Oil fired water heater with a backpressure sooting problem (C) Daniel FriedmanGuide to Oil-Fired Hot Water Heaters - Inspection, Diagnosis, & Repair

  • OIL FIRED WATER HEATERS - CONTENTS: Oil fired Hot Water heaters: how to inspect, test, adjust, repair . How to choose among types of hot water heaters. Guide to inspection of electric water heaters. No Hot water? how to get more hot water flow, quantity, performance from your water heater. Repairing and restoring a flooded water heater
  • POST a QUESTION or READ FAQs about diagnosing & repairing oil fired water heaters
  • REFERENCES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

This article explains how to inspect, diagnose, adjust, maintain, or repair oil-fired water heaters including the loss of hot water or inadequate hot water supply. We include normal water heater maintenance, temperature adjustment, and improvements to hot water quantity as well as reduction in hot water heating cost. We also discuss important safety features and checks on oil fired heating equipment. We also discuss how to restore a flood-damaged water heater to service.

This article series on oil hot water heat will answer most questions about oil-fired water heaters as well as many other building plumbing system inspection or defect topics. Our photo at page top shows an oil fired hot water system with the main components easily available, and with evidence of an oil burner operating problem.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Inspection, Diagnostic, & Repair Guide to Electric Hot Water Heaters

How do we identify an oil-fired water heater?

Schematic of an oil fired water heater (C) Carson Dunlop Associates

This page contains links to in-depth articles on inspecting, testing, and repairing problems residential hot water heaters of all types, including their parts, controls, and alternative sources for hot water as well as tips for improving hot water temperature, hot water pressure, and hot water quantity.

[Click to enlarge any image]

The sketch at left shows the basic components of an oil-fired residential hot water heater and is provided courtesy of Carson Dunlop Associates. It's easy to identify an oil-fired water heater:

Watch out: sometimes an electric water heater is installed as an additional or backup hot water source, so you'll also want to see if you have other hot water heating equipment installed, such as a Tankless Coil for Hot Water. In our photo below at left an oil-fired water heater and an indirect-fired water heater are installed in tandem.

Here are a few things to check on your oil-fired water heater:

(WARNING: This is an INCOMPLE LIST and important water heater inspection topics may be omitted as we're working on this section. If you have comments, questions, suggestions, Contact Us.)

Leaks at a hot water heater (C) Daniel Friedman

Check the pressure and temperature relief valve on your water heater: look for evidence of corrosion, leaks, improper installation, etc. A missing, modified, blocked, or leaky pressure relief valve is extremely dangerous and can lead to a catastrophic BLEVE boiling liquid vapor explosion that can cause severe damage or even fatalities at a building.

See RELIEF VALVES - TP VALVES

Look for evidence of leaks in the hot water tank, or mechanical damage, or improper installation. For example most water heaters are intended to be installed in a vertical position. Installing a hot water tank horizontally or in a hole in a crawl space is likely to cause early failure of the heater, violate the manufacturer's guidelines, and may be dangerous.

In our photo at left that puddle on the floor needs investigation.

Look for the draft regulator/barometric damper. If your conventional oil fired water heater does not have its own, personal draft regulator installed, it is impossible for the heater to have been tuned for optimum performance - you may be wasting money and heating oil.

See DRAFT REGULATOR, DAMPER, BOOSTER

Check the settings of the water heater temperature: See Temperature of Hot Water is Too Low

Look for insulation that has been improperly added to the water tank - it may be unsafe.

See INSULATE HOT WATER TANK?

Look for signs of improper oil burner operation: such as sooting, draft problems, or back-pressure burns around the oil burner or around the combustion chamber inspection port.

Oil fired hot water heater showing visible signs of improper, possibly unsafe operation (C) Daniel Friedman

Soot blowing out of the barometric damper or flue pipe, soot and burn marks, oil leaks, stumbling, rumbling, noisy oil burners, odors, are examples of improper oil burner operation that need prompt service.

Our page top photo and our photo at left show examples of improper oil burner operation on an oil fired water heater: both systems show soot blow-out at the water heater's combustion chamber inspection port. Our photo at left also shows that the discharge tube is missing from the relief valve - a safety concern.

Often these soot marks are a symptom of excessive pressure or "back pressure" inside the combustion chamber.

This problem can be caused by an oil fired water heater that is way past due for cleaning (soot blocks the exhaust flue), by a blocked chimney, by improper draft regulator adjustment, or other defects.

See OIL BURNERS

and OIL BURNER NOISE SMOKE ODORS

Check the hot water piping and control valves connected to the water heater for leaks, support, and for proper location of shutoff valves.

An improperly installed shutoff valve on a water heater can be very dangerous, risking an explosion. Usually the "hot water tank shutoff valve" is installed only on the cold water pipe coming into the water tank. There should be no shutoff valve installed on the hot water line leaving the water tank.

Check for leaks at the water heater drain valve. Most water heater manufacturers recommend that their water tank be drained periodically. This process will help remove sludge and debris or mineral deposits that may have accumulated at the bottom of the water heater tank.

Removing this debris can extend the life of the hot water tank, especially where electric and gas fired water heaters are involved. But since few people remember to open and drain the tank it may be that the drain valve does not open easily, or worse, it won't close.

Check for heating oil leaks and oil piping defects: see OIL TANK PIPING & PIPING DEFECTS

If plastic water piping is installed, such as polybutylene water supply piping, it should be at least 18" from the water heater.

Vacuum relief valves are required at water heaters in some communities, to protect against collapse of the water storage tank and to prevent backup of hot water into the cold water piping should cold water pressure drop. Here is Carson Dunlop's sketch of a vacuum relief valve.

A Guide to Oil Fired Water Heater Controls & Operation

The principal controls on an oil fired water heater include the following water tank and oil burner parts and controls:

Check the Sacrificial Anode & Dip Tube of Your Oil Fired Water Heater Tank

Schematic of a sacrificial anode on a hot water tank (C) Carson Dunlop Associates

The dip tube on many water heaters functions as a sacrificial anode, as we show here.

By constructing the dip tube of a metal which is more readily corroded than the steel of a steel hot water tank, the anode protects the hot water tank from early failure due to corrosion.

Here Carson Dunlop's sketch shows the location of the sacrificial anode on an electric water heater.

If your water supply happens to be highly conductive or corrosivehen the dip tub/sacrificial anode in the water tank may indeed corrode away until it leaks (dropping the hot water temperature) or disappears entirely.

See WATER TESTING GUIDE

If your hot water smells like rotten eggs, you should definitely check the condition of the sacrificial anode on the hot water heater, no matter what kind of water tank you've got installed.

For details of how to inspect or replace the sacrificial anode or dip-tube on a water heater, please see Water Heater Anodes & Dip Tubes

Check the Oil-Fired Hot Water Tank Temperature and Pressure Safety Relief Valve

Please see Testing the Water Heater Temperature Pressure Relief Valve

How to Restore a Flood-Damaged Hot Water Heater To Save Service

Question: How do I get my oil fired water heater running again after building flooding?

Flood waters rising at Wappingers Creek (C) Daniel Friedman

I am having problems restarting the water heater ever since hurricane irene slammed into New Jersey and my basement flooded. We changed the motor and oil filter, but are having problems getting oil to feed through the lines I was wondering if there were suggestions. - Antoinette

Reply: recommended inspection & repair points for flooded oil fired water heaters, heating boilers, furnaces

When an oil fired water heater has been flooded, such as by hurricane Irene that flooded the Northeastern U.S. in August 2011, there are a number of concerns that need to be addressed.

Before addressing flooded water heaters, boilers, or furnaces, if your building has been flooded,
see FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP for advice about priorities of entry, diagnosis & repair of homes or other buildings after flooding from any cause.

Now to the flooded water heater: you report having taken two important post-flood steps by changing parts (motor and oil filter) but below we have listed suggestions that might help get the water heater (or a flooded heating boiler or furnace) running again and also assure its safety and forward life.

The extent of disassembly, inspection, and replacement of parts of any heating appliance (water heater, furnace, boiler) after building flooding depends on the height reached by floodwaters and perhaps also the duration of flooding. Our flood damage photo (above left) shows our client pointing to flood water markings on the heating system expansion tank - water had nearly filled the basement of this home - the heating boiler had been completely under water.

Certainly any component that was under-water or soaked needs to be inspected, and as appropriate, cleaned or replaced. On the other hand, basement flooding that did not even reach the level of the oil burner assembly may have left that component intact, but still may have entered and damaged the heating appliance combustion chamber.

We list some key post-flood inspection and repair points for water heaters, boilers, furnaces, just below.

What oil fired water heater parts are replaced after a building flood?

Chimneys & flues: In addition, a thorough inspection of the combustion chamber for damage and debris must be conducted before the equipment is returned to service. Mud, sludge, debris anywhere inside of the heating appliance (combustion chamber, heat exchanger, chimneys, flues) has to be removed and the appliance cleaned. In addition, if area flooding sent flood waters inside of chimneys or flues (don't forget the chimney base and cleanout door) those areas need to be opened, inspected, cleaned.

Combustion chamber & chamber liner: most oil fired water heaters use a masonry (fire brick) or synethetic fabric combustion chamber liner. The liner heats to very hot during oil burner operation - a condition that helps assure complete combustion of fuel oil being sprayed into the combustion chamber. Firing up a flooded oil fired heating appliance before the combustion chamber liner has been dried or replaced risks damaging that component and possibly damaging the heater itself. Ask your service technician about the condition of the combustion chamber.

Controls on heating appliances: heating appliance (water heater, boiler, furnace) safety and limit switches and controls that have been flooded, in our OPINION, should be replaced. Other electrical components such as electrical wiring may be re-usable after inspection. Electrical panels and circuit breakers that have been flooded should be replaced as even if they "look" fine, we're not confident that internal working parts have not been damaged by water, corrosion, or even silt and debris.

Heat Distribution: Ductwork: The inspection points listed above pertain to oil fired heating devices that have been exposed to flooding or sewer backups. In addition, for building heating systems, the heat distribution system may also have been flooded, damaged, or require repairs and cleaning.

See FLOOD DAMAGE in DUCT WORK for examples.

Oil burner assembly: First, you said that the "motor" was replaced. If you are not sure whether just the electric motor on the oil burner was replaced or whether the whole oil burner assembly was replaced, see OIL BURNERS for an illustration of the different parts involved. If the oil burner was submerged, and if only the oil burner's driving electric motor was replaced, additional disassembly and cleaning are probably in order to be sure that the oil burner nozzle, blower assembly, and other parts are clean and working properly.

Oil filter: it makes sense to replace an oil filter cartridge after a building has been flooded; the cartridge canister is normally air tight and thus water tight. But repair steps, movement of equipment, or other events may have contaminated the canister itself or oil tank or piping, sending more debris into the canister and filter. For this reason it makes sense to not just replace the filter, but inspect and clean the canister that holds the filter.

Oil pump (fuel unit) internal filter screen: Debris, sludge, water, rust particles are often found in the bottom of the oil filter canister. If these enter the oil burner's oil pump (properly, the fuel unit), its internal filter screen may also be clogged - I'd be sure that the fuel unit has had its filter screen replaced. Debris in the fuel unit will clog its internal check valves and the oil burner nozzle too, damaging the pump and leading to improper, even unsafe oil burner operation or total loss of heat later on. Also a clogged filter screen can prevent the fuel unit from being able to pump oil from the tank - and could be mistaken for a blocked oil line.

Oil piping: if oil piping has become contaminated with sludge, it may be possible to blow the lines clear, but if not, oil line replacement will be needed. Details about unclogging a blocked heating appliance oil line are found
at OIL TANK PIPING & PIPING DEFECTS

Water heater (or boiler or furnace) insulation: most heating appliances (water heaters, furnaces, boilers) include an insulated outer jacket or "skin" that helps keep heat and noise inside the device and that improve its operation. If the insulation on a flooded appliance is still wet when the appliance is turned back on you might get lucky and dry it out during the next operating cycle. Or equipment might be damaged, or the insulation might need replacement. Ask your service technician about the condition of the appliance insulating jacket.

Oil piping on flooded water heaters

Oil lines between an oil tank and the water heater can become blocked with sludge, silt, mud, and even water or sewage if the lines are open to the flooding environment. But normally an oil line between the oil tank and oil burner, say at a water heater, is always full of fuel oil, and sealed against oil leaks out and air leaks in to the piping system. So dirt or water from outside the system would not easily enter the piping system. Details about spotting oil or air leaks in oil piping are found at OIL LINE PIPING LEAKS and also at OIL FILTERS on HEATING EQUIPMENT. Other oil piping defects and oil line clogging are detailed at OIL TANK PIPING & PIPING DEFECTS.

Check the oil tank: So how might debris enter and clog oil piping after a building flood? If the oil tank itself were flooded you might have water and mud or silt and dirt on the tank bottom - if your oil line feeds from the tank bottom all of that crud would enter the oil line. So a further check of the condition of the oil tank is in order.

A buried oil tank should, like the oil piping, be sealed against outside water entry (though in times of area flooding a partially empty oil tank might float-up and break lines or cause leaks).

An above ground oil tank should be ok IF flood waters never rose high enough to enter the oil tank vent or fill piping.

If your oil tank itself checks out as not contaminated with water and dirt, and provided we are sure that the oil burner assembly was itself entirely replaced and that the oil pump (fuel unit) is working properly, and if you are unable to draw oil from the tank, the usual step employed by the service tech is to use a CO2 gas cartridge and special "gun" assembly that connects to the oil line and attempts to "blow out" an obstruction. If you are unable to make the line usable following that procedure, and provided we remain convinced that the line is the culprit, I'd have the service company run a new fuel line between the oil tank and the burner.

Check the oil supply valves: fusible link oil piping shutoff valves should be found at the oil burner (just before the oil filter) and perhaps also at the oil storage tank.

A valve at the oil tank is often used for service convenience if the oil piping exits at the tank bottom. If oil piping or the oil tank were open to floodwaters debris often collects right at the control valve.
See FIRE SAFETY CONTROLS for a discussion of oil piping fire safety valves.

Bleed the oil piping properly: Also be sure the service tech was following proper procedure for bleeding air out of the oil piping during service restoration.

...


Continue reading at OIL BURNER INSPECTION & REPAIR or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see WATER HEATERS

Or see OIL BURNER WONT RUN

Or see WATER HEATER PROBLEM DIAGNOSIS

Suggested citation for this web page

OIL FIRED WATER HEATERS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to PLUMBING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs