  • STACK RELAY SWITCH - home - CONTENTS: Stack Relay Switches - Honeywell & replacement Type RA 117A / RA116A / RA817A Protectorelay Primary Control operations & reset buttons found on Oil Fired Heating Equipment, boilers, furnaces, water heaters. We include a Stack Relay Troubleshooting & Repair Guide. How to use the primary controller reset button - how many times to press the red reset button on an oil burner. Oil burner puffbacks explained. Troubleshooting heating system furnace & boiler safety controls; when and how to service, test, & clean the stack relay switch primary control Type RA 116A Protectorelay Switch, Delco primary control (master control), Honey Primary controls on oil fired equipment
  • POST a QUESTION or READ FAQs about oil heating equipment stack relay installation, diagnosis, repair, re-set procedure & replacement options
  • REFERENCES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Stack relay switch guide for oil fired heating equipment:

In this article series, beginning here we explain how to inspect, test, reset, or clean the stack relay switch used as a flame detection/safety device for primary control on oil fired heating systems (boilers and furnaces). Included is an explanation of the operation of the Honeywell RA116A, RA117A, and RA817A protectorelays, a primary control that senses heat to confirm that the oil burner is operating successfully.

This article series answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

A Guide to Stack Relay Control Switches on Boilers, Furnaces, or Water Heaters

Oil burner stack relay schematic (C) Carson Dunlop Associates

Article Series Contents

What is a "Stack Relay" or (Honeywell) Protectorelay switch and how does it work?

A "stack relay" is a primary heating system safety control mounted on the flue vent connector close to an oil fired heating boiler, furnace, or water heater.

This switch includes a bimetallic spring that responds to the presence of heat in the flue vent - indicating that the oil burner has achieved and is maintaining proper flame ignition.

If the stack relay does not sense successful ignition within a short period (typically 75 seconds), the switch "opens" to cut off line voltage to the oil burner, effectively shutting off the system to avoid a harmful or dangerous situation.

This switch handles loss of oil burner flame either at start-up or during ongoing operation of the heating appliance.

Following a safety shut-down, most stack relay switches must be re-set manually by pushing a reset button, illustrated and explained below.

Oil Burner Stack Relay Switches (Protectorelay® type controls), Detailed Explanation

The stack relay switch shown in the photograph at page top and illustrated in Carson Dunlop's sketch, above, is attached at the flue vent connector which in turn passes flue gases from an old "octopus" type furnace to the chimney. (See the black box with its red reset button.) This same switch might also be found on some oil-fired heating boilers (hot water, hydronic, baseboard, or radiator heat) not just on furnaces (hot air heat)

Older oil burners used to heat a warm air furnace, a heating boiler, or a water heater may use a stack relay switch as a primary controller to prevent sending fuel into the oil burner if the oil burner flame has not been successfully ignited.

Stack relays are an older type of flame sensor than the CAD CELL RELAY SWITCH, but they accomplish the same purpose (turn off the oil burner if the flame is not established).

Where to Mount the Primary Control Protecto Relay or Stack Switch

Primary control stack relay skectch (C) Daniiel Friedman

The "stack relay" uses a bimetallic spring (also called a bimetallic helix) inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney.

The round tube containing the bimetallic temperature sensing spring is inserted into the heating appliance flue stack so that it is located in the center of the path of flue gases. (Audel sketch at left, edited).

Taking advantage of the fact that two different metals laminated together will expand at different rates, the bimetallic spring moves in response to the presence or absence of heat inside of the flue vent connector ("smoke pipe" or "stack") of an oil fired boiler or furnace.

Sensing heat in the stack is a means of assuring that the burner flame is present.

Protecto Relay RA116A RA116A RA817A Manuals

How Stack Relay Safety Switches Work on Oil Fired Heating Equipment

Type RA 116A primary control (C) Daniel Friedman Audel

How Stack Relay Switches Work: Older oil burners may use a Stack Relay to accomplish the same purpose (turn off the oil burner if the flame is not established).

The "stack relay" is a bimetallic spring inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney.

If the oil burner fails to ignite or if the flame is intermittent, too small an cool, or lost entirely, this safety control will sense the loss of oil burner flame by sensing the drop of temperature in the flue.

As the bimetallic spring changes shape in response to cooling, it mechanically operates a primary control safety-off switch to turn off the oil burner motor (so that we don't keep pumping un-burned heating oil into the combustion chamber).

Similarly to failure to ignite at boiler or furnace start-up, if the flame is lost during oil burner operation this control will also turn off the oil burner motor.

The Type RA 116A or Type RA117A primary control is also designed to automatically re-start the oil burner after a cool-down cycle of a minute to a minute and a half after an abnormal shutdown. If multiple re-start attempts fail to get the oil burner operating satisfactorily the system will shut down entirely in "SAFETY OFF" condition.

This control includes a red safety reset button (#8 in the drawing) that pops out if the control has caused a safety shut down of the oil burner. Here we explain when, how, and how-often to press the red reset button to try re-starting the oil burner.

Our sketches (above) of a Type RA 116A / RA 117A Primary Control, also called a Stack Relay or a Protectorelay, shows the cover removed and identifies the principal components of this heating system control.

Sketch from Audel. The Type RA 116A primary control was used on constant-ignition oil burners that fired heating boilers, warm air furnaces, and water heaters. You will still find this old control on older oil fired heating equipment, though not on newer oil-fired equipment which is more likely to use
a  CAD CELL RELAY SWITCH Flame Sensor to detect the successful ignition of the oil burner.

The bimetallic spring warms in response to hot oil burner exhaust, confirming that combustion is taking place. If combustion is not occurring a timer inside the stack relay turns off the oil burner to prevent flooding of the combustion chamber with un-burned oil.

The stack relay switch shown in the page top photograph and in the sketch above is attached at the flue vent connector which in turn passes flue gases from an old "octopus" type furnace (in our photograph) to the chimney. (See the black box with its red reset button.) This same switch might also be found on some oil-fired heating boilers (hot water, hydronic, baseboard, or radiator heat) not just on furnaces (hot air heat).

How to Reset the Oil Burner Stack Relay - Using the Reset Button

Delco primary control stack relay (C) Daniel FriedmanA gray box with a red reset button housing the stack relay and its reset switch will be found mounted on the flue vent connector if this control is in use. The first is simply to press the red reset button that protrudes through the cover of the stack relay box itself.

The primary control reset button on a Delco master control is labeled at the center right of the illustration at left. A primary control stack relay reset button is also pointed out by arrow #8 in our sketch above.

This red button should project through a small hole in the primary control's cover.

If you don't see the red button but you see the hole in the control cover, it's possible that a plastic reset button extension has broken off and been lost, but the actual working reset button and switch can still be found inside the control cover and it can still be pressed.

Knowing how to reset the stack relay can avoid a costly no heat service call or it can keep the heating boiler running sufficiently to keep the building warm while waiting for the heating service technician.

There are actually two resets that can be performed on an oil burner stack relay.

A second stack control reset might be necessary - we discuss it at HOW TO RESET the Oil Burner Stack Relay below.

How many times can I press the reset button on the oil burner primary controller?

Watch out: Most heating technicians and inspectors will tell you to only press the reset button once. That's because we worry that a homeowner will keep pressing the button even though the oil burner flame is never igniting.

Watch out: sometimes the red plastic button on older heating equipment primary controls can break off.

At RESET SWITCH, HEATER REPAIR we show how to reset the equipment safely if this happens to you.

How do I Find the Reset Button on the Stack Relay?

You can see the "reset button" illustrated in sketch earlier on this page. Note: the "reset button" on some primary safety controls is actually a round red button protruding through the control cover. Usually when the control has locked out the oil burner, this button "pops out" to project further through the control cover.

Using a cad cell relay as a model we illustrate that the safety control red reset button may be a small (5/16" diameter) round plastic button protruding up through the control cover (below left) or it may be a larger round red rubber button such as the cad cell reset switch (below right).

Cad cell relay reset button (C) D Friedman Cad cell relay reset button (C) D Friedman

Where the Heck Are The Various Reset Buttons on Heating Equipment?

If you are looking for the main reset button on heating equipment you'll want to see:

Finding the Primary Control Reset Switch

Watch out: on many primary controls, the red plastic reset button is actually a plastic button and spring-assembly mounted to the control cover itself.

Reset switch on Energy Kinetics Oil Boiler (C) D Friedman

Just to make things tricky, on some controls the reset switch is black and even recessed, such as on the Energy Kinetics cover shown at left.

But other manufacturers know we're seeing red if we've lost heat - and most of them make the reset button red.

Below we discuss other reset functions peculiar to the Stack Relay Switch, also called the Primary Controller on older oil fired heating equipment. But first we make a brief warning about puffbacks.

Oil Burner puffback Problems & Warning

Watch out: There is a reason that instructions for a homeowner tell you to push the primary heating control reset button just "once". If you keep pushing it the oil burner will indeed keep trying to start, spraying more heating oil into the combustion chamber at each "try".

If you flood the heater's combustion chamber with un-burned oil which later does ignite, the result can be a dangerous puffback which blows soot and smoke into the building, can damage the equipment, is unsafe, and could even start a fire.

So as with cad cell relays and other heating system "reset" buttons, if the oil burner does not turn on and run continuously and normally (no smoke, no loud noises, etc.) for at least 5 or 10 minutes after resetting the relay or pressing the reset button, DO NOT keep resetting the system since doing so can flood the combustion chamber with un-burned heating oil - a dangerous condition as we just explained.

See OIL BURNER SOOT & PUFFBACKS for details.

How to Reset the Oil Burner Stack Relay - Using the Internal Relay Stepping Lever to Re-Step the control

How to reset the primary control Protectorelay (C) Daniel FriedmanWhy might you need to remove the cover and look for a second, "internal" reset lever inside of this control? Sometimes simply pressing the reset button through the cover of the stack relay switch will not turn on the oil burner, but the problem could be in the switch itself, not the burner.

Honeywell explains:

The detector contacts are actuated by a friction clutch that is mounted on a rod connected directly to the heat actuated element. Occasionally, this clutch becomes out of step after a long period of idleness.

To place the clutch and the contacts in step [... you will need to pull and release the lever shown at left and explained below] [6]

This procedure is called "re-stepping" the Protectorelay or Type RA 116A Primary Control (which we call the "stack relay" because its bimetallic spring sensor is inserted into the oil-fired boiler or furnace "stack pipe" (flue vent connector) where it senses the heat from a successful oil burner ignition and flame.

This second and more thorough reset of the stack relay (after tying just pressing the reset button found on the switch cover) can be accomplished by removing the cover on this control box.

Watch out: (SAFETY WARNING LIVE VOLTAGE electrical connections are inside this box - a shock hazard

Simple Procedure to Re-step the Pyrostat Detector Relay

The stack relay bimetallic spring assembly can be "reset" by removing the cover of the assembly and pulling the (visually obvious) reset lever out away from the flue vent connector (it will move about 1/4 of an inch), and then carefully and gently releasing it again. Put the cover back on and push the red safety reset button.

If electrical power is on to the system and if there is an oil supply and the oil valve is open, and if the thermostat is calling for heat, the oil burner should start.

Watch out for sensitive stack relays: sometimes these switches trip off during oil burner testing or operation and they can be tricky to re-set.

If you're able to get the system running again by using this internal reset, but if the relay switch tends to trip off if you simply tap on the outside of the relay switch when its cover has been replaced, then there is a problem needing further investigation, either with an electrical connection in the switch, or with the switch itself. In this case the stack relay switch may need replacement, but before replacing it see our note below on cleaning the stack relay switch.

Watch out: Honeywell warns to be careful not to bend any of the switch parts such as contact arms or stops on the "pyrostat" detector mechanism (the bimetallic spring, relays, sensors) and also warns not to try making any adjustments other than those given in the installation instructions for the equipment.[6]

Tips for Servicing and Testing the Oil Burner Primary Control: the Type RA116A / RA117A Protectorelay Stack Relay

Protectorelay scavenger timing and recycling timer (C) Daniel Friedman Audel

Moved to STACK RELAY SERVICE & TEST PROCEDURES

How to Test the Stack Relay using the Safety Switch

At CAD CELL RELAY SWITCH we describe using the safety switch, a small black plastic or metallic lever found next to the reset button on some primary heating system controls including stack relays and cad cell sensors.

When to Clean the Oil Burner Stack Relay Switch

Moved to STACK RELAY, WHEN to CLEAN

When to Adjust the Oil Burner Scavenger Cycle Restart Delay Time on the RA 116A Protectorelay Switch

Check the Scavenger Timing cycle of the primary control, using the procedure at STACK RELAY DELAY TIME ADJUSTMENT

Replacements & Cross Reference Chart for Stack Switches / ProtectoRelay's

Please see this new article: STACK RELAY REPLACEMENT CROSS REFERENCE CHART

Stack Relay Operation, Penn Oil Burner

Penn Oil Burner Primary Control Stack Relay (C) D Friedman Ben Bourdreau This discussion has moved to a new article at PENN OIL BURNER STACK RELAY OPERATING DETAILS - separate article

Question: is there a high limit built into the RA-116 Stack Relay Control?

(Oct 5, 2016) Bud said:
Really informative, Thank You, but no mention if there is a high limit built into the control, my old oil furnace control kicks out just before it reaches set temp on thermostat... what would cause this? Filters dirty? Fan not blowing enough air? Bud budnpat@telus.net

Reply:

The stack relay only monitors stack temperature in an effort to confirm that the burner has ignited.

High temperature limits on a furnace like yours will be built into the fan limit switch. A too-high plenum temperature ought to shut off the burner. But the stack relay typically used on older oil fired heating equipment will not, itself provide that additional function. As Honeywell explains in their publication on Oil Heat controls,

Critical Operations:

Failure to Light: If the burner fails to light, the cold contacts will not open. The safety switch will continue to heat until it trips and locks out. Flame Fails During Run Cycle: If the flame fails during the run cycle, the drop in stack temperature causes the detector’s hot contacts to open and drop out relay 2K, shutting down the burner. After two to three minutes, the cold contacts close, energizing the safety switch heater. If the thermostat is still calling for heat, the burner and ignition will come back on to restart the burner. If a flame is not established within 70 seconds, the safety switch will lock out.

Other Notes:

As Fig. 14 shows, the stack relay uses one set of contacts in Start mode and another in Run mode. When the cold (Start mode) contacts are closed, they close the safety switch circuit, energizing the safety switch heater. When the hot stack gases heat the bimetal, the drive shaft moves, breaking the cold contacts (and the safety switch heater circuit) and making the hot contacts that complete the run circuit.

Thermal flame detectors may be separate from the primary control (as in the R8189/C550D combination that is continuing to be used although now obsolete) or included with the primary as in the RA117. Whether it is included or separate, however, the very basis of the thermal relay is the Honeywell PyrostatÆ Flame Detector. The parts shown above are common to all Pyrostat® Flame Detectors although some details may vary.

The bimetal element is inserted in the stack where it is exposed to rapid changes in the temperature of the stack gases. On an increase in stack temperature, the bimetal straightens, moving the drive shaft outward. This outward movement of the drive shaft is transferred to the hot and cold contacts through the clutch fingers. As the drive shaft continues to move, the cold contacts are opened and the hot contacts are closed.

The clutch fingers ride on the drive shaft and must be free to slide, although there must be enough friction so they will move the contacts. If there is too much friction because of dirt buildup, the clutch fingers will not slide freely and the contacts will not be correctly sequenced.

The RA116 and RA816 Primary Controls and the C550D Detector have only one set of contacts that acts as both hot and cold contacts. The contacts must be closed when cold.

 

Heating System Fire & Safety Control Articles

...


Continue reading at STACK RELAY SERVICE & TEST PROCEDURES or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see PENN OIL BURNER STACK RELAY OPERATING DETAILS

Or see OIL BURNER INSPECTION & REPAIR

FURNACE CONTROLS & SWITCHES

HEAT WON'T TURN OFF

HEAT WON'T TURN ON

STEAM HEATING SYSTEMS & Controls

Suggested citation for this web page

STACK RELAY SWITCH at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman