InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
STRUCTURAL INSPECTIONS & DEFECTS

AGE of a BUILDING - how to determine
ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ASBESTOS LIST of PRODUCTS
ASBESTOS PHOTO GUIDE to Materials
ASBESTOS REMOVAL, Wetting Guidelines
ATTIC LEAKS, CONDENSATION & MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BARK SIDE DOWN on DECKS, TRIM, STEPS
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BARK SIDE DOWN on DECKS, TRIM, STEPS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION
BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CEILINGS, PLASTER, LOOSE HAZARDS
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CHINESE DRYWALL HAZARDS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE
CRAWL SPACES
  CRAWL SPACE DRYOUT PROCEDURES
  CRAWL SPACE GROUND COVERS
  CRAWL SPACE INSULATION RETROFIT
  CRAWL SPACE SAFETY ADVICE
  CRAWL SPACE VAPOR BARRIER
  CRAWLSPACE MOLD ADVICE
  MOLD CLEANUP by MEDIA BLASTING
  MOLD ON DIRT FLOORS
  SUMP PUMPS
CONDENSATION or SWEATING PIPES, TANKS
CONDENSATION on WINDOWS & SKYLIGHTS

DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

EARTHQUAKE DAMAGED FOUNDATIONS
EFFLORESCENCE, Salts & White / Brown Deposits
ELDERLY & VETERANS HOME SAFETY
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
ENGINEERED WOOD Flooring
EXTERIORS of buildings

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD
FLASHING MEMBRANES PEEL & STICK
FLASHING for METAL ROOFS
FLASHING ROOF WALL DETAILS
FLASHING ROOF-WALL SNAFU
FLASHING SIDING DETAILS
FLASHING WALL DETAILS
FLASHING WOOD ROOF DETAILS
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOOD DAMAGED FOUNDATIONS
FLOOD VENTS & FLOOD PORTS
FLOODS IN buildings-mold
FLOOR TYPES & DEFECTS
FOOTING & FOUNDATION DRAINS
FOUNDATION BULGE or LEAN MEASUREMENTS
FOUNDATION CRACKS & DAMAGE GUIDE
FOUNDATION WATERPROOFING

FRAMING DAMAGE, INSPECTION, REPAIR
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS
HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS
MOLD: A COMPLETE GUIDE TO MOLD
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CONSULTANTS/INSPECTORS
MOLD CULTURE TEST KIT VALIDITY
MOLD DETECTION & INSPECTION GUIDE
MOLD or INDOOR AIR EMERGENCY RESPONSE
MOLD EXPERT, WHEN TO HIRE
MOLD FAQ's
MOLD ODORS, MUSTY SMELLS
MOLD PREVENTION GUIDE
MOLD RELATED ILLNESS GUIDE
MOLD SAFETY WARNINGS
MOLD SPRAYS, SEALANTS, PAINTS
MOLD STANDARDS
MOLD TEST KITS for DIY MOLD TESTS
MOLD TESTING METHOD VALIDITY

NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PLASTER BULGES & PILLOWS
PLASTER, LOOSE FALL HAZARDS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SAFETY HAZARDS & INSPECTIONS
SEARS KIT HOUSES
SINKHOLES, WARNING SIGNS
SINKING BUILDINGS
SLAB CRACK EVALUATION
SOUND CONTROL in buildings
Splits in Structural Wood Beams
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAIN DIAGNOSIS on ROOFS
STAIN DIAGNOSIS on STONE
STAINS on INDOOR SURFACES: PHOTO GUIDE
STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STONE VENEER WALLS
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

TERMITES, ROT
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING Indicates Heat Loss
TRUSS UPLIFT, ROOF
TRUSSES, Floor & Roof

VAPOR BARRIERS & CONDENSATION in BUILDINGS
VENTILATION in buildings
VINYL Siding or PLASTIC Window ODORS in buildings
VINYL CHLORIDE HEALTH INFO

WALL FINISHES INTERIOR

WATER ENTRY in buildings
  ATTIC LEAKS Moisture or Mold
  BARRIERS, EXTERIOR WATER
  BASEMENT De-Watering Systems
  BASEMENT CEILING VAPOR BARRIER
  BASEMENT LEAKS, INSPECT FOR
  BASEMENT WATERPROOFING
  BASEMENT WATER ENTRY PREVENTION
  CATCH BASINS
  Chimney Leaks
  CONDENSATION or SWEATING PIPES, TANKS
  CONDENSATION on WINDOWS & SKYLIGHTS
  CORROSION in ELECTRICAL PANELS
  CRAWL SPACE DRYOUT PROCEDURES
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  DRYER VENTING
  DRYWELLS, FRENCH DRAINS for FLAT SITES
  DRYWELL DESIGN & USES
  EFFLORESCENCE, Salts & White / Brown Deposits
  EXTERIOR WATER SOURCE ELIMINATION
  FLOOD Damage Assessment & Repairs
  FLOOD DAMAGED FOUNDATIONS
  FLOOD VENTS & FLOOD PORTS
  FLOODS IN buildings-priorities
  FOOTING & FOUNDATION DRAINS
  FOUNDATION DRAINS, INTERIOR
  FOUNDATION WATERPROOFING
  GEOTEXTILES & DRAINAGE MATS
  GRADING & SITE WORK, EXTERIOR
  GUTTERS & DOWNSPOUTS
  HUMIDITY CONTROL & TARGETS INDOORS
  HOUSEWRAP AIR & VAPOR BARRIERS
  LOG HOME Leak Diagnosis & Cure
  LOG HOME Condensation &Moisture
  MOISTURE CALCULATIONS
  MOISTURE CONTROL in BUILDINGS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  MOLD in buildings
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  ROOF VENTILATION SPECIFICATIONS
  Soffit Intake Vents & Attic Condensation
  SEALERS, Basement Floor & Wall Moisture
  SEWAGE CONTAMINATION
  SITE & SURFACE DRAINAGE
  SUMP PUMPS GUIDE
  SWEATING (CONDENSATION) on PIPES, TANKS
  VENTILATION in BUILDINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES
  WATER ENTRY in BUILDINGS
  WET BASEMENT PREVENTION
  WINDOW / DOOR AIR LEAK SEALING HOW TO
  Window Flashing & Sealing Guide
  WINDOW LEAKS INTO BASEMENT
  SITE & SURFACE DRAINAGE
  SUMP PUMPS GUIDE
  SWEATING (CONDENSATION) on PIPES, TANKS
  VENTILATION in BUILDINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES
  WATER ENTRY in BUILDINGS
  WET BASEMENT PREVENTION
    Wet Conditions - Foundation Collapse
    Living With a Basement that Floods
    Steps to Prevent Basement Water Entry
    Soil Testing
    Water Entry Priorities
    Foundation Waterproofing, Bentonite
    Foundation Waterproofing, Crack Sealants
    Foundation Waterproofing, Geotextiles
    Foundation Waterproofing Sealers
    Foundation Footing Drain Details
    Foundation Drainage Backfill Details
    Finish Grading
    Repairs Cure Basement Leaks
    PERIMETER DRAIN SYSTEMS
    SITE & SURFACE DRAINAGE
  WINDOW / DOOR AIR LEAK SEALING HOW TO
  Window Flashing & Sealing Guide
  WINDOW LEAKS INTO BASEMENT
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING

WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

Evidence of a wet basement from roof spillage How to Seal Basement Floors & Foundation Walls Against Water & Moisture
InspectAPedia®  -      

  • Basement waterproofing guide to choices of sealants, membranes, drainage systems, basement de-watering systems, sump pumps
  • Description of various basement waterproofing paints, coatings, sealants
  • How basement water may show up in a building attic
  • Questions & answers about using sealers to waterproof basement walls - an attempt to control basement moisture & water entry leakage

Basement sealers to control moisture & water entry: this article discusses options for sealing basement or crawl space floors and walls, or other building foundation walls to stop water entry and to reduce interior moisture and mold risks. The photograph at page top shows a very wet basement foundation wall built of concrete block. The stain pattern extends high on the basement walls, down the full wall, onto the basement floor. Correcting this particular water entry problem should begin outside with roof drainage and surface runoff. This article discusses foundation wall and floor slab sealant options. .

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Basement Waterproofing Using Sealers for Concrete Floors & Masonry Foundation Walls

Aaron Kuertz, Applied Technologies, Inc.

Illustration of basement waterproofing options (C) InspectApedia and Applied Technologies Inc Aaron Kuertz

Details about water barrier coverings for foundations are at WATER BARRIERS, EXTERIOR BUILDING and FOUNDATION WATERPROOFING and also GEOTEXTILES & DRAINAGE MATS. See WET BASEMENT PREVENTION for a description of the critical steps to prevent basement water entry and foundation leaks. Also see BASEMENT LEAKS, INSPECT FOR for articles on diagnosing building water entry, and see CRAWL SPACE Dryout Procedures.

Basement Concrete and Concrete Block Sealers for Basement Waterproofing

Basements are below grade and surrounded by soil.  This soil absorbs water during rains and then releases it.  The water can migrate through a block basement and even through solid concrete such as in walls and floors by capillary action. 

This water that enters the basement can cause problems ranging from peeling paint to mold and mildew growth.  Also, naturally occurring gasses that are released from soils can be transmitted into the basement.  The interior basement air quality is lessened unless the walls and floors are sealed.

It is possible to seal the concrete or concrete blocks used in basement walls and floors and stop water and gas migration into a basement.  In fact, it can be done from the interior of a home.  Old homes and new homes alike can be sealed.

Using Exterior Foundation Coatings to Repair Foundation Wall Cracks & Leaks

Foundation wall crack repair and seal from outside (C) Carson Dunlop AssocAs Carson Dunlop Associates' sketch shows, foundation crack leaks can be repaired from outside the foundation wall using a combination of asphalt-mopped dampproofing and a waterproof bituminous membrane that is then adhered to the wall surface.

Sodium Silicate Sealers for Floor & Foundation Wall Waterproofing

Sodium silicate is used in a water-based mixture to seal the basement walls and floors. 

The sodium silicate penetrates up to 4” into the substrate. 

After penetrating the sodium silicate reacts with the free lime content of the concrete or masonry .  Concrete, concrete block and masonry has lime as a natural component in their composition. 

This reaction between the sodium silicate and free lime produces a solid crystalline structure that fills the microscopic cracks and pores of the substrate.  This hardens and densifies the concrete and masonry so that water vapor and gasses cannot migrate through by capillary action.  Also, gasses are retarded from entering a basement.  After curing, the substrate looks the same as if it were not sealed.  There is no surface film or sheen to it.

Benefits of Sodium Silicate for Building Waterproofing

By sealing the basement walls and floors with sodium silicate water vapor will be stopped from entering into a basement.  The basement will be dryer than before.  This greatly improves the interior air quality of a home by retarding the growth of mold and mildew. 

Since the surface of the walls and floors are hardened, they will have less dusting and chalking.  Gas transmission will be reduced as well, further improving air quality.

Many people like to paint the floors and walls of their basements.  If paint is applied to unsealed walls and floors, it is possible for the water vapor to get trapped under the paint.  After a period of time the water vapor can break the bond between the paint and the substrate.  This causes the paint to blister and peel.

After application of a sodium silicate the walls and floors can be painted without fear of the paint peeling and flaking.  Also, adhesives for tiles or other floor coverings can be used.

Application of Sodium Silicate for Basement or Crawl Space Waterproofing

Sodium silicate is applied to bare concrete, concrete block or masonry.  Anything that would prevent the sodium silicate from being absorbed must be removed.  No grease, dirt, soil, adhesives, oil, sealer or paint can be on the surface to be sealed prior to application.

Application is done simply by using a garden sprayer, roller or brush.  First dampen  the surface with water using a mop or brush.  Apply in areas 10’ x 10’ in several light coats.  Apply each coat after 10-20 minutes.  Concrete takes 2-3 coats, concrete block and masonry 3-4 coats.  Do not over apply the sodium silicate since if all of the product is not  absorbed it may leave a white residue.  Wipe up any excess product.

For several days after application loose dirt will be pushed out of the substrate.  This is normal and can be swept off.

A Few Caveats about Any Foundation Sealer or Weather Barrier Product - DF OPINION

Watch out: any surface coating, even a penetrating wall sealer such as discussed here, can fail if exposed to continued or chronic water and water pressure through the foundation wall.

The pressure from water, frost, or more significantly, the formation of efflorescent salts (see EFFLORESCENCE, Salts & White / Brown Deposits) can exert tremendous pressure, sufficient to separate a paint or other coating from a masonry foundation surface. Efflorescence has been cited in several paint failure studies where these forces were explored.

Some factors that affect the durability and thus success of any foundation coating or waterproofing coating include:

  • The cleanliness of the surface to which the coating is applied
  • Application of the sealer according to the manufacturer's instructions, including specifications of pre-cleaning, thickness, temperature, humidity at time of application
  • The degree of water intrusion or water presence on the exterior of the foundation wall
  • Climate, freezing temperatures
  • Chemistry of both the masonry wall and the water, affecting the formation of efflorescence
  • Chemistry, composition, and in some cases fiber reinforcement of the coating

Watch out: sodium silicate is an alkaline substance that can cause burns, eye, and skin damage. Quoting from a MSDS:

Causes moderate skin irritation. Spray mist causes irritation to respiratory tract. Due to high pH of
product, release into surface water is harmful to aquatic life. ... Causes severe irritation to the eyes. ... Causes moderate irritation to the skin. ... Spray mist irritating to respiratory tract. ... May cause irritation to mouth, esophagus, and stomach. ... No known chronic hazards. Not listed by NTP, IARC or OSHA
as a carcinogen. ... Dries to form glass film which can easily cut skin. Spilled material is very slippery. Can etch glass if not promptly removed.
...
Human experience indicates that skin irritation occurs, particularly, when sodium silicates get on clothes at the collar, cuffs or other areas where contact and abrasion may occur. The acute oral toxicity of this product has not been tested.
- MSDS for Sodium Silicate from PQ Corporation

Also see this MSDS for Krystol Hydrostop WB [copy on file as /exterior/Krystol-hydrostop-wb.pdf ] - WB from Kryton Corporation.

Thanks to reader Stan Rosenbaum for alerting us to the need for care when working with sodium silicate.

Weather Barrier Coatings, Mastics, Sealants, Adhesives used on buildings, Building Sheathing & Building Foundation Coatings

AkroGuard, Omega Products, International, 1681 California Ave, Corona, CA 92881, Tel: 800-600-6634, 951-737-7447, Fax: 951-520-2594, Quoting from the company's product description:

AkroGuard is a field applied, non-cementitious, [acrylic] flexible coating that when used with AkroFill creates a water-resistive barrier over approved substrates.

Basic Uses: AkroGuard is designed for use as a water-resistive barrier and air barrier over approved substrates and with the AkroFlex EIF Systems. Complies with ICC-ES Acceptance Criteria for Water-resistive Coatings (AC212).

AkroGuard may be applied to the following substrates:

  • Gypsum sheathing
  • Fiber-faced gypsum sheathing
  • Wood-based sheathing
  • CMU/Poured-in-place and/or tilt-up concrete/masonry
  • Cement board

Thanks to reader J. Campbell for pointing out this product, March 2010.

Krystol Hydrostop, Kryton Corporation, "Crystalline Waterproofing" masonry sealer. MSDS for Krystol Hydrostop WB [copy on file as /exterior/Krystol-hydrostop-wb.pdf ] - WB from Kryton Corporation. Masonry sealer.

  • Krystol T1 and T2 waterproofing system is brush-applied onto concrete surfaces to become an integral part of the concrete. It contains Kryton's renowned waterproofing chemicals and is durable and self-sealing.

Vi-Cryl CP-10 (Trowel Grade) & Vi-Cryl CP-11 (Spray/Brush) Weather Barrier Coatings, Childers Corporation. We discuss the use of this coating at INSULATION LOCATION for BASEMENT WALLS. Quoting from the company's product literature [copy on file as /exterior/Vi_Cryl_cp-10-11.pdf ] - ,

VI-CRYL CP-10/11 weather barrier coating is unsurpassed for the mechanical protection and weatherproofing of thermal insulations both outdoors and indoors, in hot, cold, and dual-temperature service. However, since it is a ‘breathing’ coating (vapors under pressure will pass through it) it should only be used over insulations in lowtemperature, or dual-temperature service when the insulations themselves are vapor barriers.

VI-CRYL CP-10/11 has also found use throughout the thermal insulation industry as a coating used over closed cell polyethylene and polyurethane foam insulations. Industry experience has demonstrated that all weather barrier coatings may blister when applied over polystyrene board. This effect may be limited by the use of white colored coatings.

VI-CRYL CP-10/11 weather barrier coating in its Metallic Gray color is the ideal companion product to Aluminum and Stainless Steel Jacketing. VI-CRYL CP-10/11 gives superior mechanical and chemical protection to any irregular shape or surface where the application of Childers Metal Jacketing Systems is impractical.

Also see INSULATION LOCATION for BASEMENT WALLS,

see WET BASEMENT PREVENTION for our complete list of basement dry-out or water entry prevention methods.

 

Questions & Answers regarding this article

Questions & answers about using sealers to waterproof basement walls - an attempt to control basement moisture & water entry leakage

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

  WET BASEMENT PREVENTION
    Wet Conditions - Foundation Collapse
    Living With a Basement that Floods
    Steps to Prevent Basement Water Entry
    Soil Testing
    Water Entry Priorities
    Foundation Waterproofing, Bentonite
    Foundation Waterproofing, Crack Sealants
    Foundation Waterproofing, Geotextiles
    Foundation Waterproofing Sealers
    Foundation Footing Drain Details
    Foundation Drainage Backfill Details
    Finish Grading
    Repairs Cure Basement Leaks
    PERIMETER DRAIN SYSTEMS
    SITE & SURFACE DRAINAGE

  • Aaron Kuertz is with Applied Technologies, Fairfield, OH  45018, 877-APPLY-IT (277-5948). (513) 939-3767. Mr Kuertz has been in the waterproofing industry since 1998.  Applied Technologies is a manufacturer of waterproofing products used by both professional contractors and homeowners alike.  For more information on Hydra Block™ water-based concrete and masonry penetrating sealer used for concrete and concrete block basement sealing, see Applied Technologies at www.appliedtechnologies.com
  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Kryton Corporation, 1645 Kent Ave., Vancouver BC Canada VSP 2S8 - 604-324-8280 email: info@kryton.com
  • PQ Corporation, P.O. Box 840. Valley Forge, PA 19482-0840, is a producer of sodium silicate. Quoting:
    PQ Corporation is a leading producer of silicate, zeolite, and other performance materials serving the detergent, pulp and paper, chemical, petroleum, catalyst, water treatment, construction, and beverage markets. It is a global enterprise, operating in 19 countries on five continents, and along with its chemical businesses, includes Potters Industries, a wholly owned subsidiary, which is a leading producer of engineered glass materials serving the highway safety, polymer additive, metal finishing, and conductive particle markets.
  • Thanks to reader Stan Rosenbaum for discussing sodium silicate hazards - June 2010
  • Childers Corporation, Specialty Construction Brands, Inc., producer of Vi-Cryl [copy on file as /exterior/Vi_Cryl_cp-10-11.pdf ] - water based vinyl-acrylic mastic coating for thermal insulation, 315 South Hicks Rd., Palatine IL 60067 800-231-9541 or 800-338-2975

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Asbestos: How to find and recognize asbestos in buildings - visual inspection methods, list of common asbestos-containing materials
  • Asbestos products and their history and use in various building materials such as asphalt and vinyl flooring includes discussion which draws on Asbestos, Its Industrial Applications, D.V. Rosato, engineering consultant, Newton, MA, Reinhold Publishing, 1959 Library of Congress Catalog Card No.: 59-12535 (out of print).
  • Asbestos Identification and Testing References
    • Asbestos Identification, Walter C.McCrone, McCrone Research Institute, Chicago, IL.1987 ISBN 0-904962-11-3. Dr. McCrone literally "wrote the book" on asbestos identification procedures which formed the basis for current work by asbestos identification laboratories.
    • Stanton, .F., et al., National Bureau of Standards Special Publication 506: 143-151
    • Pott, F., Staub-Reinhalf Luft 38, 486-490 (1978) cited by McCrone
  • Fiberglass: Indoor Air Quality Investigations: Health Concerns About Airborne Fiberglass: Fiberglass in Indoor Air from HVAC ducts, and Building Insulation
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • How to Clean Moldy Wood Framing & Sheathing How to clean/seal mold from/on exposed lumber or plywood subfloor or roof sheathing indoors - some suggestions based on our field and laboratory research
  • How to Find and Test For Mold in buildings A "how to" photo and text primer on finding and choosing the right spots to test for mold in buildings
  • Stuff that is not mold but is often mistaken for it - things you may not want to test. Also, not all "black mold" is toxic - here are examples of harmless black mold.
  • Mold-Resistant Building Practices, advice from an expert on how to prevent mold after a building flood and how to prevent mold growth in buildings by selection of building materials and by anti-mold construction details.
  • "Weather-Resistive Barriers [copy on file as /interiors/Weather_Resistant_Barriers_DOE.pdf ] - ", how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com