InspectAPedia ® | ||||||||||||||||||||||||||
| Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice |
| |||||||||||||||||||||||||
| InspectAPedia Home |
| | Air Conditioning |
| | Electrical | | | Indoor Environment |
| | Exteriors | | | Heating | | | Home Inspection |
| | Insulate Ventilate |
| | Interiors | | | Mold Inspect/Test |
| | Plumbing Water Septic |
| | Roofing | | | Structure | | | Contact Us |
| Directory of Professionals to Inspect or Test a Building | ||||||||||||||||||||||||||
|
HEATING SYSTEMS AIR FILTERS for HVAC SYSTEMS AIRBOUND HEAT SYSTEM REPAIRS ANODES & DIP TUBES on WATER HEATERS ANTI SCALD VALVES BACKFLOW PREVENTERS BAROMETRIC DAMPERS BLOWER DOORS & AIR INFILTRATION BLUERAY Recall BOILERS, HEATING BOILER LEAKS CORROSION STAINS BOILER NOISE SMOKE ODORS BOILER OPERATING PROBLEMS BOILER OPERATION DETAILS BOILER PARTS LIST BOILER PRESSURE SETTINGS CARBON MONOXIDE/DIOXIDE CARBON MONOXIDE WARNING CHIMNEY INSPECTION DIAGNOSIS REPAIR CHIMNEYS & Flues - Asbestos Transite Pipe COOL OFF HEAT Thermostat Switch DRAFT REGULATORS - barometric dampers DUCT SYSTEMS DUCT SYSTEM DEFECTS DUCT INSULATION - Asbestos Paper DUCTS - Asbestos Transite Pipe DUST FROM HVAC? ELECTRIC HEAT ELECTRICAL POWER SWITCH FOR HEAT ENERGY SAVINGS in BUILDINGS ENERGY SAVINGS PRIORITIES ENERGY SAVINGS RETROFIT CASE STUDY ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE ENERGY SAVINGS RETROFIT OPTIONS FLUE VENT CONNECTORS FREEZE-PROOF A BUILDING FURNACES, HEATING FURNACE CONTROLS & SWITCHES CAD CELL RELAYS DRAFT HOODS DRAFT REGULATORS FAN AUTO ON CONTROLS FAN LIMIT SWITCH What is a Fan & Limit Switch? Sensing Furnace Temperatures How to Set the Fan & Limit Control How to Test the Fan & Limit Control How to Install the Fan & Limit Control How to Wire the Fan & Limit Control SPILL SWITCHES STACK RELAYS THERMOSTATS ZONE DAMPER CONTROLS FURNACE OPERATION DETAILS GAS PIPING, VALVES, CONTROLS HEAT EXCHANGER LEAKS HEAT LOSS in BUILDINGS HEAT LOSS DETECTION TOOLS HEAT LOSS INDICATORS HEAT LOSS R U & K VALUE CALCULATION HOUSEWRAP AIR & VAPOR BARRIERS HEATING COST SAVINGS METHODS HEATING LOSS DIAGNOSIS-BOILERS HEATING LOSS DIAGNOSIS-FURNACES HEATING OIL CLOUD WAX GEL POINT HEATING OIL EXPOSURE HAZARDS, LIMITS HEATING OIL SLUDGE HEATING SMALL LOADS HEAT PUMPS HEATING SYSTEM INSPECTION PROCEDURE HIGH EFFICIENCY BOILERS/FURNACES INSULATION & VENTILATION INSPECTION & IMPROVEMENT MOTOR OVERLOAD RESET SWITCH NO HEAT - BOILER / FURNACE DIAGNOSIS ODORS FROM HEATING SYSTEMS OIL BURNERS OIL BURNER INSPECTION GUIDE OIL BURNER NOISE SMOKE ODORS OIL BURNER SOOT & PUFFBACKS OIL FUEL TYPES & CHARACTERISTICS Oil Odors: Leaky Oil Tank Piping OIL SAFETY VALVES OIL TANKS OIL TANK LEAKS & SMELLS OIL TANK PIPING DEFECTS OIL TANK PRESSURE OIL TANK SLUDGE OIL TANK TESTING OIL TANKS, BURIED PLASTIC HEATER VENT PULSE COMBUSTION HEATERS RADIANT HEAT RADIANT HEAT Floor Mistakes to Avoid RADIANT SLAB FLOORING CHOICES RADIANT SLAB TUBING & FLUID CHOICES RADIATORS RELIEF VALVES - TP Valves on Boilers Relief Valves - Water Heaters SAFETY DURING HEATING INSPECTION Safety Recalls BLUERAY Recall CHIMNEYS & Flues - Asbestos Transite Goodman HTPV RECALL Heat Recovery Ventilator RECALL Lennox Furnace Manuals Lennox WARNING Weil McLain RECALL SPILL SWITCHES STACK RELAY SWITCHES STEAM HEATING SYSTEMS TANKLESS COILS THERMAL EXPANSION of MATERIALS THERMAL MASS in BUILDINGS THERMAL MASS in UPSTAIRS THERMAL TRACKING & HEAT LOSS THERMOSTATS Transite Pipes, Chimneys & Flues WINTERIZE A BUILDING More Information InspectAPedia Blog - News Updates Air Conditioning & Heat Pumps Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Bias Pledge Contact Us |
Guide to Temperature Settings on Combination Fan & Limit Switches for Furnaces
- Honeywell L4064B
|
|
Warning: when adjusting the set points on the combination furnace control be sure to hold the round faceplate dial steady with one hand while moving the sliding fingers or pointers in its face. Otherwise you may bend, strain, or damage the temperature sensing element (the bimetallic spring and related parts). Bending the element could make the control fail to sense temperature accurately and thus could be dangerous. Also do not "turn" the silver dial by hand to try to make the control turn on or off. This too can damage the control, making it unsafe. |
The furnace combination fan and limit control FAN OFF setting lets the furnace blower continue to run for an interval after the furnace burner has turned off, but will shut the blower off after the heat exchanger has been cooled down and the heat it contained has been sent to the occupied space.
The FAN OFF setting is the left-most metal finger protruding through the round silver plate of the fan limit control. Move the FAN OFF setting lever to the temperature at which the fan is to stop in order to prevent sending cool air into the occupied space.
From the factory the FAN OFF finger is usually set to about 90 degF.
At the end of a furnace-on heating cycle, after the gas or oil burner shuts down, the furnace blower will continue to operate for a time.
This continued fan operation achieves the following:
When an adequate warm temperature has been reached inside of the furnace warm air plenum chamber the FAN ON switch turns on the furnace blower to deliver warm air to the occupied space. The FAN ON setting on this control makes sure that the blower fan does not turn on too soon (even though the building thermostat has asked for heat) so that the furnace will not blow cool air into the occupied space. This setting also prevents the blower fan from cycling on and off too frequently during a heating cycle.
The FAN ON setting is the metal finger second from left-most, protruding through the round silver plate of the fan limit control. This finger is set to a temperature range from a minimum of 20 degF above the FAN OFF set point, to a maximum o f 30 degF below the LIMIT OFF set point.
From the factory the FAN ON is usually set to about 130 degF.
3. Furnace LIMIT OFF Setting
The LIMIT OFF indicator setting is a safety control that will turn off the oil or gas burner if temperatures inside the warm air plenum exceed a safe level. This is the highest temperature setting on a furnace combination control. It is set to the furnace warm air temperature at which this safety switch is to turn off the oil or gas (or other) burner or heat source. On the Honeywell L4064B the LIMIT OFF is set to a temperature between 100 degF and 250 degF.
If the temperature inside the supply plenum reaches the "high" limit set at the LIMIT OFF finger, the switch will
turn off the oil or gas burner. This condition may not ever happen under normal conditions with most hot air furnace systems - on those systems the burner continues to run all of the time the thermostat
is asking for heat. The LIMIT OFF or "HIGH" or "MAX" on the furnace fan limit switch is a safety device.
In the unusual event that temperatures inside the supply plenum become too high, when temperatures reach the LIMIT OFF setting the fan limit
switch will turn off the burner to prevent damage to the furnace heat exchanger (from warping or cracking from excessive temperatures)
From the factory this setting out of the box is 200 degF.
The LIMIT STOP control is an extra safety device to make it difficult for an amateur to set the LIMIT OFF to an unsafe or too-high temperature. This control setting could be changed by inserting a pen tip or similar object into the round hole visible in the LIMIT STOP plate near the right end of the temperature dial and slog on the silver plate of the fan limit control.
The LIMIT STOP is set at the factory to 200 degF. You should not change this setting as to do so maybe dangerous.
Fan override switch, also called a "manual fan switch" or "fan on switch" if present, is usually a white button that can be set to cause the furnace blower fan to run continuously or to run automatically driven by the temperatures sensed by the combination fan and limit control switch..
FAN ON SWITCH Settings:
After completing these control settings be sure you test the combination fan and limit switch for safe and proper operation. See How to Test the Fan & Limit Control for details.
...
Search InspectAPedia |
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
FAN LIMIT SWITCH
What is a Fan & Limit Switch?
Sensing Furnace Temperatures
How to Set the Fan & Limit Control
How to Test the Fan & Limit Control
How to Install the Fan & Limit Control
How to Wire the Fan & Limit Control
FURNACE CONTROLS & SWITCHES
CAD CELL RELAYS
STACK RELAYS
DRAFT HOODS
SPILL SWITCHES
DRAFT REGULATORS
FURNACE OPERATION DETAILS
HEAT EXCHANGER LEAKS
STACK RELAY SWITCHES
For details about the controls, components and switches commonly found on hot hot air heating systems see the articles listed below in which we explain how to identify, set, re-set, repair, replace, or avoid problems with the components of a furnace or warm air heating system.
|
|
![]() The Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems |
![]() Use this simple, economical mold test kit by following our instructions on how to collect and mail mold samples to our lab |
Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
|
![]() Building Inspection, Problem Diagnosis, Forensic Investigation & Testing, Repair Consulting |
|
|
05/25/2009 - 09/05/1997 - InspectAPedia.com/heat/FanLimitSwitch_L4064B_Settings.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark