InspectAPedia ® Home HEATING SYSTEMS AFUE DEFINITION, RATINGS AGE of AIR CONDITIONERS & HEAT PUMPS AGE of HEATERS, BOILERS, FURNACES AIR CONDITIONING & HEAT PUMP SYSTEMS AIR FILTERS for HVAC SYSTEMS AIR HANDLER / BLOWER UNITS AIRBOUND HEAT SYSTEM REPAIRS ANODES & DIP TUBES on WATER HEATERS ANTIFREEZE for BOILERS ANTI SCALD VALVES APPLIANCE EFFICIENCY RATINGS ASBESTOS IDENTIFICATION IN buildings BACKDRAFTING HEATING EQUIPMENT BACKFLOW PREVENTER VALVE, HEATING SYS BACKFLOW PREVENTER, HEATER WATER FEEDER BACKUP HEAT for HEAT PUMPS BAROMETRIC DAMPERS BASEBOARD HEAT BIOGAS PRODUCTION & USE BLEVE EXPLOSIONS BLOWER DOORS & AIR INFILTRATION BLOWER FAN CONTINUOUS OPERATION BLOWER FAN OPERATION & TESTING BLUE vs YELLOW COMBUSTION FLAMES BLUERAY Recall BOILERS, HEATING BOILER CHEMICAL TREATMENTS BOILER COMPONENTS & PARTS BOILER CONTROLS & SWITCHES BOILER LEAKS CORROSION STAINS BOILER LEAKS, HOW TO LOCATE BOILER NOISE SMOKE ODORS BOILER OPERATING PROBLEMS BOILER OPERATION DETAILS BOILER PRESSURE & TEMPERATURE SETTINGS BOOKSTORE - InspectAPedia BTU USAGE MONITORS BUILDING SAFETY HAZARDS GUIDE CAPACITORS for HARD STARTING MOTORS CARBON DIOXIDE - CO2 CARBON MONOXIDE - CO CHEMICAL TREATMENTS for BOILERS CHIMNEY INSPECTION DIAGNOSIS REPAIR CHIMNEYS & Flues - Asbestos Transite Pipe CHINESE DRYWALL HAZARDS CIRCULATOR PUMPS & RELAYS COOL OFF HEAT, Thermostat Switch COMBUSTION AIR COMBUSTION AIR for TIGHT buildings COMBUSTION GASES & PARTICLE HAZARDS COMBUSTION PRODUCTS & IAQ COMPLETE COMBUSTION, Stoichiometric CREOSOTE FIRE HAZARDS Curved Brick Chimneys - Sulphation CONDENSING BOILERS/FURNACES CONDENSING BOILERS/FURNACES DAMAGE CONVECTOR HEATERS - HYDRONIC COILS DEFINITION of Heating & Cooling Terms DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP DIAGNOSE & FIX HEATING PROBLEMS-BOILER DIAGNOSE & FIX HEATING PROBLEMS-FURNACE DIRECT VENTS / SIDE WALL VENTS DIRECTORY of OIL TANK EXPERTS DRAFT HOODS - gas fired DRAFT MEASUREMENT, CHIMNEYS & FLUES DRAFT REGULATORS, DAMPERS, BOOSTERS DUCT SYSTEM & DUCT DEFECTS DUST, HVAC CONTAMINATION STUDY DUST SAMPLING PROCEDURE ELECTRIC HEAT, DIAGNOSIS, REPAIR ELECTRIC MOTOR DIAGNOSTIC GUIDE ELECTRIC MOTOR OVERLOAD RESET SWITCH ELECTRICAL POWER SWITCH FOR HEAT EVAPORATIVE COOLING SYSTEMS FAN, AIR HANDLER BLOWER UNIT FAN AUTO ON Thermostat Switch FAN, COMPRESSOR/CONDENSER UNIT FAN CONVECTOR HEATERS - HYDRONIC COILS FAN LIMIT SWITCH FAN NOISES FILTERS, AIR for HVAC SYSTEMS FILTERS, OIL on HEATING EQUIPMENT FIRE SAFETY CONTROLS FIREPLACES & HEARTHS FLAME COLOR, BLUE vs YELLOW COMBUSTION FLOODED HEATING EQUIPMENT REPAIR FLOODED WATER HEATER REPAIR FLUE VENT CONNECTORS FREEZE-PROOF A BUILDING FUEL OIL TYPES & CHARACTERISTICS FUEL UNIT, HEATING OIL PUMPS FURNACES, HEATING FURNACE CONTROLS & SWITCHES FURNACE EFFICIENCY, HIGH vs MID FURNACE HEAT EXCHANGER LEAKS FURNACE OPERATION DETAILS FURNACE OPERATING TEMPERATURES GALVANIC SCALE & METAL CORROSION GAS BURNER Flame & Noise Defects GAS FIRED WATER HEATERS GAS PIPING, VALVES, CONTROLS HEAT EXCHANGER LEAK TEST HEAT LOSS in BUILDINGS HEAT LOSS DETECTION TOOLS HEAT LOSS INDICATORS HEAT LOSS PREVENTION PRIORITIES HEAT LOSS R U & K VALUE CALCULATION HEAT PUMPS, DIAGNOSIS, REPAIR HEAT TAPES & CABLES on Roofs for Ice Dams HEATING COST FUEL & BTU Cost Table HEATING COST SAVINGS METHODS HEATING LOSS DIAGNOSIS-BOILERS HEATING LOSS DIAGNOSIS-FURNACES HEATING OIL EXPOSURE HAZARDS, LIMITS HEATING OIL - OLD, USEABLE? HEATING OIL PIPING TROUBLES HEATING OIL SHELF LIFE HEATING OIL SLUDGE HEATING OIL USAGE RATE HEATING SMALL LOADS HEATING SYSTEM INSPECT DIAGNOSE REPAIR HEATING SYSTEM INSPECTION DETAILS HEATING SYSTEM NOISES HEATING SYSTEM TYPES HIGH EFFICIENCY BOILERS/FURNACES HOT WATER HEATERS HOT WATER IMPROVEMENT INSULATION INSPECTION & IMPROVEMENT LOW VOLTAGE BUILDING WIRING LOW VOLTAGE TRANSFORMER TEST LP & Natural Gas Safety Hazards MANUALS & PARTS GUIDES - HVAC MIXING / ANTI-SCALD VALVES MOTOR OVERLOAD RESET SWITCH Natural Gas Combustion Products NO HEAT - BOILER NO HEAT - FURNACE NOISE / SOUND DIAGNOSIS & CURE NOISE AIR CONDITIONER / HEAT PUMP NOISE, DUCT VIBRATION DAMPENERS NOISE, HEATING SYSTEMS NOISE, PLUMBING NOISE, WATER HEATER ODORS GASES SMELLS, DIAGNOSIS & CURE ODORS FROM HEATING SYSTEMS OIL BURNERS OIL BURNER FUEL UNIT OIL BURNER INSPECTION & REPAIR OIL BURNER NOISE SMOKE ODORS OIL BURNER NOZZLE & ELECTRODES OIL BURNERS, RETENTION HEAD OIL BURNER SOOT & PUFFBACKS OIL FILTERS on HEATING EQUIPMENT OIL FILTER MISSING OIL FUEL TYPES & CHARACTERISTICS OIL HEAT FIRE SAFETY CONTROLS OIL LINE CLOGGING FIX OIL LINE QUICK STOP VALVES OIL LINE SAFETY VALVES OIL ODORS, LEAKY OIL TANK PIPING OIL PUMP FUEL UNIT OIL SPILL CLEANUP / PREVENTION OIL TANKS PLASTIC HEATER VENT PULSE COMBUSTION HEATERS PASCAL CALCULATIONS PRESSURE REDUCING VALVES PRESSURE REGULATOR, WATER PUFFBACKS, OIL BURNER PUMPS, PONY PUMPS RADIANT BARRIERS RADIANT HEAT RADIANT HEAT Floor Mistakes to Avoid RADIANT HEAT TEMPERATURES RADIANT SLAB FLOORING CHOICES RADIANT SLAB TUBING & FLUID CHOICES RADIATORS REFRIGERANTS & PIPING RELIEF VALVE LEAKS RELIEF VALVES - TP Valves on Boilers RELIEF VALVES - STEAM TP VALVES RELIEF VALVES - Water Heaters RELIEF VALVES - Water Tanks Reset Switch - Heater Primary Control Reset Switch Broken - Quick Repair RESET SWITCH - ELECTRIC MOTOR Reset Switch - Stack Relays SAFETY HAZARDS & INSPECTIONS SAFETY HAZARDS GUIDE SAFETY, HEATING INSPECTION SAFETY RECALLS, Chimneys, Vents, Heaters BLUE vs YELLOW COMBUSTION FLAMES BLUERAY Recall CHIMNEYS & Flues - Asbestos Transite Goodman HTPV RECALL Heat Recovery Ventilator RECALL Lennox Furnace Manuals Lennox SAFETY WARNING PLASTIC Plexvent / Ultravent RECALL Weil McLain RECALL STEAM HEATING SYSTEMS TANKLESS COILS Thermal Expansion Cracking of Brick THERMAL EXPANSION of HOT WATER THERMAL EXPANSION of MATERIALS THERMAL IMAGING, THERMOGRAPHY THERMAL IMAGING MOLD SCANS THERMAL MASS in BUILDINGS THERMAL TRACKING & HEAT LOSS THERMOSTATS, HEATING / COOLING THERMOSTATIC EXPANSION VALVES Transite Pipe Chimneys & Flues VIDEO GUIDES: Heating System Videos VIDEO GUIDES - InspectAPedia.com WATER HEATERS WATER SOFTENERS & CONDITIONERS WINTERIZE A BUILDING WOOD, COAL STOVES & FIREPLACES WOOD STOVE SAFETY ZONE DAMPERS ZONE VALVES More Information |
Venmar HRV recall: this document describes safety hazards on certain models of heat recovery ventilators manufactured by Venmar Ventilationand sold under many other brands (listed below) and reports on safety recalls. Warning: not all heating equipment safety or other recalls issued by various agencies and countries are included in this article. This document includes information from public safety notices from the US Consumer Product Safety Commision, from the Canadian Electrical Safety Authority, the Ontarion Fire Marshal's Office, or other sources. Information Accuracy & Bias Pledge is at below-left. Also see HEAT EXCHANGER LEAKS. Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman. Product Safety Alert: Heat Recovery Systems Present Potential Fire Hazards
Fire Safety Notes from Venmar Ventilation
Where to find the Heat Recovery Ventilator Model NumberThe heat recovery ventilator (HRV) model number is located on a silver or black label which is positioned on the outside panel of the heat recovery ventilator unit. Venmar's Recall Hotline: (866) 441-4645 Frequently Asked Questions (FAQs)... Ask a Question or Search InspectApediaUse the search box below to ask a question or to search the InspectApedia.com website. Ask a Question or Enter Search Terms in the InspectApedia search box just below. Technical Reviewers & ReferencesRelated Topics, found near the top of this page suggest articles closely related to this one.
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
| |||||||||||||||||||||||||||||||||||||||