InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTER VALVE, HEATING SYS
BACKFLOW PREVENTER, HEATER WATER FEEDER
BACKUP HEAT for HEAT PUMPS
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  BOILER OPERATION DETAILS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Air-bound boilers & radiators
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  Boiler Pressure Controls & Settings
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  Draft Regulators, Dampers
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Switch
  WATER HEATERS
ZONE VALVES
CARBON MONOXIDE - CO
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS

CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS

DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT INSULATION, Asbestos Paper

DUCT SYSTEM & DUCT DEFECTS
DUCTS, Asbestos Transite Pipe
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

FURNACES, HEATING
  DUCT SYSTEM DEFECTS
  ALLOY SYSTEMS FLEXDUCT
  DUCT & AIR HANDLER ODORS
  DUCT INSULATION, Asbestos Paper
  FAN LIMIT SWITCH
  FURNACE CONTROLS & SWITCHES
  FURNACE OPERATION DETAILS
  FURNACE OPERATING TEMPERATURES
  HEAT EXCHANGER LEAKS
  STACK RELAY SWITCHES
GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT PUMPS, DiAGNOSIS, REPAIR
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SMALL LOADS

HEATING SYSTEM NOISES
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE
HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES

NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick Repair
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES

STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  EXPANSION TANKS
  FIRE SAFETY CONTROLS
  GAUGES, HEATING EQUIP.
  LIMIT SWITCH, BOILER
  LOW WATER CUTOFF VALVE
  MIXING / ANTI-SCALD VALVES
  PRESSURE, TEMPERTURE SETTINGS, CONTROLS
  PRESSURE SWITCH, STEAM BOILER
  RELIEF VALVES - STEAM TP VALVES
  SIGHT GLASS, STEAM BOILER
  SPILL SWITCHES
  STACK RELAY SWITCH
  STEAM PRESSURE GAUGE
  STEAM TRAPS
  STEAM VENTS
  THERMOSTATS, HEATING / COOLING
  WATER FEEDER Valves, Steam

TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & FlueS

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE VALVES

More Information

LARGER VIEW of stack relay switch on an oil fired heaterGuide to Stack Relay Switches on Oil Fired Heating Equipment
InspectAPedia®  -      

  • Stack Relay Switches - Type RA 117A / RA116A Protectorelay Primary Controls on Oil Fired Heating Equipment, boilers, furnaces, water heaters: Stack Relay Troubleshooting & Repair Guide
  • How to use the primary controller reset button - how many times to press the red reset button on an oil burner
  • Oil burner puffbacks explained
  • Troubleshooting heating system furnace & boiler safety controls; when and how to service, test, & clean the stack relay switch primary control Type RA 116A Protectorelay Switch, Delco primary control (master control), Honey Primary controls on oil fired equipment
  • Questions & answers about oil heating equipment stack relay installation, diagnosis, repair, re-set procedure & replacement options

Stack relay guide: Here we explain how to inspect, test, reset, or clean the stack relay switch used as a flame detection/safety device for primary control on oil fired heating systems (boilers and furnaces). This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect residential heating systems to inform home owners, buyers, and home inspectors of common heating system defects.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

A Guide to Stack Relay Control Switches on Boilers, Furnaces, or Water Heaters

What is a "Stack Relay" or (Honeywell) Protectorelay switch and how does it work?

Oil burner stack relay schematic (C) Carson Dunlop

A "stack relay" is a primary heating system safety control mounted on the flue vent connector close to an oil fired heating boiler, furnace, or water heater.

This switch includes a bimetallic spring that responds to the presence of heat in the flue vent - indicating that the oil burner has achieved and is maintaining proper flame ignition.

If the stack relay does not sense successful ignition within a short period (typically 75 seconds), the switch "opens" to cut off line voltage to the oil burner, effectively shutting off the system to avoid a harmful or dangerous situation. This switch handles loss of oil burner flame either at start-up or during ongoing operation of the heating appliance.

Following a safety shut-down, most stack relay switches must be re-set manually by pushing a reset button, illustrated and explained below.

The articles at this website describe the basic components of a home heating system, how to find the rated heating capacity of an heating system by examining various data tags and components, how to recognize common heating system operating or safety defects, and how to save money on home heating costs. We include product safety recall and other heating system hazards. Also see GAS PIPING, VALVES, CONTROLS for more details on how to inspect and test LP and natural gas piping, controls, valves, and tanks. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

Oil Burner Stack Relay Switches (Protectorelay® type controls), Detailed Explanation

The stack relay switch shown in the photograph at page top and illustrated in Carson Dunlop's sketch, above, is attached at the flue vent connector which in turn passes flue gases from an old "octopus" type furnace to the chimney. (See the black box with its red reset button.) This same switch might also be found on some oil-fired heating boilers (hot water, hydronic, baseboard, or radiator heat) not just on furnaces (hot air heat)

Older oil burners used to heat a warm air furnace, a heating boiler, or a water heater may use a stack relay switch as a primary controller to prevent sending fuel into the oil burner if the oil burner flame has not been successfully ignited.

Stack relays are an older type of flame sensor than the CAD CELL RELAY SWITCH, but they accomplish the same purpose (turn off the oil burner if the flame is not established).


Where to Mount the Primary Control Protecto Relay or Stack Switch

Primary control stack relay skectch (C) Daniiel FriedmanThe "stack relay" uses a bimetallic spring (also called a bimetallic helix) inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney.

The round tube containing the bimetallic temperature sensing spring is inserted into the heating appliance flue stack so that it is located in the center of the path of flue gases. (Audel sketch at left, edited).

Taking advantage of the fact that two different metals laminated together will expand at different rates, the bimetallic spring moves in response to the presence or absence of heat inside of the flue vent connector ("smoke pipe" or "stack") of an oil fired boiler or furnace. Sensing heat in the stack is a means of assuring that the burner flame is present.

How Stack Relay Safety Switches Work on Oil Fired Heating Equipment

Type RA 116A primary control (C) Daniel Friedman AudelHow Stack Relay Switches Work: Older oil burners may use a Stack Relay to accomplish the same purpose (turn off the oil burner if the flame is not established). The "stack relay" is a bimetallic spring inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney.

If the oil burner fails to ignite or if the flame is intermittent, too small an cool, or lost entirely, this safety control will sense the loss of oil burner flame by sensing the drop of temperature in the flue. As the bimetallic spring changes shape in response to cooling, it mechanically operates a primary control safety-off switch to turn off the oil burner motor (so that we don't keep pumping un-burned heating oil into the combustion chamber).

Similarly to failure to ignite at boiler or furnace start-up, if the flame is lost during oil burner operation this control will also turn off the oil burner motor.

The Type RA 116A or Type RA117A primary control is also designed to automatically re-start the oil burner after a cool-down cycle of a minute to a minute and a half after an abnormal shutdown. If multiple re-start attempts fail to get the oil burner operating satisfactorily the system will shut down entirely in "SAFETY OFF" condition.

This control includes a red safety reset button (#8 in the drawing) that pops out if the control has caused a safety shut down of the oil burner. Here we explain when, how, and how-often to press the red reset button to try re-starting the oil burner.

Our sketches (above) of a Type RA 116A / RA 117A Primary Control, also called a Stack Relay or a Protectorelay, shows the cover removed and identifies the principal components of this heating system control. Sketch from Audel. The Type RA 116A primary control was used on constant-ignition oil burners that fired heating boilers, warm air furnaces, and water heaters. You will still find this old control on older oil fired heating equipment, though not on newer oil-fired equipment which is more likely to use a  Cad Cell Relay Switch Flame Sensor to detect the successful ignition of the oil burner.

The bimetallic spring warms in response to hot oil burner exhaust, confirming that combustion is taking place. If combustion is not occurring a timer inside the stack relay turns off the oil burner to prevent flooding of the combustion chamber with un-burned oil.

The stack relay switch shown in the page top photograph and in the sketch above is attached at the flue vent connector which in turn passes flue gases from an old "octopus" type furnace (in our photograph) to the chimney. (See the black box with its red reset button.) This same switch might also be found on some oil-fired heating boilers (hot water, hydronic, baseboard, or radiator heat) not just on furnaces (hot air heat).

How to Reset the Oil Burner Stack Relay - Using the Reset Button

A gray box with a red reset button housing the stack relay and its reset switch will be found mounted on the flue vent connector if this control is in use. The first is simply to press the red reset button that protrudes through the cover of the stack relay box itself.

Delco primary control stack relay (C) Daniel FriedmanThe primary control reset button on a Delco master control is labeled at the center right of the illustration at left. A primary control stack relay reset button is also pointed out by arrow #8 in our sketch above.

This red button should project through a small hole in the primary control's cover. If you don't see the red button but you see the hole in the control cover, it's possible that a plastic reset button extension has broken off and been lost, but the actual working reset button and switch can still be found inside the control cover and it can still be pressed.

Knowing how to reset the stack relay can avoid a costly no heat service call or it can keep the heating boiler running sufficiently to keep the building warm while waiting for the heating service technician.

There are actually two resets that can be performed on an oil burner stack relay.

A second stack control reset might be necessary - we discuss it at How to Reset the Oil Burner Stack Relay below.

How many times can I press the reset button on the oil burner primary controller?

Watch out: Most heating technicians and inspectors will tell you to only press the reset button once. That's because we worry that a homeowner will keep pressing the button even though the oil burner flame is never igniting.

Watch out: sometimes the red plastic button on older heating equipment primary controls can break off. At Reset Switch Broken - Quick Repair we show how to reset the equipment safely if this happens to you.

How do I Find the Reset Button on the Stack Relay?

You can see the "reset button" illustrated in sketch earlier on this page. Note: the "reset button" on some primary safety controls is actually a round red button protruding through the control cover. Usually when the control has locked out the oil burner, this button "pops out" to project further through the control cover.

Using a cad cell relay as a model we illustrate that the safety control red reset button may be a small (5/16" diameter) round plastic button protruding up through the control cover (below left) or it may be a larger round red rubber button such as the cad cell reset switch (below right).

Cad cell relay reset button (C) D Friedman Cad cell relay reset button (C) D Friedman

Where the Heck Are The Various Reset Buttons on Heating Equipment?

If you are looking for the main reset button on heating equipment you'll want to see:

AQUASTAT CONTROL Functions and

CAD CELL RELAY SWITCH (hot water boilers and some water heaters),

Stack Relay Switch on older oil fired boilers and furnaces,

SPILL SWITCHES (gas fired equipment), and

Low Water Cutoff Controls on steam heating systems.

At ELECTRIC MOTOR OVERLOAD RESET SWITCH we discuss the thermal overload switch and reset button that is found on many electric motors including those operating air conditioning fans, heating system oil burners, and furnace blowers and motors.

Finding the Primary Control Reset Switch

Reset switch on Energy Kinetics Oil Boiler (C) D Friedman

 

Watch out: on many primary controls, the red plastic reset button is actually a plastic button and spring-assembly mounted to the control cover itself.

Just to make things tricky, on some controls the reset switch is black and even recessed, such as on the Energy Kinetics cover shown at left.

But other manufacturers know we're seeing red if we've lost heat - and most of them make the reset button red.


 

Below we discuss other reset functions peculiar to the Stack Relay Switch, also called the Primary Controller on older oil fired heating equipment. But first we make a brief warning about puffbacks.

Oil Burner puffback Problems & Warning

Watch out: There is a reason that instructions for a homeowner tell you to push the primary heating control reset button just "once". If you keep pushing it the oil burner will indeed keep trying to start, spraying more heating oil into the combustion chamber at each "try".

If you flood the heater's combustion chamber with un-burned oil which later does ignite, the result can be a dangerous puffback which blows soot and smoke into the building, can damage the equipment, is unsafe, and could even start a fire.

So as with cad cell relays and other heating system "reset" buttons, if the oil burner does not turn on and run continuously and normally (no smoke, no loud noises, etc.) for at least 5 or 10 minutes after resetting the relay or pressing the reset button, DO NOT keep resetting the system since doing so can flood the combustion chamber with un-burned heating oil - a dangerous condition as we just explained.

See OIL BURNER SOOT & PUFFBACKS for details.

How to Reset the Oil Burner Stack Relay - Using the Internal Relay Stepping Lever to Re-Step the control

How to reset the primary control Protectorelay (C) Daniel FriedmanWhy might you need to remove the cover and look for a second, "internal" reset lever inside of this control? Sometimes simply pressing the reset button through the cover of the stack relay switch will not turn on the oil burner, but the problem could be in the switch itself, not the burner.

Honeywell explains:

The detector contacts are actuated by a friction clutch that is mounted on a rod connected directly to the heat actuated element. Occasionally, this clutch becomes out of step after a long period of idleness. To place the clutch and the contacts in step [... you will need to pull and release the lever shown at left and explained below] [6]

This procedure is called "re-stepping" the Protectorelay or Type RA 116A Primary Control (which we call the "stack relay" because its bimetallic spring sensor is inserted into the oil-fired boiler or furnace "stack pipe" (flue vent connector) where it senses the heat from a successful oil burner ignition and flame.

This second and more thorough reset of the stack relay (after tying just pressing the reset button found on the switch cover) can be accomplished by removing the cover on this control box.

Watch out: (SAFETY WARNING LIVE VOLTAGE electrical connections are inside this box - a shock hazard

Simple Procedure to Re-step the Pyrostat Detector Relay

The stack relay bimetallic spring assembly can be "reset" by removing the cover of the assembly and pulling the (visually obvious) reset lever out away from the flue vent connector (it will move about 1/4 of an inch), and then carefully and gently releasing it again. Put the cover back on and push the red safety reset button.

If electrical power is on to the system and if there is an oil supply and the oil valve is open, and if the thermostat is calling for heat, the oil burner should start.

Watch out for sensitive stack relays: sometimes these switches trip off during oil burner testing or operation and they can be tricky to re-set.

If you're able to get the system running again by using this internal reset, but if the relay switch tends to trip off if you simply tap on the outside of the relay switch when its cover has been replaced, then there is a problem needing further investigation, either with an electrical connection in the switch, or with the switch itself. In this case the stack relay switch may need replacement, but before replacing it see our note below on cleaning the stack relay switch.

Watch out: Honeywell warns to be careful not to bend any of the switch parts such as contact arms or stops on the "pyrostat" detector mechanism (the bimetallic spring, relays, sensors) and also warns not to try making any adjustments other than those given in the installation instructions for the equipment.[6]

When to Clean the Oil Burner Stack Relay Switch

Since this oil burner relay switch depends on sensing the heat of the flue gases as they pass through the flue vent connector (or "stack pipe") from the oil burner/combustion chamber in a furnace or boiler up to the chimney, the sensor, a bimetallic spring, is exposed to soot in the oil burner exhaust. If the oil burner has been running poorly, perhaps itself needing cleaning or adjustment, the level of soot in the oil burner exhaust can be quite high.

Soot produced by oil combustion (or by poor or incomplete heating oil combustion) is itself an insulator. Not only do we need to remove this soot from inside of a furnace or boiler in order to get the most heat from our heating oil into the building's heating distribution system (hot air or hot water), but this same soot can collect on, clog, or insulate the oil burner stack relay switch.

Soot collected on the stack relay switch bimetallic sensor spring, acting as an insulator, can "fool" the switch into thinking that there is not good combustion (temperatures look too low at the sensor) and thus it might switch off on safety and need to be frequently "reset" to keep the heating system running. It may be necessary to clean the stack relay switch sensor.

During oil burner service for a boiler or furnace, if the heating system uses a stack relay switch (which in fact is rather obsolete), the switch should be removed during system cleaning (when you remove the flue vent connector piping), and its external parts or sensor should be cleaned (normally by light brushing).

Tips for Servicing and Testing the Oil Burner Primary Control: the Type RA116A Protectorelay Stack Relay

Protectorelay scavenger timing and recycling timer (C) Daniel Friedman Audel

Do not lubricate the primary control parts with oil.

Keep the cover on the primary control - this protects the control from dust and from mechanical damage, either of which could make it stop working or make it unsafe.

How to check the safety lockout function of the oil burner primary control or stack relay or Protectorelay®:

  • with the oil burner running,
  • close the manual oil valve at the oil burner - this simulates a flame failure of the oil burner.
  • When the oil burner flame goes out, "hot contacts" (#6) should open after a the stack temperature begins to drop (and the bimetallic spring of the RA 116A contracts).
  • This should turn off the oil burner motor itself.
  • The burner should stay off until the stack relay RA116A cools down enough to re-make the cold contacts (#7) which should re-start the oil burner automatically.
  • But as you have left the oil flow turned off, after 90 seconds or less the burner motor should stop again.

Pressing the red "reset" button while the oil burner is running normally will also interrupt or stop the oil burner.

Turning off electrical power to the oil burner, with the burner running, will of course stop the burner. But loss of power should not trip the stack relay switch. This means that when electrical power is turned back on, provided the thermostat is calling for heat, the oil burner should start.

Check the Scavenger Timing cycle of the primary control, using the procedure at Scavenger Cycle Restart Delay Time.

-- the above is paraphrased from Audel with some details added from Honeywell's Protectorelay® control installation literature.

How to Test the Stack Relay using the Safety Switch

At CAD CELL RELAY SWITCH we describe using the safety switch, a small black plastic or metallic lever found next to the reset button on some primary heating system controls including stack relays and cad cell sensors.

When to Adjust the Oil Burner Scavenger Cycle Restart Delay Time on the RA 116A Protectorelay Switch

The following procedure, recommended by Frank Graham of Audel, tests the scavenger timing cycle of an oil burner that is controlled by a Type RA 116A Protectorelay or "stack relay" primary control.

Protectorelay scavenger timing and recycling timer (C) Daniel Friedman AudelWhen an oil burner is in proper adjustment and is working but has been shut off using the electrical power switch (line switch) to the oil burner, the scavenger timing is checked by turning on the oil burner at the line switch. (See ELECTRICAL POWER SWITCH FOR HEAT). The oil burner should start and operate normally.

  • Let the oil burner keep running, but watch the outer clutch finger (#3 in our sketch from Audel) in the contr9ol. You can see these parts easily when the control cover has been removed. (Watch out: Live Voltage!).

As the oil burner runs from the moment you've switched on its electrical power, you should see the clutch outer finger move outward until it engages the stop arm (#2). The drive shaft (#4) should continue to move outwards after the clutch finger reaches the stop arm. Only a small amount of movement is needed, but it's very important.

  • After letting the oil burner continue to run for about two to three minutes longer, open (turn off) and then immediately re-close (turn on) the electrical power to the oil burner (the line switch).
    Look at the second hand on your watch when you flip the electrical switch on and off, and begin timing the number of seconds until the oil burner re-starts.
  • If the oil burner restarts in less than one minute it is re-starting too soon. Turn off the electrical power again, let the heating system cool down. Then adjust the scavenger time period as follows:
  • Move the recycle stop lever (#1) outwards one notch. (You'll see detent notches on the steel rim against which the stop lever arm slides).
  • Watch the clutch finger (#3) as it moves outwards.
  • The clutch finger (#3) should move outwards until it engages the stop arm. The drive shaft (#4) should continue to move outward after the clutch finger reaches the stop. This continued movement, as we said before, is a small but important amount.
  • Now again switch electrical power to the oil burner on, let the system run as above, and then switch the electrical power quickly off and back on as before.
  • Again time the length of time until the burner re-starts. The oil burner should stop immediately and should not re-start until a minute or more has passed. If the scavenger period (the "down time" before the oil burner re-starts) is too short repeat this process, moving the stop lever one notch at a time until you've achieved more than a minute of scavenger time.

-- the above is paraphrased from Audel

Frequently Asked Questions (FAQs) about Stack Relays on Heating Equipment

Question: how long should it take for the stack relay to turn off the oil burner?

I have two really old used stack relays that I'm tinkering with to learn about them and want to know the seconds at when they are set to trip at usually? One of mine trips at 100 seconds and I have not tested the other but was wondering if that is not the right time or too long or if there is a way to lower that number so it trip at less seconds or is it fried past fixing cause I love to fix or rebuild and tinker with oil burner stuff?? Thanks Ben. Please reply. - B.B., Maine

Reply:

Ben: Typically safety switches cut off the burner at a "nominal" delay of 75 seconds (RA 116A and RA 117A Protectorelays) according to Honeywell[3] . 100 is a bit long but probably within tolerance in my opinion. Keep in mind that these are not lab grade instruments.

It is also my OPINION that in comparison with a cad cell relay switch, a stack relay type switch may have to let the oil burner run a bit longer before deciding to shut the system down. That's because the cad cell is right in the combustion chamber where it can "see" the flame (or not), while a stack relay is located in the flue vent connector - a location at which more time might be needed for the flue gases to reach a sufficient temperature to keep the switch closed (that is, to avoid turning off the burner).

The issue is the longer the oil burner gun assembly shoots unburned oil into the combustion chamber the greater the risk of a puffback when ignition finally occurs.

Exactly how long the stack relay takes to respond to the temperature in the flue vent connector depends on some variables besides the instrument itself including

  • Proper installation - that does not interfere with movement of the bimetallic spring and that does not, by contact with the equipment, conduct heat away from the sensor. Incidentally the device is capable of handling temperatures up to 1000F.
  • Proper installation location - not somewhere distant from the heater
  • Proper maintenance - a soot-coated stack relay is insulated from heat so will take longer to respond to temperature - possibly cutting off the system when it should not
  • The condition of the relays inside the switch and whether or not they have been "re-stepped" properly. You can see the re-step lever in our illustration in the Protectorelay article above.
  • The condition of any moving parts inside the switch that may have been bent or corroded due to abuse or poor environmental conditions.

When I worked on heating systems I found these switches reliable and very durable, and I note that at these Stack relays or Honeywell Protectorelay® devices have been in use for a very long time[2] and are still produced and installed and in use on some heating equipment.[3]

Modern versions of these Protectorelay® switches are the #RA117A1047/U (three wire control)[5] and the #RA116A1055 (stack relay)[6].

For a wiring schematic and installation instructions you can contact Honeywell Corporation at the location listed in our references below.

Cross Reference & Substitution Chart for Stack Switches and ProtectoRelay's

If you need to replace a stack relay switch and cannot find the same brand and model control, there are often several controls that can do the job. Your heating supplier can make sure you choose the proper safety control replacement, but here are some examples of cross referencing.

Honeywell's Protectorelay® and other stack relay switch installation instructions include a table of cross-references showing which Honey controls (or Penn Controls (Pen 664, Penn670, Penn 680)) should be used to perform the equivalent functions as controls made by other stack relay manufacturers including the following, courtesy of Honeywell Corporation[6]

  • White Rogers (WR 603, WR 611, WR 615 and WR 6L18),
  • General Electric GE (A101B2, GE CR7865)
  • General Perfex (GP 5200, GP 5300)
  • ITT General (ITT 5200, ITT R96A102A, ITT R96G102DC)
  • Mercoid (Mercoid - JM)
  • Detroit (Det CA 701 and CA 702).

Questions & Answers regarding this article

Questions & answers about oil heating equipment stack relay installation, diagnosis, repair, & replacement

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also list books on the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Stack Relay Switch - see detailed links at page left

  • [1] Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • [2] Audels Oil Burner Guide, Installing, Servicing, Repairing, Frank D. Graham, Theo. Audel & Co., New York 1946, 1947, 1955 (out of print, copies occasionally available from antique book dealers and on EBay). Originally this 364 page guide to oil burner installation, operation, diagnosis, and repair sold for $1.00 - one dollar.
  • [3] RA116A and RA117A Protectorelay®, Oil Burner Controls, Honeywell, 1985 Douglas Drive North, Golden Valley MN 55422-3992, Tel: 800-3456770 x 423, Website: customer.honeywell.com or in Canada: Honeywell Limited, 35 Dynamic Dr., Toronto, Ontario M1V 4Z9, website: www.honeywell.com, June 2000. Web search 4/3/2012, original source: http://customer.honeywell.com/techlit/pdf/63-0000s/63-9421.pdf
  • [4] Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • [5] Honeywell Protector Relay Controller 3-Wire # RA117A1047, Installation Instructions from Honeywell
  • [6] Honeywell Protectorelay Controller (Stack Switch) # RA116A1055, Installation Instructions from Honeywell
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com