building fixture traps; see our note below about use of antifreeze.
Use of antifreeze to winterize a building: Be careful: unless the anti-freeze is specifically designed for winterizing a building it could be highly toxic (such as automobile antifreeze).
We do not recommend using toxic antifreeze to winterize a building since later you're moving that contaminant into the public sewer or into soils (and possibly ground water) around a private septic system. Only inside of closed water systems such as a heating boiler do we recommend use of anti-freeze mix in a building.
This sketch of a gas-fired water heater and its control valves is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Warning: do not drain a water heater tank before first turning off its energy source: oil, gas, or electricity.
Heating an empty water tank is very dangerous and is likely to quickly destroy the tank or its heating elements.
Watch out: for all oil or gas fired heating equipment (furnaces, boilers, water heaters) we recommend having the heating equipment cleaned before shutting it down - a step that will avoid corrosion, clogs, and trouble when heat is later turned back on.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
@Mark George,
Thanks that's a great question.
Question: How long can we safely leave a building winterized.
Answer: no time at all, or several years. It depends...
When a building is shut down as we describe on this page, nothing in that technical shut-down is causing direct or active harm to the building or its mechanical systems. So in that sense it could be left shut down for years.
But, and this is a big concern:
When a building is left absolutely un-attended, even simply over the course of days, much less months or years, it is at risk of serious damage from the following:
And any of these can leave a building so damaged that it deteriorates so rapidly that even in a few days the damage can be so extensive and so serious that the building has to be gutted before it can be restored.
The photo that I attach here is from an insurance claim investigation I performed for a large insurance company. You can see that the home's interior is badly contaminated by mold - so badly that the home had to be gutted to the raw framing before it could be restored.
The cause: a burst pipe in the basement flooded the building. A burst and un-drained pipe in the basement flooded that space.
The result was a soaking wet building up-state New York that was left un-attended, un-inspected, for three months.
But a water leak can occur even in a well-winterized building if a window breaks and snow blows-in, or if shingles blow off of a roof or a branch punctures a hole in it. Something as un-expected as a bird flying-into and breaking a window can expose a home to significant water entry and damage.
Best solution: set up building monitoring
The frequency needed for live on-site monitoring visits and inspections depends on the specific building's properties, site, and geographic location, and a risk-assessment by an experienced building professional. Some example questions:
- what is the range of weather conditions like rain, heavy snow fall, high wind? Wildfire? Storm damage? Proximity to large bodies of water or other geographic hazard or damage sources?
A building in Grand Marais Minnesota, close to Lake Superior is more vulnerable to storm damage than a building in downtown Camden, New Jersey.
- what is the risk of malicious mischief? Downtown Camden, New Jersey has a different risk of break-in than downtown Grand Marais, Minnesota.
- what are the condition of the building's roof, windows, doors, flashings
- what is the building's leak history?
- what are the building's materials and how vulnerable are they to water damage
Example1: In the Hudson Valley of New York State if a home in a residential neighborhood is to be left empty for a month, and if the home has a bulletproof roof (standing seam metal) and no history of water entry, and if we're leaving the home with water turned off and winterized, we'd still want an inspection once a week and if there were a neighbor who would make a walk-around, even just outside or peeping into windows every few days that'd be better.
Example 2: In a small peaceful town in central Mexico, a home in a residential neighborhood and constructed of adobe - materials less-likely to be destroyed by water entry or mold - may need to be monitored for security, break-in's and if water is not turned off, for burst-pipe water damage. We'd install security cameras and depending on their extent we may want regular inspections for security and damage detection as well.
On 2021-12-07 by Mark George - can a building be left winterized and shut down for several years?
Once the building is winterized with RV solution can it continually be winterized and shut down for several years?
On 2020-11-11 by (mod)
I would do three items listed on this page. Of course it's possible that your home has something else that needs to be drained.
On 2020-11-10 by John Williams
If I have all my utilities turned off & water blown out of pipes, all electric turn off , what else need be done to winterizes this empty house?
On 2019-02-24 by (mod) -
Bob that should work, as long as the piping is pitched enough that water doesn't simply sit in horizontal piping or regulator or valve.
On 2019-02-23 by Bob Worthington
I have a lake house in northern Ohio. Each winter we turn off heat and drain pipes. This year my pressure regulator cracked. Here's the setup: Water pipe enters house about 3 ft below ground level into my crawl space. 18" of water pipe and there is a a cut-off valve to turn water off completely from rest of house; 18" later is my pressure regulator.
Above the pressure regulator is another cut-off valve, which I use to drain the cold water lines of the house; since it is above the pressure regulator, it's guaranteed that there will be water in the regulator all winter..
My question is: Can I move the drain value to below the pressure regulator; would water, not under pressure, drain "backwards" through the regulator, so I can drain all the water and simultaneously drain the pressure regulator?
On 2017-12-19 by (mod) -
Robert
In a freezing climate people like to install the main shutoff inside of the structure as close to the point of water main entry as feasible. The valve is drained by installing a shutoff that includes a small screw cap outlet intended for draining water out of the valve itself.
The main building piping, if it needs to be drained, should be sloped to drain down to a low point where a stopcock is installed to permit draining.
On 2017-12-18 by robert
Where to install the water shut off valve for cabin on a slab hooked to main water line. And how to drain?
On 2016-10-22 by (mod) -
Wally,
I'm too scared to bet your house and money on a promise that wood floors in will be okay in a home about which I know almost nothing.
Certainly by proper winterizing as described in this article series you can minimize the risk of damage from leaks or from frozen, burst piping. However in my OPINION, there is always a risk of some cracking or unexpected movement in building materials, especially drywall and sometimes flooring, both wood and tile flooring, when a building is left to below-freezing temperatures.
The best you can do is to properly drain everything. Better would be regular inspections to check that nothing surprising has occurred, like a broken window or a blown-off roof shingle and concomitant leaking. In many areas of southern Ontario there are people living year round in areas where many homes are closed-up for winter and who will for a fee make regular checks on the homes for damage.
On 2016-10-21 by Wally
Our home is located in southern Ontario & is built over a crawl space. Foundation walls are cement block, below frost line & have blown in insulation. We go south for the winter & want to turn off the heat. Plumbing will be totally drained & antifreeze. Windows are new. Will the wooden furniture & floors be ok?
On 2015-11-23 by (mod) -
Wade if you are turning heat OFF then you want to open all valves and drain all piping in the building.
If you are leaving the heat on in an otherwise winterized building, make sure that the heating boiler (if your heat is by hot water) is assured of having a working water supply. Other supply valves to other parts of the building can be shut off - that reduces the chance of an extensive flood should one of the water supply pipes burst.
On 2015-11-23 by Wade
Which indoor water valves to switch off for winterization?
On 2015-11-23 by (mod) -
Lynda, few places in Mexico suffer from hard freeze conditions - tell me where you are located. In general if you are not leaving water filled pipes or drains that are subject to freezing you should be fine. That is to say water and an open culverts that freezes should not damage system
On 2015-11-22 by Lynda Caton
Hi there,
I have gravity feed water system,the water comes out of the creek as needed and fills a five foot in diameter culvert which feeds into a two inch water line, I am away for the winter and have drained and put recreational antifreeze in all the drains and toilets in the house, should I drain the culvert reservoir as well?
Thanks so much,
worried in Mexico
On 2015-11-03 by (mod) -
Keep us posted; if you like send me some photos of the set-up via our email found at the page bottom CONTACT link and I may be able to comment further.
DF
On 2015-11-03 by Anonymous
Thanks! I'm heading down this weekend, so I'll give it a try.
On 2015-11-02 by (mod) -
I would not use a PSI above the maximum PSI that your water system can deliver - that should be more than enough to reach the highest water in highest pipe in the building. I would consider installing a suitable fitting and blowing "down" through the structure from a convenient high point or points.
On 2015-11-02 by Brad
Dan, that's very helpful. I have heard gurgling in the past when I've shut the water supply off and opened faucets. Can you recommend a minimum psi/volume for a compressor to blow the pipes out? Thanks!
On 2015-11-02 by (mod) -
Good question, Brad and I'm sorry to have to equivocate; as Mark Cramer says ... it depends. If the home was constructed to be winterized then all of its pipes would slope down to drain points; if not the risk is that even when you open lines to drain, enough water may remain in an upwards sloping section to freeze and burst a pipe.
If you hear gurgling at the *end* of your manual drain-effort I'd be worried.
On 2015-10-30 by Brad
We have a vacation house on the extreme southern end of the Jersey Shore. This year we are planning to winterize without heat. (It has a hot-water boiler with baseboard and radiators.) Are we far enough south that draining all the pipes would be enough, or do we need to blow them out? Thanks
On 2015-10-27 by Leaving Maine for the winter
We are planning to completely shut down our house this winter and have hired a knowledgeable plumber to drain the entire heating and water systems and treat all the traps. My question has to do with food in my pantry.
Will all my glass jars of food explode because of the freezing? And my canned goods - will they all push out damaging the seals? I figure any liquors are safe, but what about wines? We are leaving soon, so a quick reply is greatly appreciated.
Sure, provided your heating zones are individual piping loops, and that you have control valves at both ends of the un-used heating zones, you can drain them and leave them turned off.
At AIR BLEEDER VALVES we describe air bleed valves found on hot water heating systems. These valves, normally used to purge trapped air that can cause cold radiators or baseboards, can also be opened to make it easier to get water out of the heating system piping when the building is being drained so as to leave heat off completely.
Watch out: to get all of the water out of the piping. It can be difficult to get water out of long horizontal pipe runs without blowing air through the system. For this reason some winterizing companies actually cut the heating pipes, planning to repair them when the building heat is restored. Don't forget to check for cut or burst heating pipes later when de-winterizing the building.
More details about how to winterize the heating system when you are going to leave heat "OFF" are found
at Winterize- Heat Off Procedure.
Also see how WINTERIZE A BUILDING
Instead of trying to drain the heating zones I don't need, can I just put a non-toxic antifreeze in the whole boiler system? It sounds easier if it is a good solution.
Thanks again!
Sure, there are specific antifreeze products intended for use in hot water heating systems.
Also see WINTERIZE A BUILDING
I have such a system, and only one zone. The thermostat is located in the warmest room in the house. Causing frigidity and numbness of extremities in other areas of the home.
Since the location of the thermostat is also where the first radiator is in the home, can I "shut off" that baseboard radiator, and the next one, without losing heat to the rest of the home? - Jacke
Jacke
Whether or not you can shut off or turn down the first two radiators or baseboards in your home to improve heat distribution depends on how the piping is arranged.
If all of the baseboards are piped in series (which is usual for single-zone hot water baseboards) then the input of each baseboard is fed directly from the outlet of the one prior. In that case you can't turn off any baseboard because 1. you have no shutoff valve installed and 2. more important, you'd be shutting off all hot water flow through the system.
If you have radiators, heating convectors, or even some baseboard installations that are piped in parallel, that means that there will be a loop of hot water heating piping that runs through the buildings and that off of that loop, individual risers and returns feed individual radiators or convectors (heating baseboard is not usually piped this way).
In this second case it would be possible to turn off an individual radiator or convector.
So part of my long answer is due to confusion on my part - you use the terms radiator, then baseboard radiator - so I'm not sure what you've got.
Let us know the details - what we learn will assist others.
how do i add antifreeze to my boilers baseboard heating system - Gene Griswold 7/22/12
Gene, please search InspectApedia for
"Guide to Fixing an Air-Bound Hot Water Heating System - Procedure#2," and you will see an article on how a service tech uses a pony pump and fittings to place antifreeze into a hydronic heating system.
(Jan 28, 2014) Tracy said:
Help! NE North Carolina, 9-12" snow expected, possible power outages & probable road closures so leaving b4 we CAN'T leave..planning to drain piping but leave heat on...if I don't drain water heater & power goes, how long might it be safe b4 water in heater to freeze & should I leave wh breaker on or off? PLEASE HELP QUICKLY! I HAVE ONLY 3 HRS TIL LEAVE TIME!!!
Review the checklist at
WINTERIZE - HEAT ON PROCEDURE
the link is at More Reading
At a bare minimum: if you expect power to be off, turn off the building water supply.
That should minimize the extent of leakage that can occur if a supply pipe breaks.
Then on return to the home go through our De-Winterizing checklist - basically you will turn heat on and water on and check for leaks.
(Nov 5, 2014) Deborah Frenette said:
I wonder if it is true that in an unheated home that damage can occur to the walls and floors caused by the extreme cold? WE plan to not waste $$ on heating this year. my smart hubby has done all that is needed to protect the water supply. thank you.
Yes Deborah, in extreme cold some building materials may show signs of cracking or movement. I've seen this show up as drywall cracks and on a few occasions fine cracks in ceramic tile floors on a concrete slab.
For this reason, while it is still possible and even reasonable to leave heat off completely (with proper winterizing) for modern construction and where a building is not being left for an extended period such that we are trying to eliminate heating costs completely, I prefer to keep some low heat in the building to try to keep it a bit above freezing.
(Nov 5, 2014) Deborah said:
thank you! WE are not using the building (my office, it is attached to our big house) and that is why we are turning off the heat. I will show this to my hubby. The heating bill for an empty building is getting too high. But we do not want to have to repair cracks in the walls!
Deborah
You might see no cracking at all - a lot depends on the particular details of construction including materials, connectors, foundation type, basement vs slab, and importantly, water under and around the building.
If the building is more than a decade old you might have some clues by noting whether or not settlemnt or other cracking has ever occurred.
(Jan 14, 2015) Anonymous said:
house in pa had oil burner 4 heat got wood burner heats house now also electric hot water heater new in years to come what are the steps to close oil stoker down for long extended time need all steps thank you ed
(Feb 3, 2015) Crafty said:
We have a camp that we regularly dump antifreeze into the traps and toilets because it is left unheated. I absolutely hate this, so I've been looking for a way to get around it, or at least minimize how much is needed.
Would love to eliminate some traps if possible, but does anyone have a recommended non-toxic antifreeze, until I get around to finding a solution? I think I'll just buy a bunch of that to keep there. We try to use RV antifreeze as it's supposedly bio-degradable, but we've allowed people to bring their own, and they don't always comply. I hate to be dumping toxins into the ground.
Crafty there are food grade antifreeze products used in RVs and water systems. Those products should not be harmful. If you let visitors use whatever they bring we've lost control of the problem and may be killing off the septic system to boot.
We built our home 15 years ago. It is a split level with concrete foundation. When we retired we stated to spend our winters in a warmer climate (we live in N. Ontario). Every winter we have left some heat on the lower level of the house keeping the temperature around 4c.
However with the increase in the cost of oil and our dwindling income buying power, we have been thinking of ways we could cut off both the hydro and the oil heater. Is there any way of us testing what effect this might have on the concrete foundations?
The foundation is covered with a layer of ceramic tiles which we later covered over with a laminate flooring. Thank you. - C.W., northern Ontario
Our sketch (left, courtesy of Carson Dunlop Associates ) shows what happens when a home is left with heat off in a freezing climate.
I don't know of an actual test that you can perform to predict foundation damage if the heat is left off completely in your building, since testing would require creating the actual freezing conditions and would itself risk building damage. Sketch at left, showing evidence of frost heaving is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
At "A Common Source of Vertical Frost Heave - Un-heated Homes" found in our article
VERTICAL MOVEMENT IN FOUNDATIONS we discuss the problem of foundation damage in un-heated homes.
And at FROST HEAVE / Expansive Soil Cracks in Slabs we provide more details.
Sketch (left, courtesy of Carson Dunlop Associates ) shows upwards as well as horizontal frost pressure on a building and it indicates where cracks and dislocation commonly appear.
Here are some things you can check:
Watch out: other factors can still cause slab or foundation damage due to frost.
An alternative to turning heat off in the building entirely is to continue your practice of leaving heat on at a low setting (4 C or about 40 F) but take measures to protect the building from damage (possibly allowing a slightly lower heat setting) and to reduce heating cost by finding and fixing drafts, air leaks, or by improving building insulation.
See WINTERIZE - HEAT ON PROCEDURE
...
Continue reading at ANTIFREEZE for BOILERS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WINTERIZE - HEAT OFF PROCEDURE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.