InspectAPedia®

Brick pattern vinyl sheet flooring from 1973 containing asbestos in flooring & mastic (C) Inspectapedia RDBrick Pattern Floor Tiles & Sheet Flooring
that May Contain Asbestos

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Asbestos-containing floor tile and also sheet flooring or resilient flooring product identification for white brick sheet flooring, red brick sheet flooring and similar patterns such as Bradford Brick, Romford Brick, Glenmore Brick.

This article describes floor tiles and also sheet flooring,  both asbestos-free sheet flooring and sheet flooring products known to contain significant levels of asbestos produced in a white red or golden brick pattern between the 1960's to the late 1980's.

We also include photographs for identification of known asbestos-containing resilient sheet flooring as well as unknown flooring submitted for identification. The article gives safety and asbestos testing advice for sheet flooring products.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Armstrong Bradford Brick / Congoleum Red Brick or White Brick Pattern Vinyl Sheet Flooring Asbestos Content Test Results

Red brick pattern sheet flooring (C) InspectAPedia.comThis article gives advice for people worried about whether or not sheet flooring in their home contains or contained harmful asbestos. We include photos and descriptions of the most-popular brick pattern sheet flooring products to help in identifying this material.

Bottom line: asbestos confirmed in some but not all older sheet flooring of various brick-patterns & brick-colored varied-size rectangle patterns

Several readers report asbestos test lab results confirmed asbestos in several popular brick-pattern sheet flooring installed in North America as well as some other areas before the mid 1980's.

Watch out: red brick sheet flooring including varied-square-sized flooring like the Armstrong pattern shown here (probably Armsrtrong #5352 "Linoleum") has been found to contain asbestos.

Adding confusion, some reader's tests of identical-looking flooring (reported later in this article) found no asbestos in their sample.

Bottom line: treat the sheet flooring shown here as PACM - Presumed Asbestos Containing Material - or have a sample of your specific floor tested for asbestos.

That does not mean that occupants of a building where such flooring was installed is in grave danger from airborne asbestos from the flooring.

Where the floor is not glued down, asbestos or not, it can be removed easily with no significant asbestos hazard. Where it's glued down, sheet flooring removal needs to consider minimizing dust and cleaning up properly afterwards. Note too that some floor mastic adhesives also contained asbestos.

When the asbestos-suspect flooring has already been removed but where you are worried about asbestos dust, you can test settled dust or you can simply do more cleaning: damp wiping and HEPA vacuuming.

Below: a reader-supplied Asbestos Test Report for a 1970 home. Their Armstrong red brick sheet flooring varied-square-sized flooring shown below along with the report was confirmed as containing Chrysotile form asbestos.

Armstrong sheet flooring containing Chrysotile asbestos, red squares 1970 (C) Inspectapedia.com DR Sheet flooring asbestos test report (C) InspectApedia.com DR

[Click to enlarge any image]

If there is a reason concern for high levels of indoor dust that might be significantly contaminated, for example after an interior demolition job that did not control the spread of dust that might be high in asbestos,

this DUST SAMPLING PROCEDURE

provides a general guide to collecting settled dust to send to a qualified laboratory for analysis.

You'll want to know if significant levels of asbestos or other potentially harmful particles are found in the sample.

This approach, while not giving a quantitative "number" in in fact a more-reliable way to assess a remaining asbestos-dust hazard than an "air test" whose variability error can be several orders of magnitude.

Reader Question: does this red brick linoleum sheet flooring contain asbestos?

Vinyl asbestos sheet flooring (C) InspectAPedia JPWe recently purchased a house that was built in 1900 and decided to rip the carpet up because underneath was hardwoods which is what is in the rest of the house.

After we ripped it up we noticed what looks like old linoleum backing and glue which we have tried to scrape up and did not think about the risk of asbestos.

Around the very edges of the room there was still 2 inch strips of the old linoleum and I have tried to find the style in the reference pictures you have and I haven't seen any like it so I have attached a picture that is almost identical to what we have to see if you know if contains asbestos or not.

The damage is already done as I have scraped all the glue and old backing up but I am very concerned as it is my daughters bedroom.

I would appreciate any help you could possibly give me as I cannot afford to send off a sample for testing. - J.P. 8/18/2013

Here is a picture of the flooring I have in questions about weather it has asbestos in it or not. I couldn't find a picture of it on your site but I did find a lot of other helpful information.

Our house is from the 40s but i have no idea about the vinyl flooring it has been covered by carpet and other vinyl flooring its becoming the mystery house full of surprise. - J.W. 9/18/2013

Reply:

J.P.

I think that the sheet flooring in your photos is probably Congoleum's "Red Brick" vinyl sheet flooring pattern. Some web articles we reviewed called this material "linoleum" and although I think that word is often used too loosely to simply mean "sheet flooring" the product names are confusing. For example some Armstrong sheet vinyl floor coverings were labeled as "linoleum".

Here is how you can be sure to identify a true linoleum floor product (not asbestos-containing) by simple visual inspection - that is, how to tell linoleum from sheet vinyl resilient flooring:

If the flooring has what looks like burlap - a jute backing - on its reverse it's probably very old and not an asbestos-containing product.

If it has a smooth, non-fabric backing it may contain asbestos and should be treated as PACM - presumed asbestos containing material. From your photo (above left) this looks like a very-widely used sheet flooring with an impregnated asphalt felt backer - let me know.

Some such felt backers included asbestos. As we report below, a reader obtained an asbestos test lab report on a sample of flooring that looks like that above: the lab did not report finding asbestos in that sample.

Don't panic, just don't create a dusty mess by using power tools, saws, grinders;

Watch out that the mastic used to adhere old sheet flooring may also contain asbestos. After trying various solvents on a black mastic years ago I discovered that it was water soluble and came up easily once I let it sit wet for a few hours. Try that.

J.W. Indeed I've found other similar flooring patterns to those in your photo that by date, records, tests, were confirmed as having asbestos in the vinyl backing; it would be prudent to treat the material as presumed-asbestos-containing material. Don't panic; non-friable materials like this can usually be handled with a minimum of dust and debris - provided the floor was not glued down;

If you are facing a large cost or have other reasons to be concerned about asbestos contamination in the building it would not be costly to have a small sample of the floor tested. At the end of this article we include links to information on how to minimize the asbestos hazard from asbestos-suspect sheet flooring or tile flooring.

Reader follow-up from J.P.

It had almost a felt type black backing that is what was still stuck to the floor that I had to scrape and it did get soggy mushy in warm water.

Scraped up fairly easy and the glue I was able to mop up with several times of mopping over the entire floor. Just wanted to see if that is the burlap type backing you were possibly talking about.

Reply:

Watch out: No the backing you describe is not a jute backer; rather it sounds like an asphalt impregnated felt type backer - some of which contained asbestos; wetting and mopping make some sense in that case.

Reader Question & Test Results: 1973 Brick Pattern Vinyl Sheet Flooring & Mastic Adhesive Asbestos Test Results

We are concerned about asbestos in our kitchen sheet flooring. We are 99% sure it is the original floor--as there is nothing underneath it. The Home was built 1973, and we are pretty sure it was Forest City Enterprises who built it (if that helps?).

I attached some pictures.

Brick pattern vinyl sheet flooring from 1973 containing asbestos in flooring & mastic (C) Inspectapedia RD Brick pattern vinyl sheet flooring from 1973 containing asbestos in flooring & mastic (C) Inspectapedia RD

I carefully wet-scraped up a small piece. It was fairly stubborn if you scraped the bottom part or did not go 'under' the tile fully --almost like sand, but if you scraped below the sheet, it came up easier. I believe it is an embossed sheet vinyl (has recessed grout lines) the bright orange paint on the edges is what I used to seal any potential dust.

Any thoughts? If there's question and it's possible asbestos, can you suggest a good lab (that reasonable cost) to send a sample to? Thank you for all you guys have done! - R.D. 2/9/2014

Brick pattern vinyl sheet flooring from 1973 containing asbestos in flooring & mastic (C) Inspectapedia RD Brick pattern vinyl sheet flooring from 1973 containing asbestos in flooring & mastic (C) Inspectapedia RD

Reply:

Vinyl asbestos floor tile identification photo U.S. Library of CongressGiven the date of the floor installation (1973) and pattern you should have treated the flooring as presumed to contain asbestos. It would not perhaps be necessary nor appropriate to test something that is easily rolled up and disposed-of, but you'd have wanted to avoid creating a dusty mess.

Sheet flooring in the brick pattern was popular in both red (yours) and white, and may have had its original pattern design in 12" tile format in the Romford Red pattern (little image at left) as we document

at 1973 - ARMSTRONG EXCELON VINYL ASBESTOS FLOOR TILES where we include additional flooring image links:

Craftlon Romford Brick 9" x 9" x 3/32" vinyl asbestos floor tiles were available in White 57020 and in Red 57021 - shown at above left. Gold patterns appeared later.

If you want to test a sample

see ASBESTOS TESTING LAB LIST for help in finding a certified asbestos test lab.

Typically the asbestos test lab fee is around $50. U.S.

Asbestos is found in older floor tile mastic adhesives, particularly the older black asphalt mastics often contained asbestos, as did other similar mastics used in roofing and flashing cements.

See MASTIC, CUTBACK ADHESIVE, FLASHING CEMENT ASBESTOS

Asbestos is found in some (not all) sheet flooring backing materials as well.

It is possible that this popular vinyl asbestos pattern originated in the early 70's as Armstrong's "Romford Red" which is itself an interesting name as I suspect the name leaked over from Rumford - the colonial Tory who fled the colonies back to Britain during the American Revolution.

Rumford was sent to Bavaria where he developed the measurements on the perfect fireplace design - a specification that many red brick fireplaces as of course other fireplaces later followed. A less likely origin of the name is from Romford in Northeast London.

White Brick Pattern Sheet Flooring Containing Asbestos

White brick pattern sheet flooring, probably Romford Brick from Armstrong (C) InspectApedia.com AD

Shown here, a torn-up white Romford Brick-like floor pattern in sheet flooring form.

Brick pattern tile and sheet flooring that look like this were produced at least by Armstrong (under several pattern names I give below) and by Kentile Ken-Flex Flooring.

[Click to enlarge any image]

If your building contains this white brick (or red or green brick) pattern in a floor that was installed before the mid 1980's it would be prudent to treat the floor as PACM or "Presumed Asbestos Containing Material" - not something to panic about, but take care not to make an unnecessary dusty mess.

See ASBESTOS FLOORING HAZARD REDUCTION for detailed guidance.

This white brick pattern sheet flooring photograph was contributed by Anonymous by private email 2017/08/15 who wrote

Based on what I saw when I removed the flooring, which I believe was old asbestos backing, I'm hoping what I removed was a newer version. - Anon.

Below we report on another reader's asbestos test result for this floor pattern.

White brick pattern sheet flooring may contain asbestos (C) InspectApedia

Above, another white brick and half-brick sheet flooring product that may contain asbestos.

Below: an Armstrong White Romford-brick floor tile pattern sent to us from a reader whose home was built in 1968. From the age of the home and the appearance of this white brick pattern flooring it would be reasonable to assume that this floor tile contains asbestos.

White Armstrong Romford Brick floor tile pattern from a 1968 Home (C) InspectApedia.com Linda DR

Notice (from my next illustration) that this floor pattern was also sold as 12x12 floor tiles.

Here are more examples of widely-sold Armstrong vinyl-asbestos floor tiles in brick patterns. Brick pattern tile flooring was sold in both 9x9" and 12x12" versions.

Vinyl asbestos floor tile identification photo U.S. Library of Congress

Armstrong CRAFTLON ROMFORD BRICK (9" x 9" 0.80" gauge) pattern vinyl asbestos floor tiles shown above were sold in WHITE 57020, and RED 57021

Don't confuse this with Armstrong CUSTOM GLENMORE BRICK 12" x 12" x 1/16"

Romford Brick asbestos floor tiles (C) InspectApedia.com

or Armstrong ROMFORD BRICK floor tiles like this example from 1973 shown above

Below: Custom Old Forge, another brick floor tile pattern in 12x12" format followed by yet another 12x12 brick pattern, Armstrong Country Brick.

Vinyl asbestos floor tile identification photo U.S. Library of Congress

Armstrong CUSTOM OLD FORGE 12" x 12" x 1/16" brick pattern floor tiles shown above in WHITE, 57081>

Vinyl asbestos floor tile identification photo U.S. Library of Congress

COUNTRY BRICK 12" x 12" regular brick pattern Armstrong vinyl asbestos floor tiles sold in these colors: TERRA COTTA 57400, WHITE 57401, BURNT TOAST, 57402, above and especially recommended for kitchens, ALMOND 57403)

Similarly, note this White Romford Brick sheet flooring pattern (below, Armstrong but not a Solarian product) was sold also as vinyl-asbestos floor tile.

Armstrong white brick floor tile herringbone pattern (C) InspectApedia

Armstrong CUSTOM GLENMORE BRICK 12" x 12" and CUSTOM OLD FORGE 12" x 12" x 1/16" thick floor tiles, are shown in our first photograph below.

Armstrong vinyl asbestos floor tile photo (C) Daniel Friedman

Also see ARMSTRONG BRADFORD BRICK SHEET

Follow-up: positive asbestos content of a white brick pattern vinyl sheet flooring and asbestos in the black mastic

I did have it tested locally at accredited lab. They found asbestos in the top red-grey-black brick vinyl layer AND in the black mastic. (BUT amazingly, NOT in the grey mastic or the paper-felt backing)

Brick floor tile pattern containing asbesto (C) InspectApedia.comFeel free to add that red brick sheet vinyl to the list of 'known' asbestos.

Thanks, R.

Reply:

Thanks R.D. You can see more brick pattern asbestos floor coverings that contained asbestos in a tile form that is very similar to the red brick sheet flooring in your photos. Both were very popular.

More white brick flooring pattern photographs

This brick-like floor pattern was sold

in both tile and sheet flooring forms

in several colors including red, white, gray, green

See ARMSTRONG FLOOR TILE IDENTIFICATION 1974-1979 for more images of brick pattern asbestos containing flooring like the white brick Armstrong flooring shown at above-left.

More brick pattern flooring ID photos from this era are at

Reader comment: this light Olive-Green Brick Pattern vinyl sheet flooring from 1969-1971 tested positive for asbestos

I wanted to add to your photo guide - this light olive-green & white brick pattern sheet flooring with a white backer tested positive for asbestos. It's original to the house, which was built between 1969 and 1971. - C.B. 2017/04/23

White brick pattern asbestos  vinyl sheet flooring 1969 1971 (C) InspectApedia.com CB

Reply:

Thanks C.B. - if you can send along a copy of the asbestos test lab report it would be good for us to have that on file, protecting your anonymity but also supporting any future questions about this report - Ed.

Reader Question: no asbestos content in later 1980's era Armstrong Red Brick Pattern Sheet Flooring

We did not find our particular style of Armstrong vinyl sheet flooring on your website and therefore are submitting our photos and information in hopes that you are familiar with the style and know whether or not it contains asbestos.

Red brick pattern flooring without asbestos (C) InspectApedia PC

From our research, we determined that the Armstrong vinyl flooring brick pattern first appeared in the 1970s but continues through today.

The style appears to be most closely related to the Bradford Brick vinyl tile pattern, but the coloring is more varied and it comes in sheet flooring with white paper backing.

Red brick pattern flooring without asbestos (C) InspectApedia PC Red brick pattern flooring without asbestos (C) InspectApedia PC

The first few pictures are our own (installed kitchen flooring, view of hardwoods and kitchen threshold to flooring, and backing on extra sheeting roll in basement - with no labels or information unfortunately) and the last photo we found online - it confirms that Armstrong was the manufacturer (logo on demo photo).

Red brick pattern flooring without asbestos (C) InspectApedia PC Red brick pattern flooring without asbestos (C) InspectApedia PC

Our home was built in the 1950s, but the floor was clearly installed at a later date as it is not continuous under the original cabinets and the original hardwood floors can be seen continuing from our living room under the vinyl sheet which is glued to plywood on the hardwood floor (note the height difference and threshold in the kitchen flooring photo).

Any help would be greatly appreciated! We would really love to pull this floor up ourselves and refinish the hardwood underneath!

Thanks so much for your time and consideration! - P.C., Decatur, GA, 2 Aug 2015 [private email]

Reply:

Indeed because this has been such a very long and popular floor pattern in both tile and sheet flooring forms it's difficult to guess reliably about its asbestos content unless we have reason to think that the floor was installed before the mid 1980's.

Some readers have had later flooring tested for asbestos and have confirmed that later, that is newer flooring did not contain asbestos.

If you think the floor is that old or older it's reasonable to treat it as presumed to contain asbestos.

ADVICE: For buildings with floor tiles or sheet flooring that can be assumed to have been installed in North America before 1986 it would be prudent to treat the flooring as "PACM" or "Presumed Asbestos Containing Material".

That does not mean we should panic nor undertake an expensive and dangerous asbestos removal project.

Asbestos is safe and legal to remain in homes or public buildings as long as the asbestos materials are in good condition and the asbestos can not be released into the air.

Generally the safest approach is to leave such flooring alone and to cover it over with a coating or with another layer of flooring.

IF you are faced with a requirement for demolition and if you are uncertain about the flooring's asbestos content and cannot identify it through our guides, then you have a sample tested. At the end of this article we give a link to help with finding an asbestos test lab.

Reader follow-up: the Armstrong brick pattern sheet flooring above did not contain asbestos

I previously spoke with the woman who owned our home from 1987 - 2001 and she claims to have installed the vinyl sheet flooring (along with our green formica countertops - the good 'ol days :), however, I do not know when the product was manufactured.

Are there Armstrong flooring product catalogs available for the 1980s and 1990s? I'm wondering if it would be possible to find out when this color option and style was first introduced - if it was post-1986, we should be in the clear? I have contacted Armstrong but have not heard back. Thanks again for your help - we'll let you know the results of the test! - P.C. 2 Aug 2015

... we had our floor tested by an accredited lab and confirmed that it did NOT contain asbestos and the glue was modern and safe. However!

1960's-1970's (estimated) Red Brick Pattern Sheet Flooring: test shows no asbestos content

When we removed the layer of vinyl over plywood, and pulled back a section of the plywood, we discovered yet another layer of hidden vinyl sheet flooring glued to our original hardwoods (pictures attached) this appears to be an older model and the company is currently unknown to us.

We will have it tested this week and I'll let you know the results. Your website has been helpful to us and we're happy to contribute our various (!!) test results and photos anonymously, as you see fit. ... - P.C. 15 Aug 2015

Red brick pattern flooring without asbestos (C) InspectApedia PC

Reply:

This flooring pattern is discussed in the article above beginning

at RESILIENT SHEET FLOORING ID GUIDE in a section beginning

at RED BRICK PATTERN SHEET FLOORING

where there is this photo https://InspectAPedia.com/interiors/Red_Brick_Linoleum_023_JPs.jpg

The owner of that floor did not have a sample tested so your test results will be important.

More examples are

at at ARMSTRONG BRADFORD BRICK SHEET

Other readers' tests of your second flooring example (below) are given higher on this same web page and have confirmed the presence of chrysotile asbestos.

Red brick pattern flooring without asbestos (C) InspectApedia PC

Reader follow-up

Good news! There was not any asbestos in the vinyl sheet flooring, black felt backing, or mastic.

Asbestos test result on brick pattern sheet flooring (C) InspectAPedia PC

[Click to enlarge any image]

...


Continue reading at RESILIENT SHEET FLOORING ID GUIDE or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see ASBESTOS TESTING LAB LIST if you are faced with a costly, messy demolition of asbestos-suspect sheet or tile flooring

Or see SHEET FLOORING INSPECT / TEST

This article DUST / MOLD TEST KIT INSTRUCTIONS gives details on how to collect a dust sample using clear adhesive tape: low cost and easy.


This article ASBESTOS FLOOR TILE LAB PROCEDURES - gives bit of background on how a lab might test actual flooring samples.

Or see these

Asbestos Floor Hazard Reduction Articles

Suggested citation for this web page

SHEET & TILE FLOORING BRICK PATTERN ID at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice or see this topic index:

INDEX to RELATED ARTICLES: ARTICLE INDEX to ASBESTOS HAZARDS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman