InspectAPedia®

Foundation insulation, above ground, Maine © Daniel Friedman How to Calculate Building Heat Loss Rate, Insulation Values & Heating Efficiency

  • HEAT LOSS R U & K VALUE CALCULATION - CONTENTS: How to calculate the rate of heat loss (or gain) in a building through insulation, walls, etc.How to measure heat transmission in materials: definition of R-values, U-values, K-values, BTU, calorie, and rates of heat loss or gain. Building design temperatures & how to use a home energy audit or heat loss analysis. What insulation "R" values should be used in a building insulation?
  • POST a QUESTION or READ FAQs about how to calculate building heat loss rate, R-values, Insulation Values, Heating Efficiency
  • REFERENCES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

How to calculate building heat loss rates R, U and K.

This article gives details and formulas for calculating R-values, U-values U-coefficient of heat loss resistance, and K-values, all ways of looking at insulation values or building heat loss rates.

Our page top photo of above-ground building perimeter & foundation insulation using styrofoam board was observed at a home Maine - Ed.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Definition of & How to Calculate the R value or R-coefficient of Resistance to Heat Loss in a Building or its Insulation

Infrared scan of attic hatch (C) D Friedman S Bliss PEPThe "R" value of a material is defined as the material's resistance to heat flow through the material. For purposes of insulation, you might think of "R" value as the opposite of thermal conductance, since it's described as thermal resistance or resistance to heat flow. And you'd be correct. If thermal resistance to heat flow is "resistance" we can say that the thermal conductivity of a material is equal to the reciprocal of its thermal resistance.

More practically, by convention we use thermal resistance or R-value when buying various insulation materials. You will almost always see an "R" value quoted for the material. In general, higher "R" means more resistance to heat loss and therefore lower heating or cooling bills for the building. [Assuming all other fadctors like air leakage are either equal or have been factored into the R-value calculation.]

Mathematically, but in painfully circular reasoning, "R-value" is simply the reciprocal of the two measures of resistance to heat flow "K-value" (R = 1/K) or "U-value" (R(whole building) = 1/U) that we define further below.

What do U and K values have to do with R-values?

As you'll read below "K" measures the heat flow through an individual substance and "U" as most folks use it measures the overall building heat loss by adding all of the various areas and substances together. U-values measure the thermal transmittance of heat in or out of a building and combines heat movement by all principles that are occurring at a building: radiation, convection, and conduction. So you can see that "U" values are more complex but really more complete than "R" values.

Escaping the Circular Reasoning of R=1/K

We can escape the horrible circular reasoning that appears in some writing about heat loss measurements if any one of the three values, R, U, K is defined independently. We'll take a stab at this just below.

The R-value of a material is typically expressed as R [resistance to heat flow] per inch of material thickness. More technically, "R-value" is measured in mete Watt [metric system] or h/Btu [U.S. measurement system].

Materials may be rated in R per inch or R per meter or similar measures.

Here are Some Basic Formulas for Calculating R-Values

R-value = temperature difference [in degF] x area [sq ft] x time [in hours] / heat loss[in BTUs]

Calculating R-Value [U.S. metrics]

R = (Heat Resistance x Degrees F x square feet) / BTUs

or stated in metric: (R-value) = t/k, measured in [editing needed]

Definition of & How to Calculate the U value or U-coefficient of heat loss resistance

Computing "K" values tells us the heat loss rate for a specific material, thickness, area, and temperature difference but while we need to be able to calculate "K" values, those alone don't tell us what's going on in an actual building. We need to be able to combine all of the rates of heat loss (or gain) across all of the types of surfaces, insulation, and building material for the whole building - at least for all of its external or perimeter surfaces including roofs, walls, and floors as well as windows and doors. That's where the "U" value makes its appearance.

A building's "U" value or U-coefficient of resistance of heat loss is a related measure of resistance to thermal energy or heat flow out of a building (if it's warmer inside than outside) or conversely the same concept works in a warm climate where air conditioning is in use, except that we expect outside heat to be flowing into the building.

A building's "U" value is much more complete, and therefore useful than "K" values alone because a building's "U" value combines the "K" factors for all of the building's surfaces and materials. In other words, we add the effects of heat loss (or gain), still expressed in the number of BTU's per hour per square foot of area, and still expressed per degree of Fahrenheit of temperature difference and still expressed per inch of thickness of material (just as with "K" values), for all of the substantial areas and surfaces of the exterior of a building's floors, walls, windows, doors, ceilings, or roofs (if cathedral ceilings are present).

To calculate the "U" value, or overall heat loss (or gain if we're air conditioning) for a building, we need to add the "R" values for each material in the structure, and to factor in the total area of each material in the structure. We discuss this procedure in more detail below at "Calculating Heat Loss for a Building".

U-value = BTUs / (hours x Degrees F x Square Feet)

A building's "U" value or U-coefficient of resistance of heat loss is a related measure of resistance to thermal energy or heat flow out of a building (if it's warmer inside than outside) or conversely the same concept works in a warm climate where air conditioning is in use, except that we expect outside heat to be flowing into the building.

A building's "U" value is much more complete, and therefore useful than "K" values alone because a building's "U" value combines the "K" factors for all of the building's surfaces and materials. In other words, we add the effects of heat loss (or gain), still expressed in the number of BTU's per hour per square foot of area, and still expressed per degree of Fahrenheit of temperature difference and still expressed per inch of thickness of material (just as with "K" values), for all of the substantial areas and surfaces of the exterior of a building's floors, walls, windows, doors, ceilings, or roofs (if cathedral ceilings are present).

To calculate the "U" value, or overall heat loss (or gain if we're air conditioning) for a building, we need to add the "R" values for each material in the structure, and to factor in the total area of each material in the structure. We discuss this procedure in more detail below at "Calculating Heat Loss for a Building".

Formulas Used to Calculate the Rate of Building Heat Loss Per Hour for a Building Using it's "R" Values or "U" Values

Formulas and an explanation of how we use R U or K values to determine the rate of heat loss at a building (or heat gain if we are cooling it) are at HEAT LOSS in BUILDINGS or within that articler at section Formulas to Calculate the Rate of Heat Loss Per Hour for a Building Using it's "R" Values or "U" Values.

Definition of & How to Calculate the K value or K-coefficient of heat transmission

A building's K value or K-coefficient of heat transmission is one way to express the heat loss in a building. "K" is defined as the number of BTU's of heat moving through any material with these details:

So "K" takes a lot of variables into consideration and gives us the rate of heat loss per square foot of building surface, per inch of thickness of material in that building surface, per degree of temperature difference in Fahrenheit, in BTUs per hour.

By "degree of temperature difference in Fahrenheit" we mean that we are taking into consideration the difference in temperature on the two sides of our building surface. For example, if the indoor temperature in a building is 68 deg. F. and the outdoor temperature is 48 deg. F., then we have a 20 degree temperature difference on the two sides of the building (wall or roof for example).

This temperature difference on the two sides of a surface, say an insulated building wall, for example, is very important in understanding how a building loses heat (in the heating season) or gains heat (in the cooling season). That's because the rate of heat transfer through a material increases exponentially as a function of the temperature difference. This is intuitively obvious and is confirmed by physicists.

For example, if the temperatures on either side of a building wall were the same, there would be no heat loss or gain through the building wall. As the temperature difference on either side of that same wall increases, say from one degree of difference to 20 degrees of difference the rate of heat transfer increases.

An interesting version of this heat transfer theory was shared with the author in a class on how to minimize building heating costs when the instructor told us that "the thermal conductivity of finned copper heating baseboard is exponentially greater at higher temperatures".

He was saying that if we ran heating water from our heating boiler through the baseboards at 200 deg.F. we would see much more efficient heat transfer from the heating baseboards into the building. There are other factors involved in heating system efficiency such as the length of boiler on cycle (longer is more efficient), so there was more to think about, but the instructor was applying classic heat transfer theory that is reflected in the "K" values of building insulation as we've discussed here.

Computing "K" values tells us the heat loss rate for a specific material, thickness, area, and temperature difference but while we need to be able to calculate "K" values, those alone don't tell us what's going on in an actual building. We need to be able to combine all of the rates of heat loss (or gain) across all of the types of surfaces, insulation, and building material for the whole building - at least for all of its external or perimeter surfaces including roofs, walls, and floors as well as windows and doors. That's where the "U" value makes its appearance.

Sorting out the Definitions of U.S. k-values, lambda or values, and European k-values

Note: In the U.S. k-value when discussing the heat loss resistance of window glazing is equivalent to lamdavalue in Europe, and in case that's not confusing enough, an older European k-value (the total insulation value of a building) is currently referred to in Euripe as U-value. You'll recall from our notes above that U-value is a reciprocal or 1/R-value. - Wikipedia web search 03/11/2011 see "Thermal Conducitivity".

To convert U.S. R-values to European U-values:

[ (1 / R-value USA) x 0.176 ] / 1 = U Europe

and

U Europe = [watts / kelvin x meters2]

 

Beginning at HEAT LOSS in BUILDINGS article series explains how to insulate a building and how much insulation is needed including how to measure or calculate heat loss in a building, defines thermal terms like BTU and calorie, provides measures of heat transmission in materials, gives desired building insulation design data, and shows how to calculate the heat loss in a building with R values or U values

Formula-R™ and Owens Corning™ which may be visible in this photograph of pink Styrofoam™ insulation boards are registered trademarks of Owens Corning® and were photographed at a Home Depot® building supply center.

Energy Savings Articles

...


Continue reading at HEAT LOSS RATE CALCULATIONS or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see INSULATION INSPECTION & IMPROVEMENT - home

Suggested citation for this web page

HEAT LOSS R U & K VALUE CALCULATION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING ENERGY SAVINGS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Questions & answers or comments about how to calculate building heat loss rate, R-values, Insulation Values, Heating Efficiency.

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman