Measuring relative moistore in fiber cement siding at time of delivery (C) Daniel Friedman Eric GalowFiber Cement Siding Moisture Levels / Wetness
How, when, & why to measure fiber cement siding moisture level. How wet is "too wet to install"?

  • SIDING, FIBER CEMENT MOISTURE LEVELS - CONTENTS: how to measure moisture in fiber cement siding; what problems are caused by high moisture content in fiber cement siding? Field reports of wet or high-moisture-content fiber cement siding as delivered in factory packaging may mean shrinkage and other cosmetic issues.
  • POST a QUESTION or READ FAQs about the cause & cure of butt joint gaps in fiber-cement siding & about fiber cement siding installation
  • REFERENCES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Fiber cement siding moisture problems: fiber cement manufacturers advise that the product should not be installed if it is wet. Doing so can lead to unsightly butt joint gaps in siding courses as the product dries on the building. But how to figure out what wet actually means can be tricky.

We include diagnostic inspection photos and in related articles cited here we explain how to recognize, diagnose, and cure this problem.

We organize & include fiber cement siding gap repair advice from the manufacturer as well as from builders and building inspectors. We provide a table of all fiber cement siding installation clearance or gap specifications, caulking requirements & storage or moisture requirements.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Examining the Visible & Measured Moisture of Hardieplank Fiber Cement Siding on the Job

Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow

Lots of building products may be at a too-high moisture content without being visibly wet to the eye or even to touch by hand. And important if we're going to avoid moisture problems with any siding material is figuring out where the problem water or moisture is coming from.

Common sources of wet fiber cement siding products are said to be improper handling or storage before or at the job site. But as the study reported here shows, on occasion you may be getting wet fiber cement siding right from the supplier or even right from the siding factory.

Following the removal of "counterfeit siding" that had shrunk, leaving ugly butt joint gaps and disappointing the building owners of a property in Dutchess County, New York, the contractor, Galow Homes, ordered new Hardieplank™ siding from a local building supplier.

At Eric's suggestion, we inspected the Hardieplank™ siding when it was delivered and we monitored its performance during and after installation in 2013. There were some surprises!

Two pallets of fiber cement siding were delivered to the job: an incomplete bundle that had been re-wrapped in clear polyethylene plastic, presumably by the local supplier, and a complete bundle that was still in its original, un-damaged, un-torn, factory-sealed plastic wrapper. On opening the fiber cement after delivery we could plainly see, even without moisture measurement, that the products were wet!

At delivery, the siding was stored outdoors, off the ground, and for "insurance" against bad weather, the contractor wrapped additional plastic tarps around the material at the time of delivery (below left).

Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow

The second bundle that had been in its original factory wrapper is shown at left just after we began to open this package for examination of the siding itself.

Definition of "too wet" fiber cement siding

The manufacturer told us that the material must be kept dry and "not installed" if the contractor thinks it's "wet".

But despite repeated begging, we could not get the slightest definition of "wet" or "too much moisture" or "dry" fiber cement siding from the service rep with whom we spoke.

The same factory rep, in the company's warranty claims department, told us that the fiber cement siding moisture cannot be measured, a statement which is nonsense, see Hardieplank Technical Bulletin No. 8 found below in this article. Using a proper instrument and with proper precautions it is indeed possible to make relative moisture measurements in fiber cement products even without a clear industry standard. With a bit of work one could also make calibrated moisture measurements of product moisture.

At MOISTURE METER STUDY we provide details about using moisture meters, moisture meter scales, calibration, and accuracy.

Measuring Relative Moisture Content in Samples of Fiber Cement Lap Siding

Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow

Measuring moisture using a pin-type moisture meter is inaccurate for cementious products into which the pins don't penetrate, but a Tramex Moisture Encounter® or similar electronic moisture meter can give comparative moisture levels in cementious materials even without calibration to obtain an actual moisture percentage. [23]

Certainly relying on visible water alone would not be enough to define a siding product as "too wet to install" as products may look dry but have very high moisture content.

But in this case we found visible water in droplet form and sheer "wet" areas soaking the interior surfaces of both the distributor-wrapped and the factory wrapped plastic wrappers on this fiber cement siding on the day it was delivered to the job site.

Above you can see my hand wiping away water found on the inside of the plastic wrapper.

Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow

In response to a series of inquiry calls, the factory rep [S.] advised that in such cases the contractor should refuse the delivery and stop the job - advice that unfortunately fails to consider the drastic cost to owner, supplier, and in particular the contractor when a long-scheduled job has to be scrapped to wait for new materials without any assurance that the replacement will be any better!

What we would have preferred is some guidance on how to assess the moisture in fiber cement siding products, and perhaps a discussion with the various manufacturers (it's likely every one faces these concerns) about product drying, wrapping, shipping, and storage before and during installation.

I thought the factory rep would want to know that the product had arrived visibly wet and that refusing the material and cancellling the job was a very costly proposition, moreso if the existing siding has already been stripped from a building to prepare it for installation of the new material.

Her advice, delivered in an impressively nasty tone, was for the owner, or perhaps the contractor to "Put in a claim". In other words, "Buzz off, buster!" While we found slightly better data and encounterd no such rudeness when inquiring about a different product, (DRYWALL MOLD RESISTANT) there too we found a similar lack of clarity about "excessive moisture" exposure.

Causes of Wet Fiber Cement Siding - at Delivery

Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow

Where did this water come from? It would appear to be coming from the fiber cement siding itself, as we found these conditions in the factory-wrapped product as well as the distributor-wrapped siding.

Our electronic moisture meter, set on the "cement" scale, was quite capable of making relative moisture comparisons among various examples of fiber cement siding.

In the photo at left you can see that we are reading in the "wet" end of the scale. As a comparison point, on the same scale the garage floor, building sheathing, and other samples measured in the green or "dry" end of the instrument's range.

We measured the fiber cement siding relative moisture content at the board ends and center, and then began lifting boards out of the bundle to measure siding boards in the center of the pallet.

Variations in Fiber Cement Siding Moisture Confirm the Point of Origin of the "Wet" Material

Significantly, the fiber cement siding boards near the top of the bundle measured as much lower in moisture content than those in the center of the bundle - a strong argument for the moisture source as the product itself. We suspect the product may have b een wrapped and shipped from the factory while still rather high in moisture.

Measurements of surface moisture can be made using a pin-type moisture meter (shown below) and those, too, confirmed that these fiber cement boards were more wet at the board center than at the bundle ends, and boards in the center of the whole bundle were more wet than those on the bundle top layer or two.

Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow Hardieplank fiber cement siding as delivered (C) Daniel Friedman Eric Galow

At above left you can see the pin type moisture meter reading in the center of its wetness scale (center of a board) and at above right, at the dry end of its scale near the board end. [Click to enlarge any image].

Watch out: we do not recommend using pin- type of moisture meters for making comparative moisture level measurements fiber cement products: stick with an electronic unit such as the Tramex Moisture Encounter. Other factors such as ambient and test material temperature, even type of paint coating can affect the reading of moisture meters, particularly pin-type meters.

Fiber cement board stored indoors, measuring "dry" using the Tramex Moisture Encounter (C) Daniel Friedman

However, for demonstrating relative moisture or for comparing siding moisture to a known dry example, even relative moisture meter readings can be perfectly adequate.

Moisture meter techniques & sources of error are discussed in detail at MOISTURE METER STUDY.

Without calibration to a known source, moisture meter readings taken on fiber cement siding products are relative, not absolute in percent moisture content for this material, though being cementious, probably the cement or masonry scale on the moisture meter is not far off.

Finally, for a fiber cement siding board comparison measurement, we took a look at the moisture content of a "dry" fiber cement siding board that was several years old, had been removed from the building, and had been stored indoors for several months.

You'll notice that the moisture meter in use above indicated very low moisture content in this similar product when it was in fact "dry".

What About Laying the Damp or Wet Siding Out to Dry

When the parties ruled out leaving the home naked to wait for new siding that might in fact show up just as wet as the present material, we discussed steps to try to dry out the siding to a lower moisture content before its installation.

We calculated that spreading out all of the siding indoors to dry was out of the question. The total square feet of all sides of a typical two story home far exceeds the available indoor conditioned space to lay out all of the material to dry.

We had observed that left in the sun on a bright dry day, placed on a clean dry plastic tarp outdoors, siding boards driedf to a relatively very low moisture content, possibly low enough for safe installation. Sadly , for practical reasons the contractor pointed out that spreading out all of the siding in the sun to "dry" was just a crazy idea.

The job would require thousands of square feet of dry tarped surface all in the sun;

The siding would have to be laid out when the sun was up but stacked again and put away at the end of the day - until the material was both dry and installed on the building. The time and labor for this step, even if there was adequate space and tarps, was more than the time to install the siding on the building. And the repeated handling risked product damage.

Other Steps to Minimize Butt Joint Shrinkage Gaps

In addition to installing only "dry" siding (whatever that actually is - in the absence of an actual factory specification of measurable moisture content or moisture content expressed in percentages that map to common electronic moisture meters), the contractor should make every effort to minimize the number of butt joint gaps - focusing instead on using the factory-specified clearances (and caulking) at abutting vertical trim on the building.

Watch out: when installing long runs of continuous siding may avoid shrinkage gaps but if enough end clearance is not provided at the board ends there may be thermal expansion and buckling problems. We discuss these below.

Will the contractor continue to recommend the selection & installation of this product type? We'll see.

Bottom line on Fiber Cement Siding Moisture & Shrinkage:

HardiePlank Thermal or Moisture Expansion Properties: shrinkage gaps vs. expansion buckling

In addition to moisture-related shrinkage and butt joint gap concerns discussed above and traced to the dry-out of too-wet siding at time of its installation, some installations of fiber cement lap siding as well just about every other building siding material may experience buckling or bulging due to thermal or moisture-related expansion, particularly on very long horizontal siding runs and particularly if the material is not installed according to the manufacturer's recommendations.

While these details are not in the product installation instructions (as of June 2013), the company has issued James Hardie Technical Bulletin No. 8 addressing this topic. Excerpting from the company's data, :

Fiber cement (complying with ASTM C1186), as do all building materials, expands and contracts with changes in relative humidity and temperature. James Hardie recommends designing for this type of movement on buildings with long runs of continuous siding. Coefficient of Thermal Expansion (COTE) per ASTM E228 is:

Note that this rather modest total moisture movement over the length of the siding product refers to cyclic movement due to normal moisture conditions in a properly stored, installed, coated, sealed, and flashed product.

At SIDING, FIBER CEMENT GAPS we discusse more significant moment that can appear as gaps at siding butt joints and caused most likely by improper storage or coating.

Reader Question: Gaps at Butt Joints in fiber cement lap siding

I had CertainTeed factory painted fibre cement siding installed on my new home last year. The installer, contrary to the CertainTeed installation instructions, left a 1/8" gap at all butt joints. He now maintains that CertainTeed and other contractors state that a 1\4" gap at butt joints is acceptable.

... I maintain that the requirement by CertainTeed to not leave a gap of any kind is to greatly minimize any shrinkage that might subsequently occur at the butt joints. - M.D 4/11/13

Reply: 3 causes of gaps at lab siding butt joints in fiber cement installations

You are partly correct. The product specifications call for no gap at fiber cement lap siding butt joints, but it's not the gaps that cause shrinkage but rather product shrinkage that causes these gaps or increases their width as the product dries on the building. My OPINION from what I've learned both by field investigation and by reading the various manufacturer's installation instructions & technical bulletins is that there are three distinct sources butt joint gaps in fiber cement siding installations:

  1. Improper siding installation (leaving gaps where they should not be)
  2. Siding shrinkage (probably excessive product moisture at the time of installation)
  3. Thermal movement of siding (not usually significant, but a possible source of buckling and gaps at the lapped edges in long continuous siding runs)

A complete discussion of the question above, including factory specifications for siding clearances and gaps, the causes & cures of butt joint gaps, and lap siding butt joint gap repairs are found at SIDING, FIBER CEMENT GAPS and its companion articles.

...


Continue reading at SIDING, FIBER CEMENT REMOVAL or select a topic from the More Reading links or topic ARTICLE INDEX shown below.


Suggested citation for this web page

SIDING, FIBER CEMENT MOISTURE LEVELS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

More Reading

Green link shows where you are in this article series.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ARTICLE INDEX to BUILDING SIDING

OR use the Search Box found below at Ask a Question or Search InspectApedia

...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman