InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
ANODES & DIP TUBES on WATER HEATERS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTERS
BACKDRAFTING HEATING EQUIPMENT
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPES RADIATORS
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  Air Bleeder Valves
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  DIAGNOSE & FIX BOILER
  DRAFT REGULATORS, BAROMETRIC DAMPERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  OIL LINE QUICK STOP VALVES
  OIL LINE SAFETY VALVES
  Pressure Gauges, Boilers
  Pressure & Temperature Settings, Controls
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  Water Feeder Valves, Hydronic Boiler
  Zone Valves

BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
  Types of Boiler Defects
  Air-bound radiators, baseboards, boilers
  COMBUSTION AIR DEFECTS
  Diagnose Loss of Heat
  Diagnose Oil Heat Noises
  FUEL UNIT, HEATING OIL PUMPS
  GAS BURNER Flame & Noise Defects
  OIL BURNER NOISE SMOKE ODORS
  OIL BURNER SOOT & PUFFBACKS
  Heat Won't Turn Off - Stop Unwanted Heat
  Heating Malfunctions & Implications
  Heating Defects & Implications
  Leaks at Heating Boilers
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch

COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE EFFICIENCY, HIGH vs MID
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAKS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES, Heat, Insulation prevent Freeze-Up
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SMALL LOADS

HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM INSPECTION DETAILS
HEATING SYSTEM NOISES

HEATING SYSTEM TYPES

HIGH EFFICIENCY BOILERS/FURNACES

HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion Products
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick Repair
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters

SOLAR ENERGY SYSTEMS
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES
STAIN DIAGNOSIS on BUILDING INTERIORS
STEAM HEATING SYSTEMS

TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION

WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY
ZONE VALVES

More Information

Automatic water feed valve (C) Daniel FriedmanGuide to Fixing an Air-Bound Hot Water Heating System - Procedure#1, Using Built-In Controls & Valves
InspectAPedia® -

  • Service Procedures to force air out of an air-bound hot water heating system
  • How to diagnose cold heating baseboards or radiators
  • How to diagnose heating circulator pumps that won't stop running
  • Guide to Air Bleeder Valves on Heating Systems: Heating System Radiator, Baseboard, or Convector Air Bleeder Valve Troubleshooting & Repair Guide
  • Cold radiators: if your radiators won't get hot : how to check for an airbound radiator and other causes
  • How to diagnose and fix heating system noises & air in hot water heating system pipes
  • Questions & answers about fixing an air-bound hot water heating system

Airbound heating baseboard or radiator repairs: Here we explain how to remove un-wanted, air from noisy or air-bound hot water heating system pipes, radiators, convectors, and baseboards using the automatic water feed valve on a heating boiler. If a hot water heating system develops too much air in the piping you may hear bubbling or gurgling in the heating pipes when the heating system is operating, or worse, so much air may be in the heating piping, radiators, or baseboards that heat may simply not circulate at all.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Diagnosing an Air-Bound Hot Water Heating System

If heating radiators or baseboards of your building are not getting hot, or if your building circulator pump runs continuously but heat is not being delivered to the heating zone served by that circulator, the discussion here can help diagnose and cure that problem.

Readers should also see Diagnose Oil Heat Noises for diagnosis and repair of other heating system noises on both oil and gas fired heating equipment. This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

If you don't know what kind of heat your building uses, we explain how to figure out the answer at HEATING SYSTEM TYPES. If your heating system is not working properly, see NO HEAT - BOILER or NO HEAT - FURNACE. This article series answers nearly all questions about Heating System Boiler Controls on central heating systems to aid in troubleshooting, inspection, diagnosis, and repairs. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

Question: Why does my heating circulator keep on running?

Here’s the problem, I have a one pump three zone hot water baseboard heating system. The circulating pump keeps running even though there is not call for heat. This happens even in the summer, so I just shut the emergency switch off, but now, it’s getting cold and I want to turn the system on. One of the zones does not get heat, so I replaced the TACO zone valve head thinking that was the problem.

Well, the pump is still running, and no heat even when the thermostat is set to 90. The furnace does not fire up either. I plan on eliminating the thermostat to see if the furnace would turn on by touching the two wires together, but saw your email and decided to write to you first.

The other two zones do heat up when heat is called. This is an American Standard system that was installed new in 1960. The pump has been changed a few times over the years. Any suggestions? - anonymous, Union NJ

Reply:

Your heating system baseboard, hot water piping, or one or more radiators may have become airbound if:

Your thermostat for the heating zone(s) involved is calling for heat, the boiler is hot, the circulator pump is running, but all or part of the heating zone served by that circulator pump is not getting hot. More than one problem could cause this symptom but below we list possible causes in order of probability:

  1. The heating pipe, baseboard or radiator has become air-bound: this means that a sufficient volume of air has become trapped in the radiator or hot water distribution piping or baseboard piping so that the circulator is unable to cause hot water to circulate through the heating distribution system. Keep in mind that most circulator pumps do not have a lot of "lift" or water pushing ability. To be able to move hot water around the heating piping loop the circulator pump depends on the piping being full of water, so that water "falling" on the return side of the heat piping loop reduces the "lift" needed to be provided by the circulator pump.

    If this is the problem your heating system is having, the article below explains how to cure the difficulty as well as how to prevent it from happening again.
  2. A check or control valve in the heating water piping system that should be open happens to be closed, such as a stuck heating zone valve (see ZONE VALVES) or a flo-control valve that has been manually put into the "closed" position (see CHECK VALVES, HEATING SYSTEM).
  3. A room heating thermostat may be stuck, damaged, or set too high - see THERMOSTATS. On occasion a heating zone control relay could also be stuck or damaged, but we don't encounter that problem often. If the circulator keeps running even when you are not calling for heat, such as in summer (the reader's example above) there could be the problem at the thermostat, zone valve switch, or circulator pump relay switch. Typically we inspect and eliminate each of these in turn.

    Watch out: Be careful to turn off electrical power before working on thermostats or other electrical components. In addition to shock hazards, shorting a wire can add to your troubleshooting woes by blowing a hidden fuse (such as on a control board), or damaging a component such as a transformer.
  4. The circulator pump itself could be damaged or defective. Try checking the problems above first. If none of those conditions apply, you may need to replace the circulator pump or pump assembly or motor.
  5. There could be some other problem we haven't thought of but that your experienced heating service technician may point out. CONTACT us to add that information here to help others.

In this article we explain how to locate, inspect, diagnose problems with, use, or replace automatic and manual air bleed valves on hot water heat, and we explain methods used to remove air from air-bound hot water heating systems by finding and repairing or using automatic or manual air bleeder valves, or by using two different service procedures to force air out of air bound pipes in a hot water heating system. This article is divided into these main sections:

Our discussion of radiators or baseboards that do not get hot when they should includes these key sections:

  1. Air Bleeder Valves - a Guide to Air Bleeder Valves for Hot Water Heating Systems: Radiators, Baseboards, Convectors - how to find and use manual and automatic air bleeders to fix noisy gurgling heating pipes or an airbound heating system. Air purges for steam heating systems are discussed separately at Steam Vents.
  2. Air Scoops, Air Separators, Air Purgers: Since on many hot water heating systems a key air bleeding or air vent point is at the air scoop or air separator closer to the boiler, see Air Scoops Purgers Separators.
  3. Airbound Heating System Relief Procedure #1 Using Water Feeder & Boiler Drain - how to use built-in controls and valves to force air out an air-bound heating system whose radiators, convectors, or baseboards are not warming up
  4. Airbound Heating System Relief Procedure #2 Using a Pony Pump - how to use a portable pump, short sections of garden hose, and heating system valves to force air out an air-bound heating system whose radiators, convectors, or baseboards are not warming up.
  5. WATER FEEDER Valves, Hydronic - a defective automatic water feeder valve on a hot water heating boiler can result in too little starting water pressure in the system - radiators on upper floors may fail to receive heat. On a steam heating boiler a defective automatic water feed valve can cause the heating system to shut down completely or can lead to boiler damage or even unsafe conditions.

    At BOILER PRESSURE & TEMPERATURE SETTINGS we discuss the pressures needed for hydronic or hot water heating systems - a taller building needs higher starting (cold) pressure in the heating boiler. At WATER FEEDER Valves, Hydronic we discuss problems with water feeder valves that also control water pressure in the boiler and we explain how to adjust the water feeder valve and thus boiler water pressure. If your heating system uses a steam boiler, see WATER FEEDER Valves, Steam.

Service Procedures: How to Fix an Air-Bound Hot Water Heating System

Here we describe the procedure that a heating service technician may use to remove un-wanted air in a hot water heating system in order to correct noisy gurgling pipes or to correct loss of heat due to an air-bound radiator, heating convector, or section of hot water heating baseboard.

If your hot water heating system has become air-bound (one or more sections of heating radiators or baseboards are staying cold even though the boiler is on and the circulator pump is running), and if your system does not have an air bleed valve to remove air blocking water flow, you probably need to call a heating service technician who will use one of the methods we describe here.

If your heating system does include both automatic and manual air-bleeder valves it is possible that you can correct a noisy or airbound heating system yourself. See Air Bleeder Valves and then How to Open Manual Air Bleeder Valves.

Airbound Heating System Relief Procedure #1 Using Water Feeder & Boiler Drain

We use this procedure to remove air blocking heating water flow through baseboards or radiators when there is no convenient air bleed valve already installed on the airbound section of heating baseboard or radiator.

Of course if your heating system already has air bleeder valves (see Air Bleeder Valves) installed on high sections of baseboard or radiators (higher hydronic heat delivery baseboards or radiators are the more likelyi ones to become airbound as air naturally migrates upwards to highest piping in the heating system) you should try opening one or more of those first to see if you can bleed out the air.

LARGER VIEW of a heating boiler cad cell relay switchThe following procedure is the more simple of the two we describe for correcting an air-bound hot water (hydronic) heating system, and it avoids the need to use pumps or to install extra service drains that may have been omitted on the heating system. While this is the easiest and simplest procedure to remove air from an airbound heating system, you might not want to use this method if

  • The boiler is very hot and it is a cast iron unit that could be cracked by a sudden surge of incoming very cold water
  • The heating system has been filled with antifreeze.
  • The heating boiler drain (located at or near the bottom of the boiler) is in poor condition and may not be opened and then closed reliably.

In these cases see Procedure #2 at Air-bound heating systems part-2.

Here are the steps in airbound heat remedy #1

  1. Turn off the heating boiler, using the service switch. If necessary, see ELECTRICAL POWER SWITCH FOR HEAT.
  2. Confirm that the heating system appears to be air-bound: heat is on and boiler temperature is up and the circulator pump is running; by touch the technician confirms that one or more sections of radiator, convector, or heating baseboard remain cold even though all radiator or convector or other circulating system valves are in the open position.
  3. Heating boiler drain (C) Daniel Friedman

    Connect a garden hose to the boiler drain and run the end of the hose outside or to a convenient indoor building drain. Open this drain.

    Our photo (left) shows a typical boiler drain valve - this one has been leaking, as you can see by the stain on the floor and the mineral deposits on the drain valve.

    All boiler drains have threads that accept a standard garden hose.












  4. LARGER VIEW of a heating boiler cad cell relay switchOpen the water feeder bypass: Locate and open the bypass or "over-ride" on the automatic water-feeder pressure-reducer on the heating boiler.

    On a residential heating boiler the automatic water-feeder/pressure reducing valve that automatically provides makeup water to the heating boiler if pressure drops below 12 psi. (12 psi is for typical U.S. / Canadian residential heating systems normal cold temperature starting pressure. U.K. and european heating systems should be pressurized to between 1 and 1.5 bar - cold.)

    Usually this valve has a lever that can be lifted to temporarily bypass the pressure-reducing function and feed water directly to the heating boiler at street water pressure (up to 70 psi). See Water Feeder Valves, Hydronic Boiler for details about how this valve works.

    Lift the lever to feed high pressure water into the heating boiler. This should also force high pressure water through the heating distribution pipes, radiators, convectors, or baseboards, forcing air out of those components.

    Pressure in the boiler should not exceed 30 psi (otherwise the pressure/temperature relief valve will begin to spill water). Let the water "run" through the heating system, watching the hose output end for evidence that air along with water is spurting out of the hose.

  5. Close the water feeder bypass and quickly move to step 6 just below. This will stop forcing higher-pressure water into the boiler and the heating system piping.
  6. Close the boiler drain valve. This will stop water from leaving the boiler.
  7. Set the proper boiler cold water pressure: The automatic water feeder will put additional water into the boiler until it reaches its starting pressure.

    If the boiler pressure is below its normal level the automatic water feeder should correct this problem. Watch the boiler pressure fill up to its normal cold pressure setting - typically this is around 12 psi on a two story home.

    If the boiler pressure is too high and the boiler is cold, use the boiler drain to drop the boiler pressure to the proper starting level.

    See Water Feeder Valves, Hydronic Boiler for a description of the typical pressures needed in residential hot water heating systems depending on the height of the highest radiator or baseboard above the heating boiler.
  8. Turn on the heating boiler and assure that the thermostat is calling for heat. When the system has reached normal operating temperature and pressure, check the radiators, convectors, or baseboard sections that were previously cold - they should now be warm.

    If the previously cold radiator (etc) still remains cold, either you have not removed enough air from the system or there is another problem causing loss of heat. In that case see HEATING LOSS DIAGNOSIS-BOILERS.
  9. Check the boiler drain valve to be sure it's not leaking. In an emergency we screw a garden hose cap on the end of a leaky heating boiler drain.
  10. Monitor heating system operation: we never leave a property where we have worked on the heating system without first checking for leaks, inspecting for obvious safety hazards (such as a bad relief valve, blocked flue, improper oil or gas burner operation), and confirming that the heating system runs through it's on-off cycle normally.

How Do we Know That the Air Bleed Valve Operation Has Been Successful?

  • If you open a manual air bleeder valve on a hot water heating system and air hisses out, there was air that needed removal. If only water comes out, that device was not the one that is air bound.
  • If the heating boiler is already running and hot, quite quickly, in a minute or three, the radiator or convector that was air bound will get hot to the touch. Feel first at the pipes that enter the radiator, convector or heating baseboard since that's where hot water will begin entering the previously air-bound device.

Contact us if you have other suggestions for improving this procedure. We are pleased to give credit and links to contributing reviewers, authors, or critics.

Questions & Answers regarding this article

Questions & answers about fixing an air-bound hot water heating system

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.


BOILERS, HEATING
BOILER OPERATION DETAILS
BOILER CONTROLS & SWITCHES
Air Bleeder Valves
Air-bound boilers & radiators
Air-bound heating systems part-2

  • Thanks to reader Les Luka for pointing out that we needed to clarify step 5-6 in the air bleed procedure, 08/03/2010
  • Thanks to (anonymous) reader for discussing circulator run-on problems, October 2010

For details about the setting, re-setting, or function of the controls and switches commonly found on hot air heating systems see these articles:

  • Hot Air Heating Furnace Basic Operating Steps
  • Guide to Heating System Components: see BOILER CONTROLS & SWITCHES and FURNACE CONTROLS & SWITCHES and STEAM HEATING SYSTEMS or if appropriate for your building, RADIANT HEAT. If your building uses a heat pump, see AIR CONDITIONING & Heat Pump SYSTEMS
  • Air Bleeder Valves for Hot Water Heating Systems: Radiators, Baseboards, Convectors
  • Aquastats Heating Boiler Primary Controls: A guide to Aquastats for control of hot water heating boilers and tankless coils
  • CAD CELL RELAY SWITCH on oil fired furnaces or boilers as flame sensors & safety devices
  • Check Valves Guide to check valves and backflow preventers on hydronic hot water heating systems gas or oil fired
  • Draft Hoods on gas fired heating equipment, function and safety
  • Draft Regulators & barometric dampers on oil fired heating equipment
  • Expansion Tanks Guide to pressure control and expansion tanks on hydronic hot water heating systems gas or oil fired
  • Fan Limit Switch on hot air furnace heating systems gas or oil fired
  • Flue Gas Spill Switch on gas fired heating equipment sense combustion and protect from blocked flues
  • Gas Piping, Valves, Controls including gas regulator assembly and other controls
  • MIXING / ANTI-SCALD VALVES: Guide to mixing valves on hot water heating systems and radiant heat systems
  • Noises: see Diagnose Oil Heat Noises
  • Power Switches to turn on or off heaters for furnaces & boilers, oil & gas fired, heat pumps or electric furnaces or boilers
  • RELIEF VALVES - TP VALVES: A guide to temperature and pressure relief valves & safety controls on hot water and steam heating systems
  • Stack Relay Switches Explained on oil fired furnaces or boilers as flame sensors & safety devices
  • Steam Vents provides details about air vents or steam vents on steam heating systems and diagnoses hissing sounds and failure of a steam radiator to get hot.
  • Thermostats & Heat Controls for furnaces & boilers, oil & gas fired, heat pumps or electric furnaces or boilers
  • Water Feed Valves: A guide to water-feeding/pressure-reducing valves on hot water and steam heating systems
  • Zone Valves: A guide to zone valves for heating zone control on hot water heating systems

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • DUST CONTAMINATION FROM HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com