InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

VENTILATION in BUILDINGS

AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR POLLUTANTS, COMMON INDOOR
AIR SEALING STRATEGIES
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
ANIMAL ODORS IN buildings
ATTIC LEAKS, CONDENSATION & MOLD

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BATHROOM VENTILATION
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING VENTILATION
CEILINGS, DROP or SUSPENDED PANEL
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COMBUSTION AIR for TIGHT buildings
COOLING LOAD REDUCTION by ROOF VENTS
CONDENSATION or SWEATING PIPES, TANKS
CONDENSATION on WINDOWS & SKYLIGHTS
CRAWL SPACES

DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DRYER VENTING

FIBERGLASS INSULATION
FIREPLACES & HEARTHS
FLAT ROOF MOISTURE & CONDENSATION
FORMALDEHYDE HAZARDS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING
GREENHOUSE / SUNSPACE GLARE

HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR HAZARDS TABLE
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION INSPECTION & IMPROVEMENT
INSULATION R-Values & Properties

LOG HOME GUIDE

MOISTURE CONTROL in BUILDINGS
MOLD: A COMPLETE GUIDE TO MOLD

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION

RADIANT BARRIERS
RADIANT HEAT
ROOF VENTILATION SPECIFICATIONS

SHEATHING, FOIL FACED - VENTS
SOFFIT VENTILATION
SOUND CONTROL in buildings
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL MASS in buildings
THERMAL TRACKING Indicates Heat Loss

VAPOR BARRIERS & AIR SEALING at BAND JOISTS
VAPOR BARRIERS & HOUSEWRAP
VAPOR CONDENSATION & BUILDING SHEATHING
VENTILATION in BUILDINGS

WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE DAMPERS
ZONE VALVES


More Information

Severe ice dams, eaves to ground in Poughkeepsie NYHow to Inspect Soffit Ventilation from the Attic
     

  • Guide to Inspecting Attic and Under-Roof Ventilation - soffit intake vent adequacy
    • How to Correct Inadequate Attic Venting to Stop Attic Condensation, Ice Dam Leaks, Attic Mold, & Roof Structure Damage
    • How to detect roof venting deficiencies, attic insulation defects, and attic condensation problems
  • Questions & Answers about attic moisture, condensation & ventilation: finding attic vent problems by inspecting from inside the attic
  • References

Click to Show or Hide Related Topics

  • ROOF VENTILATION SPECIFICATIONS - home
  • AIR & HEAT LEAKS
  • AIR CHANGE RATE ACH HEAT SAVINGS
  • AIR LEAK DETECTION TOOLS - home
  • ATTIC LEAKS, CONDENSATION & MOLD
  • ATTIC MOISTURE or MOLD
  • ATTIC VENTILATION
  • ATTIC CONDENSATION CAUSE & CURE
  • BASEMENT MOISTURE to ATTIC
  • BLOCKED SOFFIT INTAKE VENTS
  • BLOWER DOORS & AIR INFILTRATION
  • CATHEDRAL CEILING VENTILATION
  • COOLING LOAD REDUCTION by ROOF VENTS
  • FLAT ROOF MOISTURE & CONDENSATION
  • HEAT TAPES & CABLES on Roofs for Ice Dams
  • HEAT LOSS in BUILDINGS - home
  • HEAT RECOVERY VENTILATORS
  • HOT ROOF DESIGNS: Un-Vented Roof Solutions
  • HUMIDITY LEVEL TARGET
  • ICE DAM PREVENTION
  • ICE DAM CURE: Comparing Two Houses
  • INDOOR AIR QUALITY & HOUSE TIGHTNESS
  • RIDGE VENT, ATTIC INSPECTION
  • ROOF VENTILATION SPECIFICATIONS
  • Inspect Building Exterior - Roof Venting
  • ROOF VENTIILATION INTAKE-OUTLET RATIO
  • ROOF VENT LOCATIONS
  • ROOF VENT SOFFIT & RIDGE NEED
  • ROOF VENT if NO SOFFIT
  • ROOF VENT SOFFIT, CONTINUOUS
  • ROOF VENTING ENERGY SAVING DETAILS
  • ROOF VENTING NEEDED?
  • ROOF VENTING ENERGY SAVING DETAILS
  • ROOF VENTING NEEDED?
  • SKYLIGHT VENTILATION DETAILS
  • SOFFIT INTAKE BLOCKED
  • SOFFIT VENTILATION SPECS
  • UN-VENTED ROOF SOLUTIONS
  • VENTILATION in BUILDINGS - home
  • VENTILATION DESIGN PROBLEMS & SOLUTIONS
  • VENTILATION, WHOLE HOUSE STRATEGIES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

This article explains how to spot attic ventilation defects in the soffits or building eaves, as visible from the attic or building interior. This soffit venting discussion is part of "How to Correct Improper or Inadequate Attic or Under-Roof Ventilation in buildings", our discussion of "Attic Condensation". This article describes inspection methods and clues to detect roof venting deficiencies, insulation defects, and attic condensation problems in buildings. It describes proper roof ventilation placement, amounts, and other details.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Inspecting the Soffit or Eaves Vent System from the Attic - look for blockage

Inspecting in the building attic, we check to be sure that there is good air flow at the lower roof edges or "eaves". Even when we see apparent vents installed outside, such as soffit vent strips or perforated soffit covering material, the venting may be blocked or otherwise inadequate.

The cost to heat and cool a building is increased and the risk of an under-roof rot or mold problem is increased as well if the roof is not properly designed and vented.

For example, installing exit venting a the ridge without installing adequate intake venting at the building eaves will increase heat loss from the building during winter months. Warm air leaking into the attic or roof cavity from the building creates a convection current of rising air in the building.

When the convection current of warm moist air leaving at the ridge vent is unable to draw dry cool outdoor air into the under-roof space at the building eaves or lower roof edges, it tends to draw more heated air out of the living space.

Look for these insulation and ventilation defects a the building eaves or lower roof edges:

  • Inadequate or incomplete insulation in the attic floor or knee walls.

  • Insulation up tight against the roof decking - blocking air flow there, no air path along roof sheathing or decking

  • Intake venting at the roof eaves blocked by insulation - See Blocked Soffit Intake Vents

  • Intake venting at the roof eaves is only between some rafter pairs, not all rafter pairs - See Continuous Soffit Intake Venting Needed

  • Moisture stains from ice dam leaks or roof leaks, found on rafters and roof sheathing, particularly at the lower roof edges over a poorly-insulated or poorly-vented attic or cathedral ceiling

  • Bath vents or kitchen vents that spill moist air into the attic rather than directing it outdoors; vent fan ducts that are not insulated and that slope so that their interior condensate leaks back into the building.

  • Mold stains on roof sheathing or rafters in areas of inadequate ventilation and high moisture. See Inspect Attics for Moisture or Mold for more indications of attic moisture

Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Questions & answers or comments about attic moisture, condensation & ventilation: finding attic vent problems by inspecting from inside the attic

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • "Energy Savers: Whole-House Supply Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Supply_Vent.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11880?print
  • "Energy Savers: Whole-House Exhaust Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Exhaust.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11870
  • "Energy Savers: Ventilation [copy on file as /interiors/Energy_Savers_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Natural Ventilation [copy on file as /interiors/Energy_Savers_Natural_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Energy Recovery Ventilation Systems [copy on file as /interiors/Energy_Savers_Energy_Recovery_Venting.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11900
  • "Energy Savers: Detecting Air Leaks [copy on file as /interiors/Energy_Savers_Detect_Air_Leaks.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Air Sealing [copy on file as /interiors/Energy_Savers_Air_Sealing_1.pdf ] - ", U.S. Department of Energy
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • "Weather-Resistive Barriers [copy on file as /interiors/Weather_Resistant_Barriers_DOE.pdf ] - ", how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • ...

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.
  • ...

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com