FPE Sub Panels: Risk Assessment of Federal Pacific Electric FPE Stab Lok Sub Panels vs Main Panels
- How much risk reduction is achieved by replacing the main FPE panel and leaving FPE sub panels in place?
- What are the types of hazard that remain where FPE Sub panels are installed
- Insurance company policy may exclude coverage where FPE Stab-Lok® equipment is installed
- Photographs of FPE circuit breakers, labels, and bus designs provide means to identify this equipment
- Questions & Answers about FPE Stab-Lok® sub panels and main disconnects
- References
|
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
This article discusses and compares the hazards of Federal Pacific Stab-Lok® Electric Main Electrical Panels compared with Sub-Panels in buildings, and addresses the question of amount of risk reduced if only the main disconnect or main FPE panel is replaced. This information assists building inspectors, home buyers, home owners, electricians exploring hazards associated with Federal Pacific Electric Stab-Lok® circuit breakers and service panels.
Our page-top photo shows a main FPE Stab-Lok® electrical panel and service disconnect (at left) and three FPE Sub-panels.
Replacement FPE Stab-Lok® circuit breakers are unlikely to reduce the failure risk of this equipment. We recommend that residential FPE Stab-Lok® electrical panels be replaced entirely or the entire panel bus assembly be replaced, regardless of FPE model number or FPE year of manufacture. We do not sell circuit breakers nor any other products.
Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.
Comparing the Hazard of Federal Pacific Stab-Lok® (FPE) Electric Sub-Panels vs. Main Panels & Main Disconnects
Readers of this article should also see Federal Pacific Electric Panels: Fires Waiting to Happen and The Federal Pacific Electric FPE Panel/Breaker Hazard Summary - the main FPE Hazard Website. Also see our discussion of pre-1970 FPE Stab-Lok® circuit breakers at FPE Pre-1970 STAB-LOKS OK?.
Our photo (left) shows an FPE Stab-Lok® main electrical panel. Multiple main disconnects are in the top section of the panel.
Question: Do FPE Stab-Lok® Sub-Panels Present as Much Risk as the Main FPE Panel?
A commercial insurance broker in the Western U.S. placed insurance on a hotel built in 1964.
In 2000 the Main Electrical Panel, an FPE Stab-Lok® unit, was replaced with a unit made by Murray.
The hotel includes nine remaining “sub-panels” made by FPE
The insurance company that we placed the hotel with has a policy that they do not accept properties with FPE panels.
Our question is: Do the FPE sub-panels present as much risk as the main FPE panel?
It seems in a perfect world the hotel would change out all sub-panels, but at least they have upgraded the “main” panel. Do you think this is an acceptable compromise? - (Anon.)
Reply: Replacing the Main FPE Panel reduced risk but significant risks remain with the FPE Subs. Here are some of the risk factors:
A competent onsite inspection by an expert usually finds additional clues that help accurately assess the actual electrical hazards that would not be included whatsoever in a theoretical discussion. For example there could have been a history of failures to trip, overheating, or unusual circuit usage on specific circuits serving particular areas of the hotel, or there may be other significant electrical hazards (or other hazards) outside of the FPE topic that also merit urgent attention.
That said, here are some things to consider in assessing the degree of risk that has been achieved by replacing only the main FPE electrical panel:
- Replacing the main disconnect & panel did reduce risks: We agree that having installed another brand main panel has reduced the overall hazard for the building (if an FPE was in that role before), but
- The absolute risk for a given or individual FPE sub-panel or breaker or a circuit wired from such a breaker actually depends in part on the circuit's usage. An FPE breaker does not initiate a hazard or failure - it simply fails to protect the circuit from overheating (and fire) if an overcurrent or similar hazard occurs. This behavior is detailed in FPE Technical Report - Independent Research 2007
- Problem history: It is a dangerous error to presume that if no problem has occurred to date, the wiring and breakers are safe. A problem could have occurred previously that resulted in a much greater chance that at a subsequent overcurrent the breaker won't trip (that phenomenon was demonstrated in independent testing);
- Changes in circuit use are not predictable: even if a problem never occurred on a circuit, simply a change in use (someone plugs in an electric heater) can and probably will change the risk level.
- Risk for similar circuits in similar use: Our opinion is that for two circuits of similar level of usage, the hazard is similar, regardless of whether or not the circuit is wired out of a main or a sub panel.
Here too, hidden circuit differences, such as a poor connection, would change that picture.
- Two Pole breakers: It would be fair to argue that because the FPE no-trip problem is more severe on 2-pole breakers, and as a main panel would have at least one 2-pole breaker (the mains) while a sub panel that contains less than 6 switches may not have a main switch and so may not have a 2 pole switch, then the absolute risk might be lower, but that is in my opinion a "constructed" and is too theoretical an argument to be safe - if for no other reason than it does not consider circuit usage.
- Risk of incomplete electrical repairs: As a general opinion on electrical safety, we are very nervous about "partial" repairs of electrical hazards because of the risk that building occupants or management, thinking that an unsafe condition has been addressed, may ignore warning signs of an impending disaster.
In sum, the experience of insurers with FPE failures and perhaps their review of the research has indeed led some companies to ask that FPE panels be replaced.
- Can't afford or need to stage-in FPE panel replacements? As a sub panel replacement is likely to be under $1000. that cost compared with a fire is surely small and reasonable. Some suggestions for people who cannot afford to immediately replace an FPE Stab-Lok® electrical panel are found at CAN'T AFFORD A NEW ELECTRIC PANEL?
|
...
Frequently Asked Questions (FAQs)
...
Ask a Question or Search InspectApedia
Questions & answers or comments about FPE Stab-Lok® sub panels and main disconnects.
Ask a Question or Enter Search Terms in the InspectApedia search box just below.
Technical Reviewers & References
Related Topics, found near the top of this page suggest articles closely related to this one.
- Thanks to reader C.J., a professional insurance broker, for discussing risk and loss reduction associated with FPE Stab-Lok® electrical panels, January 2011
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.
|
- Aluminum Wiring Information Website Aluminum Electrical Wiring Hazards and Repairs: in-depth authoritative info, photos, documents including selection of proper vs. ineffective repair methods. E.g.: Ideal 65 "Twister" purple connector fails in field and lab testing with aluminum wire.
- Ampacity of an Electrical Service: How to determine the electrical service size or ampacity entering a building
- Circuit Breaker, a bad one fails to trip failure at aluminum bus-to-circuit breaker connection - field report and photographs
- Electrical System & Wiring Hazard Inspection, Detection, Cause, Remedy, Prevention - Main Electrical Page
- Electrical Panels, How to Inspect in buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects, defective products. Inspection Class Presentation
|