InspectAPedia®

Heat anticipator adjustment tool from Amps Check Heat Anticipator Precise Adjustment Methods
How to use an ammeter to adjust or repair room thermostats by fine tuning the heat anticipator circuit

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Thermostat heat anticipator testing & fine tuning procedure: this article explains how and why we fine-tune a room thermostat or wall thermostat by checking its heat anticipator using a mini ammeter.

We describe the use of the T.D. Amps-Check mini ammeter specifically designed for thermostat heat anticipator adjustment.

This mini ammeter gives precise amps readings in the 0 - 1.2A AC range. By measuring the current (amperes) flowing through the thermostat contacts on a call for heat we can adjust the heat anticipator precisely to its optimal setting.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

How to Use a Mini Ammeter to Check Heat Anticipators and Thermostats for Proper Adjustment

Why do some thermostats include a heat anticipator?

Heat anticipator adjustment tool from Amps CheckSince a room heating or cooling thermostat is really just a simple "on-off" switch, some fuzziness needs to be built into the thermostat's control of the air conditioner or heating system, lest it cycle on and off too frequently, oscillating very closely around the set temperature.

Article contents

The job of the heat anticipator circuit in a wall thermostat is to prevent heating or cooling "overshoot" too far past the set temperature, but to permit some overshoot to prevent system on-off oscillation.

When we serviced heating systems and our clients sometimes complained that the thermostat did not seem to be responding as desired to room temperature.

The thermostat might permit the room to get much warmer, or much cooler than the temperature to which the thermostat was set.

This was a reason to whip out our little ammeter to see what was really going on with the thermostat circuit.

A second reason we'd use this ammeter to check the current draw of the thermostat circuit was to allow proper setting of a heating or air conditioning system control set which was made by a different manufacturer from the one who made the wall thermo sat.

For example, if the air conditioning or heating system control being switched on and off by the thermostat was not one of the ones in Honeywell's list, one of the checks we'd make is to actually measure the heating control circuit ampacity using a special mini ammeter sold just for that purpose, and shown in our photo at left.

Since we no longer service heating systems, we'll give our tool free to a trained heating service technician who'll pay the shipping postage.

How to Connect & Use a Low-Range or Mini Ammeter to Check the Thermostat Circuit and the Heat Anticipator

Thermostat heat anticipator ammeter measurement connections (C) InspectApediaWith the heat set "down", power to the equipment on, and the thermostat set to heating mode, the alligator clips are connected to the thermostat wire terminals in the thermostat.

Usually these are "R" (red) and "W" (white wire) or "R" and "Y" terminals on thermostats.

Just connect the ammeter's leads to the thermostat terminals where you see the red and white wires coming from the heating system are already wired. (You'll have to remove the thermostat cover to perform these steps.)

The current flow (Amps) is read on the meter, and the heat anticipator is set to match the actual current that was just read.

How to Make the Correct Current (Amps) measurement at the thermostat heat anticipator

  1. Turn power on to the heating system.
  2. Set the thermostat to call for heat
  3. Adjust the set temperature on the thermostat to well above current room temperature so that the heating system will operate
  4. Run the heat for at least five minutes to warm up the system to normal operating temperatures.
  5. Remove the thermostat cover (if necessary) to expose the R and W terminals. Connect the T.D. Amps-Chek or equivalent ammeter test leads onto the two thermostat terminals that make (connect or close) on a call for heat. These are the R and W terminals on most thermostats.
  6. Read the current flow indicated on the meter.
  7. Remember to re-set the room thermostat to the desired room temperature

Watch out: T.D. points out that a few controls, such as motorized gas valves, draw more current while operating than when they are in the fully-open position. So if your ammeter shows an unusually high reading (say more than 1.2A) you should hold the ammeter leads on the terminals for an entire minute. By that time the motorized valve should be fully open and you should see a lower AMPS reading. Examples of equipment where you will face this problem include

Watch out: the amps reading made at the room thermostat can also indicate a system or wiring problem: if the meter continues to read current over 1.2A there is probably a system problem, risking damage to the thermostat itself.

What is the Exactly Correct Heat Anticipator Setting when Using an Ammeter?

Heat anticipator scale (C) InspectAPedia


Set the heat anticipator pointer to the same AMPS reading on its heat anticipator scale as the actual AMPS or current read on the mini ammeter.

Example: thermostat 24VAC circuit reads 0.7A. Set the pointer to 0.7A on the scale as shown in our sketch at left.

What do we gain from fine-tuning the thermostat's heat anticipator adjustment?

This places the thermostat heat anticipator in exactly the right setting for the equipment to which it is attached. Then we simply removed our test leads and re-set the thermostat to the desired room temperature.

When the heat anticipator is working correctly, it prevents too much temperature "overshoot" when the thermostat is turning heating or air conditioning equipment on or off. Ultimately this means that the thermostat will maintain room temperature more accurately and more closely to the "SET" temperature set by the occupants.

Watch out for static cling that can foul up an ammeter reading when measuring a thermostat circuit

Precaution when using this equipment: if the meter is wrapped in plastic there may be a static charge when you unwrap it. Because it is very sensitive, any static charge on this meter (or many other ammeters or VOMs or multimeters) can cause the dial movement to show an erroneous reading. Just wait 5 minutes before using the meter, allowing the static charge to dissipate.

Where to Buy the Mini-Ammeter Amps-Chek® from T.D. Instruments or equivalent low-range high precision amps measuring instruments

...


Continue reading at HEAT ANTICIPATOR OPERATION or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see HEAT ANTICIPATOR ADJUSTMENT

Or see TEMPERATURE RESPONSE of ROOM THERMOSTATS

Suggested citation for this web page

HEAT ANTICIPATOR MINI AMMETER TEST at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ARTICLE INDEX to HVAC THERMOSTATS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman