InspectAPedia®   -   Search InspectApedia

Honeywell room thermostat Procedure to Set Room Thermostat Accuracy & Calibration
Thermostat Accuracy is affected by its location and sometimes by position or by internal settings

Room thermostat calibration & accuracy guide: this article explains why a room thermostat may not be responding correctly to the actual room temperature.

Factors that affect the room thermostat's behavior include is location in the building, for some models how level the thermostat was installed, the thermostat's heat anticipator adjustment, even dust and debris in or on the thermostat.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Guide to Room Thermostat Accuracy, Calibration & Adjustment

Where NOT to locate the room thermostat  (C) Carson Dunlop AssociatesWhere to Locate & Mount a Room Thermostat & what spots to avoid

Locate the room thermostat at about chest height on an interior wall, in a location where the thermostat won't be affected by drafts or other unusual temperature conditions.

Good thermostat locations:

As Carson Dunlop Associates ' sketch (left) explains, there are a number of places where you should not locate the room thermostat.

Bad Room Thermostat Locations

Don't locate the room thermostat in these locations:

Even when your room thermostat is properl-located and even when a warm-air heating system is operating normally, some rooms or areas within some rooms may be uncomfortable as heat may be distributed unevenly.

Air stratification during the heating season can leave warm air collected near the ceiling with air nearer the floor uncomfortably cool. Solving this problem by turning up the thermostat or moving it lower on the wall can "work" but is likely to increase heating costs unnecessarily.

Details are at WARM AIR STRATIFICATION INDOORS

Does the Room Thermostat Need to be Level on the Wall?

Thermostat wire connections (C) Daniel FriedmanYes for Older Mercury Bulb Switches

It's important to mount mercury-bulb thermostats as level as possible since otherwise you're putting the thermostat out of accurate temperature calibration.

That's because the coiled bimetallic spring has to move that mercury bulb to a tipped position to turn the heating or air conditioning system on or off in response to room temperature.

When we found a thermostat that did not heat a room accurately to the called-for temperature, we'd take a look to see if it was installed out of level before looking further.

Because the "set" range on these thermostats may have had a lower-end of 55 deg .F.,

when we wanted the thermostat to maintain a building at a temperature lower than the minimum that the thermostat dial provided,

we just tilted the whole thermostat backing plate on the wall in the proper direction to shift the operating range of the switch.

No for Newer Solid State, or Digital Room Thermostats

Newer thermostats that rely on other sensor and switch designs do not have this sensitivity to being out of level and some (such as the 3M-22 thermostat) note in their installation instructions that the thermostat does not have to be level.

Thermostat wire connections (C) Daniel FriedmanOur photo illustrates the red (R) and white (W) wire connections in a simple two wire heating control thermostat hookup using the Honeywell RTH2300/RTH221 series programmable wall thermostat.

Here is a copy of the Honeywell RTH2300/RTH221 Series Programmable Thermostat Owners Manual [PDF]

Because some controls are used in common on hot water heat, hot air heat, and steam boilers, readers should see these other articles:

see BOILER CONTROLS & SWITCHES

If your building uses warm air heat,

see FURNACE CONTROLS & SWITCHES.

If your building uses steam heat

see STEAM HEATING SYSTEMS.

 

Reader Question: the A/C blower is not working properly in response to the thermostat

A friend's a/c unit has the blower fan that will only work in auto, it will not work on manual. On the other hand, even when you turn the unit from cool to off, the blower still remains on. The only way the blower will turn off, is to turn the fan to manual.

He changed the thermostat, and the unit will cool to the desired temp and kick off, but you can't turn the fan off on your own unless you turn it to manual. Anyone ran into this before? - John

Reply: check thermostat wiring connections against the schematic for your unit and see these standard wire color codes

The wiring to the unit depends on if you have a heat pump, or straight a/c unit. It also depends on how the installer has wired the thermostat. With the heat pump, the red is power, the yellow is for cooling, the white is for heat, the green is for the fan, the orange is for the reversing valve, and the blue is usually always common.

Again, you will have to check to see how the installer has ran the wires from the thermostat. If you have a a/c only unit outside, you will only have a red wire, and a white wire coming form the inside unit, to the outside unit. These will go on the contactor to send 24 volts to the coil to pull the contactor in.

These are the traditional wiring schematics, again, check the thermostat to see if this is the case with yours. - Bryan

Also see THERMOSTAT WIRE CONNECTIONS where we provide lists and tables of color codes and wire connections for thermostats in various uses.

Room Thermostat Accuracy & Calibration Questions & Answers

 




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Question: How do I Calibrate my Thermostat

How to calibrate the thermostat? My temp reads 4 degrees lower than my set temp,in AC mode. - NC

Reply:

NC

Calibrating wall thermostats:

most modern wall thermostats do not provide an adjustment that will calibrate the TT to the actual room temperature (and most of them are quite accurate).

OLDER round Honeywell and other TTs that use a mercury bulb sensor can be tipped slightly on the wall - changing the TT out of level will change its calibration, since on those models a blob of mercury in a moving bulb rolls to connect or disconnect the two TT wires.

But take a look at other factors that might make your thermostat inaccurate, including

- its location:

is air from the A/C blowing right on to the TT,
is the TT on an exterior wall,
is the thermostat exposed to direct sunlight

and also check that the thermostat openings are not blocked by dust or debris

Finally, some thermostats include an adjustable heat anticipator that could be improperly set -

see
HEAT ANTICIPATOR Adjustment

Question: how do I fix a thermostat that I have to set lower than the level of heat I want?

My traditional honeywell simple dial-type thermostat on the wall has two pointers and two temp. scales.

However I have to set it on 60 degrees to get heat temp to 70 degrees.
What can I do? It was working fine until my condo changed the air/heating system this summer. - Jeannette 1/23/2013

Reply: check these reasons for a room thermostat that keeps calling for heat

Jeannette,

On most two-scale room thermostats, one scale reads the current or actual room temperature while the other scale is the set temperature - and is adjustable. When you move or adjust the thermostat to call for a different room temperature you will see the scale pointer move to your new setting on the "set" scale.

Remember that a thermostat is just an "on-off" switch that turns heating or cooling ON or OFF in response to the actual room temperature and the desired or "set" temperature you've specified. Make sure that your thermostat is properly set - to "Heat" mode with the fan switch set to "Auto".

You are describing having to set the thermostat lower (60F) than the desired temperature (70F) to get the proper level of heat in your home. In other words, you say that the room gets too hot - hotter than you asked-for. Here are some things that would cause that problem:

Keep us posted, what you learn will help other readers.

Question: heating thermostat seems to show wrong temperature

My heater's thermostat is showing wrong temp. At off setting , it shows the room temp at about 80 when it feels like 60 degree in the house. I tried removing and putting batteries again but doesn't solve the problem. Do I need to replace it? - P. 1/2/2013

Reply:

P

You might, but first check the thermostat's room temperature reading (not its SET temperature reading) against the actual room temperature - use a room thermometer; Then be sure the thermostat is set to HEAT mode and make sure that the SET temperature is above room temperature.

Then heat should run until the sensed temperature at the thermostat turns it back off; See the next Q&A for more details.

Question: why do we have to turn our heat up higher than previously just to get warm

Our heating and air unit is roughly 8 or 9 years old. When we first moved here (6 years ago) we kept the air set on 73-74 during the summer months. We were comfortable.

Now, we have to keep it up to 79-80 and we still feel like the house is too cold. We had the unit checked out last year ( because we started having double and triple utility bills) and the guy said it was fine. Could this be thermostat problems? I don't really feel that the unit runs more than it should though. - Rachel 8/22/12

Reply:

Rachel,

First, are we looking at the same outdoor temperatures as previously? If not, if it's colder now than previously, the problem could be with your home's rate of heat loss - bad insulation, leaky windows &c.

If weather conditions are the same, then we have some other questions to ask: you don't say if your heat is from hot water or forced warm air. In either of those systems, even if the equipment is running as before, you could have a simple maintenance problem like a clogged air filter or air bound radiator that's the problem. I'd need to know more.

On 2021-01-29 - by (mod) -

The heat type ONLY affects the equivalent of a heat anticipator in the unit - it won't or ought not affect the simple on-off function on a call for heat; I'd have wanted a careful check of the TT wires and connections.

I HAVE fund however on some of the newer TTs that the screw terminal does not make good electrical content with some older very small diameter thermostat wires. I had to address that in some installations.

On 2021-01-29 by Vincent

I think this solution probably also applied to the reader Jessica's comment which is posted on Nov 28, 2020

On 2021-01-29 by Anonymous


On 2021-01-29 by Vincent

Do you know the mystery of the Honeywell CT87K4446 manual heat on round thermostat or similar models? My father help his friend who is a building owner in New York City to replace a thermostat which the tenant broke off, the hydronic heat and domestic water are offer by the modulating boiler of LAARS Endurance EPB. The landlord preferred simple heat-only non-digital thermostat for easy use. So my father purchased Honeywell CT87K4446 for replacement. After installing the thermostat, turn the dial all the way up, the boiler didn't work, no heat, but the boiler didn't show any error or diagnostic info.

Thereafter, the landlord called three heating technicians, and replaced the thermostats twice, spent five hundred fixing the problem. The technicians always condemned the defective thermostat wires or bad thermostat which is brand new. Finally dig out the problem the thermostat is too simple to pay attention to set up the tiny switch at the back correctly, which is default to steam boiler system. In my insight, the thermostat is working as switch, why the switch setting will affect the boiler operation?

On 2020-11-29 - by (mod) -

That does indeed sound odd. I guess it's possible that there was an incorrect Connection in the thermostat or that one of the wires is damaged and when pushed back into the wall is opening up and therefore breaking the connection

On 2020-11-29 by Jessica

I thought my old Honeywell mercury based thermostat went out, as when I touch the red and white wires together the propane "Heat-n-Glo" fireplace furnace turns on. I have tried two thermostats, Nest E and Honeywell CT87K with no luck. The nest troubleshooting said no power was reading from red wire...but why does it work simply by touching wires together? The Honeywell fails to trigger as well. What am I missing?

On 2020-07-03 - by (mod) -

1. Check that the batteries are good and are properly inserted

2. Check for a loose, broken, or shorted thermostat wire

3. Check for a bad transformer that is not delivering power to the thermostat

On 2020-07-03 by CJ

The battery died on the thermostat. After replacing the batteries, it does not read when to turn on. The AC does work but comes on randomly. Not based on set temperature. What should I do to correct this?

This article is part of THERMOSTATS our article series Guide to Finding, Using, and Adjusting Thermostats for Heating & Air Conditioning Furnaces & Boilers, Heat Pumps or Electric Furnaces or Boilers.

This article series answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.


...

Continue reading at TEMPERATURE RESPONSE of ROOM THERMOSTATS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see THERMOSTAT CALIBRATION FAQs - questions & answers about thermostat accuracy and calibration posted originally in this article

Or see these

Recommended Articles

Suggested citation for this web page

THERMOSTAT CALIBRATION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HVAC THERMOSTATS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT