InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

HEATING SYSTEMS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTERS
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  DIAGNOSE & FIX BOILER
  DRAFT REGULATORS, BAROMETRIC DAMPERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  OIL LINE QUICK STOP VALVES
  OIL LINE SAFETY VALVES
  Pressure Gauges, Boilers
  Pressure & Temperature Settings, Controls
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  Water Feeder Valves, Hydronic Boiler
  Zone Valves

BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUCT SYSTEM DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE EFFICIENCY, HIGH vs MID
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS

HEAT EXCHANGER LEAKS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS, DiAGNOSIS, REPAIR
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SMALL LOADS
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE
HEATING SYSTEM TYPES
HIGH EFFICIENCY BOILERS/FURNACES
HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion Products
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick Repair
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
SPILL SWITCHES
STACK RELAY SWITCHES
STAIN DIAGNOSIS on BUILDING INTERIORS
STEAM HEATING SYSTEMS

TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & FlueS

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE VALVES

More Information

LARGER VIEW of a heating boiler cad cell relay switchGuide to Heating System Boiler Controls & Switches
InspectAPedia®  -      

  • Troubleshooting guide for heating system boiler controls and switches
  • What are the basic components of heating systems?
  • How to inspect & repair central heating systems
  • An owner's guide to heating system controls and switches
  • Heating system bleeder valves
  • Aquastats on heating boilers
  • Cad cell relays on heating systems
  • Circulator pumps and pump relay switches on home heating systems
  • Heating system high limit and low limit and differential controls explained
  • Explanation of low water cutoff controls on boilers
  • Explanation of temperature & pressure relief valves on heating boilers
  • Explanation of heating boiler pressure gauges
  • Explanation of heating boiler water feed valves
  • Explanation of heating system zone valves
  • Questions & answers about controls used on heating system boilers: adjustments & settings, diagnosis, function, maintenance, repair or replacement

Heating system controls guide: This article describes the operating and safety controls on a Heating System Boiler - central heating systems. Start here to learn how to identify the different controls found on heating equipment. & to aid in troubleshooting, inspection, diagnosis, and repairs. The photo above shows a modern cad cell relay on an oil fired heating boiler - one of the safety controls which we discuss in this article.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Heating System Controls Inspection, Peripherals, Key Components

Photograph of an oil fired heater stack relayHere we describe the key operating and safety controls on heating boilers used to provide hot water heat through baseboards, convectors, radiators, and radiant heat flooring or ceilings. Because some controls are used in common on hot water heat, hot air heat, and steam boilers, readers should see these other articles: see BOILER CONTROLS & SWITCHES, and also see BOILER COMPONENTS & PARTS for a detailed list of heating boiler controls, other heating system components, parts such as circulator pumps & draft regulators.

If your building uses warm air heat, see  FURNACE CONTROLS & SWITCHES.
If your building uses steam heat see STEAM HEATING SYSTEMS.

How to Identify, Reset, or Adjust Hot Air Heat Furnace Controls and Switches

While going through the detailed sequence in the operation of the heating boiler, watch for and inspect the condition of the heating boiler controls and safety devices (as required by ASHI 9.1.A.3 automatic safety controls). Here we provide a list of most of the switches and controls found on heating systems. Each item is defined and we provide links to one or more detailed articles about the inspection, testing, setting, and use of each of these devices.

Air Bleeder Valves on Hot Water Heating Systems - the basics

Air scoop and air purge valve atop a heating boiler (C) Daniel FriedmanAir bleeder valves, manual or automatic, are installed on hot water heating systems at several places in order to remove unwanted air from the heating system.

Air trapped in hot water heating lines, radiators, baseboards, or convectors is not only responsible for a bubbling and gurgling noise, it can also actually prevent hot water from circulating, thus preventing the heating system from working.

See Air Bleeder Valves for details.


Aquastats: Combination or Multi Function Primary Controls (Aquastats) for Heating Boilers - A Guide

Photograph of a multi function combination control on a heating boilerCombination control or primary control on heating boilers: this control, such as a Honeywell R8182D combine High Limit and "Low Limit" boiler controls (The dial marked "low limit" on a combination control may or may not be in use depending on presence of a tankless coil).

This primary control, the most common type on modern heating boilers, controls the oil burner operation, turning the burner on or off as the boiler low limit or high limit temperatures are reached respectively.

This control may switch on and off a single circulator pump, and if a tankless coil is installed on the boiler, it may also turn the oil burner on and off as needed to maintain temperature in the boiler to provide domestic hot water as well.

  • Combination Control High Limit: On a typical combination control, the "Hi Limit" is the cut-off temperature for the heating boiler on a call for heat. The cut-on temperature is hard wired in this control at about 15 degF below the "Hi Limit" setting.
  • Combination Control Low Limit: On these controls the "Low Limit" is NOT the "cut on" point for heat but rather it is a setting which is intended to maintain heat inside the boiler in order to assure that the boiler can produce hot water when a tankless coil is installed.
  • The "Low Limit" is normally set at least 20 degF below the "Hi Limit" to avoid a "lockout" condition on this control which we discuss just below. During warm months when the boiler is not being called-on to heat the building itself, the "Low Limit" keeps heat in the boiler for the tankless coil. So the "Low Limit" is actually a "low range" operating upper limit on boiler temperature that applies out of the heating season.
  • Combination Control Differential: On this control, the "Diff" or differential control dial specifies the amount below the "Low Limit" to which boiler temperature can fall before the boiler should turn on to keep the boiler warm for making domestic hot water through the tankless coil.
  • Details about the control settings of boiler aquastats and how to set these devices to save money on heat, remain safe, and function properly, can be read at AQUASTAT CONTROL Functions
  • For a discussion about individual High Limit Switches and Low Limit Switches and controls on hot water heating boilers see High Limit Controls and Low Limit Controls

Backflow Preventer Valves on Heating Boilers - A Different Check Valve

Backflow preventer (C) Daniel Friedman

 

Backflow preventers are a different type of check valve found on heating systems.

The backflow preventer is installed to keep hot, high pressure water in the hydronic heating system from flowing backwards through a boiler water feed line into the building water supply - a sanitation concern.

See Check Valves Flow Control Valves Flo Control.


Cad Cell Relay Switches on Oil Fired Heating Boilers & Furnaces - the basics

Photograph of an oil fired heater stack relayFlame sensing devices on heating boilers: modern heating boilers using an oil burner for heat source use a Cadmium Cell sensor, usually located inside the oil burner tube, to "see" the presence of flame and thus to assure that the oil burner assembly stops pumping oil into the combustion chamber if flame ignition is unsuccessful.

Some older heating boilers, steam boilers, and water heaters may use a stack relay switch to confirm oil burner operation.


Heating Boiler Oil-burners use either a cad cell or stack relay to confirm that the furnace oil burner is operating properly and to avoid flooding the combustion chamber with un-burned oil.

See CAD CELL RELAY SWITCH and   Stack Relay Switch .

  • Boiler Cad Cell Relays Explained Modern heating boilers use a Cadmium Cell sensor, usually located inside the oil burner tube, to "see" the presence of flame and thus to assure that the oil burner assembly stops pumping oil into the combustion chamber if flame ignition is unsuccessful.
  • The cad cell is wired to a relay switch (usually a gray box with a red "reset" button located on top of the oil burner) which switches the oil burner off when a flame is not established in the burner.
  • Resetting the Oil Burner Cad Cell Relay: if the red button on the cad cell relay is sticking up and the oil burner has shut down, the homeowner is permitted to try ONCE to "reset" the system by pressing the red reset button. If the oil burner does not turn on and run normally and continuously (no smoke, no loud noises, etc.) for at least 5 or 10 minutes after resetting the relay or pressing the reset button, DO NOT keep resetting the system since doing so can flood the combustion chamber with un-burned heating oil - a dangerous condition.
  • Details about Cad Cell relay switches, how to inspect, test, and reset them can be read at CAD CELL RELAY SWITCH

Check Valves Prevent Un-wanted Gravity or Convection Circulation of Hot Water

Boiler check valve or flow control valve (C) Daniel FriedmanIf electrical power switch to a hot water heating boiler is in the on position (see ELECTRICAL POWER SWITCH FOR HEAT) and the room thermostat is set above room temperature, the heating system (hot water or steam) boiler or (warm air) furnace should not run.

And hot water should not be circulating through the building's radiators or baseboards.

But for hot water heating systems (baseboards, radiators), check valve settings (in the forced-on position) or other internal defects could cause or permit hot water to circulate through the heating system by "gravity" (convection, that is warm water rising on its own through the heating piping) even though the thermostat is not calling for heat.

The problem, if this is occurring, is usually that a check valve (photo above-left) (found internal to some circulator pumps, or external as a physical device) intended to prevent hot water from circulating on its own - when the circulator pump is off - is either set to a "forced open" position, or it has become defective.

If that's the problem (diagnosed by a heating and service technician) then the valve or circulator needs to be replaced. While waiting for that repair to be made, you can still turn off the heat, by turning off electrical power to the boiler.

See CHECK VALVES, HEATING SYSTEM for more about various kinds of check valves and flow-control or flo-control valves on heating boilers.

Circulator pumps & circulator relay switches on gas or oil fired heating boilers - the basics

LARGER VIEW of a heating boiler circulator pump set

Circulator pumps & relays on heating boilers - an older and by some heating service technicians, a preferred method to control the distribution of heat to individual building areas uses a individual circulator pump to force heating water through each individual heating zone piping.

This system too is usually found on hot water baseboard heating systems.

Two or more circulator relay switches, one relay for each circulator pump, will be installed to turn on and off each heating water circulator if more than one heating circulator is installed. Individual low-voltage thermostats located in the living area will respond to a call for heat by switching on the circulator relay which in turns on the (120V) circulator pump.

Details about circulator pumps and circulator relay controls can be read at Circulator Pumps & Relays.

Differential Bypass Valves - BG

Differential bypass valve from BandG

Differential bypass valves are not usually found on residential heating systems, but you may encounter one. According to B&G:

The differential bypass valve is used in systems where heating loads may be excluded from the circuit as zone valves close. It controls the excess flow in the system by acting as a bypass while ensuring adequate flow to the remaining open circuits. The differential bypass valve helps reduce velocity noise caused by excess flow through the circuits while maintaining the pump head at a constant value. The differential by-pass valve should be installed after the pump between the supply and return piping. It can be installed either in the horizontal or vertical position provided it is in accordance with the direction of flow as indicated by the arrow on the valve body.

Electrical Switches that Control Heating Systems - the basics

LARGER VIEW of an octopus furnace

An electrical on-off switch is located out of the heating equipment room and serves to turn off electrical power to heating equipment in an emergency. This switch should be one of the first things you check if your building has no heat, as someone may have turned it off on purpose (such as for safety reasons) or by accident.

A second electrical switch is located on or close to the heating equipment.

A third electrical switch or fuse turns off power to the heating equipment service at the building electrical panel.

See ELECTRICAL POWER SWITCH FOR HEAT wHere we explain these electrical switches on heating systems in more detail.

Heating Thermostats & How They are Set

Photograph of an oil fired heater stack relay

Heating & Air Conditioning Thermostats where are thermostats usually located, what types of thermostatic controls are used on various heating and cooling systems, how do we find all of the thermostats, how do we set, adjust, and use thermostats

The round Honeywell (R) wall thermostat shown in this photo has been locked in a plastic enclosure to prevent people from changing its set temperature. Set temperature and how the thermostat works are described in excruciating detail below.

Room thermostats for air conditioning work and are set the same as when these devices are used for controlling heating systems. We provide lots of detail about how these devices work - see THERMOSTATS for complete details.

High Limit Controls and Low Limit Controls on Heating Boilers - the basics of single limit switches

Limit switch on a steam boiler tankless coil

Individual High Limit and Low Limit relay switches on heating boilers: these may be provided on older heating boilers.

A separate high limit control, usually mounted near the top of the heating boiler monitors boiler temperature and shuts off the oil or gas burner when that limit has been reached.

A separate low limit control (that looks like the high limit unit), usually mounted lower on the heating boiler monitors boiler temperature and turns on the oil or gas burner when the heating boiler internal water temperature reaches the low limit.

Details about individual limit switches and controls on boilers can be read at Limit Switches, Boilers.

Stack Relay Controls on Oil Fired Heating Boilers & Furnaces - the Basics

LARGER VIEW of stack relay switch on an oil fired heaterOil Burner Stack Relay Switches Explained Older oil burners may use a Stack Relay to accomplish the same purpose (turn off the oil burner if the flame is not established).

The "stack relay" is a bimetallic spring inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney. The bimetallic spring warms in response to hot oil burner exhaust, confirming that combustion is taking place.

If combustion is not occurring a timer inside the stack relay turns off the oil burner to prevent flooding of the combustion chamber with un-burned oil.

For details concerning this device see Stack Relay Switch

LARGER VIEW of a steam boiler low water cutoff control
Low water cutoff
on steam heating boilers and on some hot water heating boilers: on both some hydronic (water) and all steam type heating boiler systems a sensor is installed on some modern heating boilers (and on virtually all steam boilers) to turn off the oil burner should the water level or pressure in the system fall below a safe level.

For details see LOW WATER CUTOFF CONTROLS


Pressure relief valve - unsafe (C) Daniel FriedmanPressure and Temperature Relief Valve on heating boilers: a TP valve is installed on all modern heating boilers to release hot water and pressure should the boiler's internal pressure or temperature rise to an unsafe level.

The relief valve should be piped to a few inches from the floor with the end of the discharge tube always in a visible location so that if it is leaking or open the building owner or manager can observe that (unsafe) condition. Some very old heating boilers may not have a relief valve installed.

These systems used a pressure relieving overflow tank located high in the building, above any upper floor radiators or baseboards, often in the building attic.

The attic pressure tank was open to the atmosphere and often itself included an overflow pipe which would permit any excess water (or pressure) to flow out of the tank and out of the building, perhaps through a building wall to the outdoors. While these systems worked well for decades, placing a temperature relief valve right on or very close to the heating boiler is a safer installation.

See RELIEF VALVES - TP VALVES for details.

Boiler pressure gaugePressure and Temperature gauge on heating boilers: this gauge displays the heating boiler internal pressure and temperature.

Typical pressure for a residential boiler serving a two story home would show 12 psi cold, and less than 30 psi hot. Over 30 psi boiler pressure will cause the pressure relief valve to open.

Typical hydronic heating boiler operating temperature settings are LO-120-160 HI-180-200 degF. At 200 degF. we'll see should see pressure under 30 psi.

Typical operating temperature observed at the gauge will be below the high, and can be as low as nighttime room temperature in non-heating season if no tankless coil is in use. The temperature/pressure gauge may help in checking for normal conditions before and during boiler operation. However the gauge can be wrong!)

See GAUGES ON HEATING EQUIPMENT for more details about pressure gauges on hydronic (hot water) heating boilers.

Pressure gauges for steam boilers are discussed at Steam Pressure Gauge.


Photograph of a multi function combination control on a heating boiler Tankless coil use on heating boilers: This device is not itself a boiler "control" but boiler controls include features to make the coil work properly.

A tankless coil is basically a coil of finned copper tubing which is inserted into the heating boiler, is used to provide domestic hot water to some buildings. Watch out for leaks at piping fittings or more seriously the coil mounting plate which bolts the coil to the boiler (leaks at this location can destroy a steel boiler).

Watch out also for missing a mixing/tempering valve which mixes cold in with the outgoing hot water to avoid scalding temperatures at nearby taps.

Some building jurisdictions require a separate temperature/pressure relief valve on hot water piping at the boiler. The photo shows a pile of tankless coils found in a building basement next to the heating boiler. We suspected that high mineral content in the building's water supply was causing frequent coil clogging.

See TANKLESS COILS for details. If you see a pile of tankless coils in a home (our photo above) you can guess that there has been a problem with hard water and tankless coil clogging - the home needs a water softener - see WATER SOFTENERS & CONDITIONERS.

Water Feeder Valves on Hot Water and Steam Heating Systems - the basics

Automatic water feeder valveAutomatic water feeder and Expansion Tank on heating boilers - these are often controlled in a single unit on modern heating boilers which use an Amtrol or similar expansion tank. The water feeder is the brass assembly at the bottom of the expansion tank on these units.

On older heating boilers the expansion tank and water feeder valve are separate physical units. On these older systems the "automatic water feeder" is often a bell-shaped device which opens and sends makeup water into the heating boiler and its piping whenever the heating system's internal water pressure falls below a normal level (perhaps 12 psi when the boiler is cold).

Some older heating systems may not have an automatic water feeder and may only provide a manually operated valve to add water to the boiler.

Systems without an automatic water feeder are less safe and risk serious boiler damage should boiler water be lost and should there be no low water cutoff installed on the system. See WATER FEEDER VALVES for details about water feed valves for hydronic boilers. Steam boiler automatic water feed valves are discussed at WATER FEEDER Valves, Steam.

Zone Valves on Hot Water Heating Systems - the basics

Honeywell heating zone valveZone valves on heating boilers - heating water piping in a building, particularly where hot water baseboard heat is used, may be divided into separate heating zones (different floors, or different areas on a single floor) to permit more detailed control of heat distribution in a building.

The control of heating water through these different heating zones may be accomplished by use of zone valves (one per heating zone or area or "loop" of heating piping) which in turn are connected to individual thermostats.

When the thermostat calls for heat in a particular building area, the thermostat switch causes the zone valve to open, to permit hot water to flow through that zone. When the zone valve is fully open, an "end switch" inside the valve tells the heating system's circulator to begin operating, causing hot water to flow through the zone.

Typically heating systems using zone valves will have two or more zone valves (usually but not always located close to the heating boiler) and a single circulator pump (usually located on the return end of the hot water piping close to the heating boiler).

Details about zone valves on hot water heating systems can be read at Zone Valves.

Questions & Answers regarding this article

Questions & answers about controls used on heating system boilers: adjustments & settings, diagnosis, function, maintenance, repair or replacement

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES - see detailed links at page left

  • Bell & Gossett Air Separators and other heating system components, Bell & Gossett, 8200 N. Austin Ave., Morton Grove IL 60053, USA - Tel 847 966-3700 Fax 847 965-8379.
  • Thanks to Bottini Fuel service manager Ron Thomas for discussing aquastat functions, low limit controls, oil burner short cycling causes, and boiler maintenance, reliability, and service contracts 4/13/2010. Bottini Fuel is a residential and commercial heating oil distributor and oil heat service company in Wappingers Falls, NY and with offices in other New York locations. Bottini Fuel, 2785 W Main St, Wappingers Falls NY, 12590-1576 (845) 297-5580 more contact information for Bottini Fuel

How to Identify, Reset, or Adjust Hot Water Heating Boiler or Steam Boiler Controls and Switches

For details about the controls, components and switches commonly found on hot water heating systems see the articles listed below in which we explain how to identify, set, re-set, repair, replace, or avoid problems with the components of a hot water heating system.

  • Hot Water Heating Boiler Operating Details - 39 Steps to Hot Water Heating Success
  • Air Bleeder Valves for Hot Water Heating Systems: Radiators, Baseboards, Convectors
  • Aquastats Heating Boiler Primary Controls: A guide to Aquastats for control of hot water heating boilers and tankless coils
  • BLUE vs YELLOW COMBUSTION FLAMES - the Blueray history and blue flame vs. yellow flame combustion, flame color & combustion efficiency, & how oil competes with gas as a heating fuel.
  • CAD CELL RELAY SWITCH on oil fired furnaces or boilers as flame sensors & safety devices
  • Check Valves Guide to check valves and backflow preventers on hydronic (hot water) heating systems (gas or oil fired)
  • Circulator Pumps Guide to circulator pumps and circulator relays on hydronic (hot water) heating systems (gas or oil fired)
  • Draft Hoods on gas fired heating equipment, function and safety
  • Draft Regulators & barometric dampers on oil fired heating equipment
  • Electrical Power Switches: Where to Turn On or Off Heaters for Furnaces & Boilers, Heat Pumps or Electric Furnaces or Air Conditioners
  • Expansion Tanks Guide to pressure control and expansion tanks on hydronic (hot water) heating systems (gas or oil fired)
  • Flue Gas Spill Switch on gas fired heating equipment sense combustion and protect from blocked flues
  • Gas Piping, Valves, Controls: Guide to LP and natural gas meters, valves, tanks, piping, gas leaks, gas regulator assembly & other gas controls
  • Gauges for Temperature & Pressure: Guide Temperature & Pressure Gauges on Hot Water or Steam Heating Boilers
  • LOW WATER CUTOFF CONTROLS: Guide to LWCOs on hot water heating systems
  • MIXING / ANTI-SCALD VALVES: Guide to mixing valves on hot water heating systems and radiant heat systems
  • Oil Burners: Guide to Oil Burners for heating systems, boilers & Furnaces: basic parts, operation, maintenance, performance & money-saving tips
  • Oil Tanks: Guide to Heating Oil Underground & Above ground Oil Storage Tank Leaks, Testing, Problems & Solutions, Home Buyer's / Home Owner's Guide
  • Oil Piping: A guide to heating oil piping, valves, controls, leaks, repairs for heating systems
  • Parts & Components Guide for Heating Boilers: How to Identify the Components of Hot Water Heating Boilers - A Guide to Hydronic Heating System Parts
  • RELIEF VALVES - TP VALVES: A guide to temperature and pressure relief valves & safety controls on hot water and steam heating systems
  • Stack Relay Switches: Guide to finding, resetting, maintaining stack relays on oil fired furnaces or boilers as flame sensors & safety devices
  • TANKLESS COILS: A Guide to tankless coils used to produce domestic hot water on heating boilers: hot water quantity, safety, temperature control, leaks, corrosion, repairs
  • Thermostats & Heat Controls for furnaces & boilers, oil & gas fired, heat pumps or electric furnaces or boilers
  • Water Feed Valves: A guide to water-feeding/pressure-reducing valves on hot water and steam heating systems
  • Zone Valves: A guide to zone valves for heating zone control on hot water heating systems

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com