Mobile ViewWATER HEATERS AGE of WATER HEATERS AIRBOUND HEAT SYSTEM REPAIRS ALTERNATIVE HOT WATER SOURCES Electric Shower Heaters High Efficiency Water Heaters Indirect-fired Water Heaters Instantaneous Water Heaters Multiple water heaters in parallel Multiple water heaters in series Range Boiler Water Heaters Side Arm Coil Water Heaters Solar Water Heaters Tankless Coil for Hot Water Tankless Water Heaters ANODES & DIP TUBES on WATER HEATERS ANTI SCALD VALVES APPLIANCE EFFICIENCY RATINGS AQUASTAT CONTROL Functions BACKDRAFTING HEATING EQUIPMENT BACKFLOW PREVENTER VALVE, HEATING SYS BACKFLOW PREVENTER, HEATER WATER FEEDER BACKUP HEAT for HEAT PUMPS BLEVE EXPLOSIONS BOILERS, HEATING CARBON MONOXIDE - CO CHECK VALVES, WATER SUPPLY CHEMICAL CONTAMINANTS in WATER CHIMNEY INSPECTION DIAGNOSIS REPAIR CLOGGED DRAIN DIAGNOSIS & REPAIR CLOGGED SUPPLY PIPING CROSS CONNECTIONS, PLUMBING DEBRIS in WATER SUPPLY, Water Heater DRAIN a WATER HEATER TANK ELECTRIC WATER HEATERS Electric, Gas, Oil Water Heater Efficiency Electric Shower Heaters Electric Water Heater Checklist Electric Water Heater Controls List Electric Water Heater Element Replacement Electric Water Heater Element Tests Electric Water Heater High Temp Cutoff Test Electric Water Heater Repair Guide Electric Water Heater Reset Switch Electric Water Heater Thermostats Electric Water Heater No Hot Water Electric Water Heater Parts Identification Electric Water Heater Reset & Temp Set Hot Water Temperature & Pressure Valve Timers for Electric Water Heaters Water Heater Anode & Dip Tube Check ENERGY SAVINGS in buildings FLOODED HEATING EQUIPMENT REPAIR FLOODED WATER HEATER REPAIR FREEZE-PROOF A BUILDING FROST HEAVES, FOUNDATION, SLAB GALVANIC SCALE & METAL CORROSION GAS BURNER Flame & Noise Defects GAS FIRED WATER HEATERS DRAFT HOODS - gas fired Gas BTUH & Cubic Feet Gas Conversion LP Natural Gas GAS PIPING, VALVES, CONTROLS SOOT on OIL FIRED HEATING EQUIPMENT SPILL SWITCHES - Flue Gas Detection GAS PIPING, VALVES, CONTROLS HEAT TAPES, Heat, Insulation prevent Freeze-Up HEATING COST FUEL & BTU Cost Table HEATING COST SAVINGS METHODS HEATING SYSTEMS HOT WATER SUPPLY HOT WATER IMPROVEMENTS HOT WATER DELIVERY SPEED UP HOT WATER EFFICIENCY IMPROVEMENT HOT WATER PRESSURE EXPANSION RATE HOT WATER PRESSURE LOSS HOT WATER PROBLEM DIAGNOSIS HOT WATER QUANTITY IMPROVEMENT Alternative Hot Water Sources & Methods Anti-Scald Valves & Hot Water Quantity CLOGGED PIPING & Hot Water Flow Extra Tanks to Increase Hot Water Insulate Hot Water Piping Insulate Hot Water Tank? Larger Diameter Water Supply Piping Water pipe clog diagnosis Water pipe clog repair guide HYDROGEN SULFIDE GAS INDIRECT FIRED WATER HEATERS MANUALS & PARTS GUIDES - HVAC MIXING / ANTI-SCALD VALVES NO HEAT - NO HOT WATER: HEATER DIAGNOSIS NOISE / SOUND DIAGNOSIS & CURE NOISE CONTROL for HEATING SYSTEMS NOISE, PLUMBING CHECKLIST NOISE, WATER HEATER ODORS GASES SMELLS, DIAGNOSIS & CURE ODORS IN WATER OIL FIRED WATER HEATERS PIPING IN buildings, Clogs Leaks Types PLASTIC HEATER VENT RADIANT HEAT RANGE BOILERS RELIEF VALVES - TP Valves on Boilers RELIEF VALVES - Water Heaters RELIEF VALVES - Water Tanks SAFETY, HEATING INSPECTION SCALE REMOVAL, WATER HEATERS SEWER GAS ODORS SOLAR ENERGY SYSTEMS SOLAR HOT WATER HEATERS SOOT on OIL FIRED HEATING EQUIPMENT SPILL SWITCHES - Flue Gas Detection TANKLESS COILS AQUASTAT CONTROL Functions Clogged Pipes / Tankless Coil De-Scale MIXING / ANTI-SCALD VALVES Tankless Coil Conversions Tankless Coil Leaks Tankless Coil Hot Water Increase TANKLESS WATER HEATERS Electric Shower Heaters Guide to Tankless Water Heaters Operation & Characteristics Problems & Defects Hot Water Delivery Speedup Installation Requirements & Costs Should I Convert to a Tankless Heater? Calculate Water Heater Requirements Capacities of Tankless Water Heaters Life Expectancy & Applications Temperature Pressure Relief Valves - Water Heaters THERMOSTATS, HEATING / COOLING THERMOSTATS, WATER HEATER AQUASTAT CONTROL Functions Electric Water Heater Thermostats TIMERS for ELECTRIC WATER HEATERS VALVES, PLUMBING WATER CONTAMINANT LEVELS WATER HAMMER NOISE DIAGNOSE & CURE WATER HEATERS WATER HEATER ALTERNATIVES WATER HEATER ANODES, DIP TUBES WATER HEATER AIR INLET WATER HEATER DEBRIS FLUSH WATER HEATER DRAIN PROCEDURE WATER HEATER EFFICIENCY WATER HEATER FLUSH PROCEDURE WATER HEATER NOISES WATER HEATER PROBLEM DIAGNOSIS WATER HEATER PROPERTIES Electric, Gas, Oil Water Heater Efficiency Water Heater Life Expectancy Comparisons Water Heater Operating Cost Comparisons Water Heater Purchase & Maintenance Costs Water Heater Water Quantity Comparisons Water Heater Recovery Speed Comparisons Water Heater Safety Comparisons WATER HEATER EFFICIENCY WATER HEATER SCALE - De-Liming Procedure WATER HEATER SCALE PREVENTION WATER HEATER SAFETY WATER HEATERS for HOME HEATING USE? WATER ODORS, CAUSE CURE WATER PIPES, Clogs Leaks Types WATER PRESSURE & FLOW MEASUREMENT WATER PRESSURE VARIATION CAUSES WATER PRESSURE TOO HIGH: DANGERS Definition of Static Water Pressure Definition of Dynamic Water Pressure Measure Municipal Water Pressure Measure Pump & Well Water Pressure WATER FLOW RATE MEASUREMENT HOT WATER PRESSURE EXPANSION RATE WATER PRESSURE GAUGE ACCURACY WATER PRESSURE LOSS DIAGNOSIS & REPAIR WATER PRESSURE REDUCER / REGULATOR WATER PRESSURE REPAIR GUIDE - WELLS WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS WATER PUMPS & WELLS WATER PURIFIERS WATER QUALITY TESTS, CONTAMINANTS, TREATMENT WATER QUANTITY IMPROVEMENT WATER SOFTENERS & CONDITIONERS WINTERIZE A BUILDING More Information |
This article describes procedures for inspection and repair of flooded heating appliances: flooded heating boilers, furnaces, and water heaters. Area flooding due to storms or building flooding due to a fire or burst water pipe can leave heating appliances inoperative as well as unsafe to use unless adequate inspection, cleaning, and repair or replacement of certain parts are made. InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.This article series on oil hot water heat will answer most questions about oil-fired water heaters as well as many other building plumbing system inspection or defect topics. Our page top photos shows a client pointing to the level reached by flood waters in a building basement - the heating boiler, water heater, and other basement appliances had been inundated with muddy water from area flooding. © Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website. Flood Response: Inspection & Repair Advice for Flooded Oil-Fired Boilers, Furnaces, Water HeatersQuestion: How do I get my oil fired water heater running again after building flooding?I am having problems restarting the water heater ever since hurricane irene slammed into New Jersey and my basement flooded. We changed the motor and oil filter, but are having problems getting oil to feed through the lines I was wondering if there were suggestions. - Antoinette Reply: recommended inspection & repair points for flooded oil fired water heaters, heating boilers, furnaces
Before addressing flooded water heaters, boilers, or furnaces, if your building has been flooded, see FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP for advice about priorities of entry, diagnosis & repair of homes or other buildings after flooding from any cause. Now to the flooded water heater: you report having taken two important post-flood steps by changing parts (motor and oil filter) but below we have listed suggestions that might help get the water heater (or a flooded heating boiler or furnace) running again and also assure its safety and forward life. The extent of disassembly, inspection, and replacement of parts of any heating appliance (water heater, furnace, boiler) after building flooding depends on the height reached by floodwaters and perhaps also the duration of flooding. Our flood damage photo at the top of this page shows our client pointing to flood water markings on the heating system expansion tank - water had nearly filled the basement of this home - the heating boiler had been completely under water. Our oil fired water heater sketch (left, - Courtesy Carson Dunlop Associates, used with permission) shows the internals of that appliance and illustrates what gets wet at different flood water levels. Certainly any water heater, boiler,or furnace component that was under-water or soaked needs to be inspected, and as appropriate, cleaned or replaced. On the other hand, basement flooding that did not even reach the level of the oil burner assembly may have left that component intact, but still may have entered and damaged the heating appliance combustion chamber. We list some key post-flood inspection and repair points for water heaters, boilers, furnaces, just below. What oil fired water heater parts are replaced after a building flood?
Combustion chamber & chamber liner: most oil fired water heaters use a masonry (fire brick) or synethetic fabric combustion chamber liner. The liner heats to very hot during oil burner operation - a condition that helps assure complete combustion of fuel oil being sprayed into the combustion chamber. Firing up a flooded oil fired heating appliance before the combustion chamber liner has been dried or replaced risks damaging that component and possibly damaging the heater itself. Ask your service technician about the condition of the combustion chamber. Controls on heating appliances: heating appliance (water heater, boiler, furnace) safety and limit switches and controls that have been flooded, in our OPINION, should be replaced. Other electrical components such as electrical wiring may be re-usable after inspection. Electrical panels and circuit breakers that have been flooded should be replaced as even if they "look" fine, we're not confident that internal working parts have not been damaged by water, corrosion, or even silt and debris. Heat Distribution: Ductwork: The inspection points listed above pertain to oil fired heating devices that have been exposed to flooding or sewer backups. In addition, for building heating systems, the heat distribution system may also have been flooded, damaged, or require repairs and cleaning. See FLOOD DAMAGE in DUCT WORK for examples. Oil burner assembly: First, you said that the "motor" was replaced. If you are not sure whether just the electric motor on the oil burner was replaced or whether the whole oil burner assembly was replaced, see OIL BURNERS for an illustration of the different parts involved. If the oil burner was submerged, and if only the oil burner's driving electric motor was replaced, additional disassembly and cleaning are probably in order to be sure that the oil burner nozzle, blower assembly, and other parts are clean and working properly. Oil filter: it makes sense to replace an oil filter cartridge after a building has been flooded; the cartridge canister is normally air tight and thus water tight. But repair steps, movement of equipment, or other events may have contaminated the canister itself or oil tank or piping, sending more debris into the canister and filter. For this reason it makes sense to not just replace the filter, but inspect and clean the canister that holds the filter. Oil pump (fuel unit) internal filter screen: Debris, sludge, water, rust particles are often found in the bottom of the oil filter canister. If these enter the oil burner's oil pump (properly, the fuel unit), its internal filter screen may also be clogged - I'd be sure that the fuel unit has had its filter screen replaced. Debris in the oil burner fuel unit will clog its internal check valves and the oil burner nozzle too, damaging the pump and leading to improper, even unsafe oil burner operation or total loss of heat later on. Also a clogged filter screen can prevent the fuel unit from being able to pump oil from the tank - and could be mistaken for a blocked oil line. Oil piping: if oil piping has become contaminated with sludge, it may be possible to blow the lines clear, but if not, oil line replacement will be needed. Details are just below at Oil piping on flooded water heaters. Pressure temperature relief valve: this important safety device should be flushed and tested as per the manufacturer's instructions. Dirt or debris in the relief valve interior could prevent its proper operation or, more often, it can cause the valve to leak if it has not been adequately cleaned. See RELIEF VALVES - Water Heaters Water heater (or boiler or furnace) insulation: most heating appliances (water heaters, furnaces, boilers) include an insulated outer jacket or "skin" that helps keep heat and noise inside the device and that improve its operation. If the insulation on a flooded appliance is still wet when the appliance is turned back on you might get lucky and dry it out during the next operating cycle. Or equipment might be damaged, or the insulation might need replacement. Ask your service technician about the condition of the appliance insulating jacket. Oil piping on flooded water heaters Oil lines between an oil tank and the water heater can become blocked with sludge, silt, mud, and even water or sewage if the lines are open to the flooding environment. But normally an oil line between the oil tank and oil burner, say at a water heater, is always full of fuel oil, and sealed against oil leaks out and air leaks in to the piping system. So dirt or water from outside the system would not easily enter the piping system. Details about spotting oil or air leaks in oil piping are found at OIL LINE LEAKS. Other oil piping defects are detailed at OIL TANK PIPING & PIPING DEFECTS. Check the oil supply valves: fusible link oil piping shutoff valves should be found at the oil burner (just before the oil filter) and perhaps also at the oil storage tank. A valve at the oil tank is often used for service convenience if the oil piping exits at the tank bottom. If oil piping or the oil tank were open to floodwaters debris often collects right at the control valve. See FIRE SAFETY CONTROLS for a discussion of oil piping fire safety valves. A Guide to Oil Fired Water Heater Controls & Operation
Check the Sacrificial Anode & Dip Tube of Your Oil Fired Water Heater Tank
Check the Oil-Fired Hot Water Tank Temperature and Pressure Safety Relief ValvePlease see Testing the Water Heater Temperature Pressure Relief Valve Questions & Answers regarding this articleQuestions & answers about diagnosing & repairing oil fired heating equipment that has been subject to flooding or water damage Ask a Question or Search InspectAPediaHTML Comment Box is loading comments...