Photograph of a water pressure tank air volume controlHow to Eliminate the Air Volume Control (AVC)
Can I get rid of the air volume control completely?

  • AIR VOLUME CONTROLS, GET RID OF - CONTENTS: is it possible to eliminate the pesky air volume control and thus stop problems with hissing, leaks, or loss of air charge in the water pressure tank? Sure. But it requires replacing the bladderless water tank with an internal-bladder type tank. Be sure to remove the snifter valve in the well too if one is present.
  • POST a QUESTION or READ FAQs about how to repair the air volume control (AVC) used on water pressure tanks & controls
  • REFERENCES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Air volume control elimination:

this article explains how to get rid of the AVC or air volume control entirely. AVCs are required to maintain the air charge in a water pressure tank that does not use an internal bladder. By changing the water tank itself we can eliminate this control and its occasional issues.

But there are some things to watch out for, such as leaving old AVC controls in place (a snifter valve in the well?) where they no longer belong.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Getting Rid of the Air Volume Control Valve

Leaky air volume control (C) Daniel FriedmanInstall a water pressure tank that uses an internal bladder

If you convert from a non-bladder type water pressure tank to a water tank using an internal bladder, part of that installation will include the removal of any air volume control valves on the system, including an AVC that may be mounted on the well pump (above-ground jet pumps) or a hidden AVC that is found inside the well piping (submersible well pumps only).

Remove and Discard the Air Volume Control Valve

You can keep the older bladderless water pressure tank and still remove the AVC entirely, abandoning its automatic function, but if you continue to use a bladderless water pressure tank you will need to restore air into the tank from time to time using one of the other methods discussed in this article series:
See WATER TANK AIR, HOW TO ADD

If the the rusty, leaky air volume control valve does not work, can I just remove it?

The short answer is sure. Or if it's not leaking you can leave it in place, which is safer as it avoids disassembly and possible trouble sealing the fittings against water leaks. But if you abandon the air volume control you will occasional have to add air to the water pressure tank when the well pump starts to short cycleor turn on and off too often.
See WATER TANK AIR, HOW TO ADD to fix a short-cycling well pump
or
See SHORT CYCLING WATER PUMP to diagnose other causes of frequent water pump on-off cycling

In 40 years of messing with plumbing I've rarely found an old AVC that worked reliably for long in a residential application. The AVC at left (that round thing in the center of the photo) was found by Langdon who found it to be rusty, leaking, and not working. He replaced it.

An air volume control on a water pressure tank can be left in place but don't count on it to work. If the air volume control valve itself is leaking or fittings on its tubing leak, you may decide, as do many plumbers, to simply remove it.

Just screw in a pipe plug where it was mounted on the water tank, and a smaller (usually brass) plug may be needed at the point of connection of the other end of the copper tube if one was installed on your system.

(You'll have to turn off the pump and release water pressure and drain some water from the tank before replacing an AVC with a new one or with a pipe plug.)

In rare cases an air volume control may put too much air into a pressure tank -
see AIR DISCHARGE at FAUCETS, FIXTURES.

If your AVC is not working or has been removed, and if your water tank is a non-bladder type system, you'll need to use one of the other methods discussed here for adding air to your water tank when it's needed. Forget this method for maintaining the proper air charge in a water tank, except for the Leaky Air Volume Control tip below.

Remove old Air Volume Controls if Changing to an Internal Bladder Water Pressure Tank

Leaky air volume control (C) Daniel FriedmanWatch out: if you replace a bladderless water tank with a new pressure tank using an internal bladder, you do not want to leave old air volume controls in place.

Those controls will inject air into the water (that is inside the bladder) duplicating the role of the bladderless tank whose air charge is kept separate from the water in the tank.

A result of leaving old AVC components in place might be less water draw-down before the well pump has to run and also air discharge at faucets.

Look for and remove the following, not all of which may be present on your system:

...


Continue reading at WATER TANK REPLACEMENT or select a topic from the More Reading links or topic ARTICLE INDEX shown below.

or see WATER TANK BLADDERS


Suggested citation for this web page

AIR VOLUME CONTROLS, GET RID OF at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

More Reading

Green link shows where you are in this article series.

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

OR use the Search Box found below at Ask a Question or Search InspectApedia

...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman