InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ACCURACY vs PRECISION of MEASUREMENTS
AFCIs ARC FAULT CIRCUIT INTERRUPTERS
ALUMINUM SECs & WIRING
ALUMINUM WIRING HAZARDS & REPAIRS
AMPS & VOLTS DETERMINATION
AMPACITY - the LIMITING FACTOR
APPLIANCE EFFICIENCY RATINGS

BACKUP ELECTRICAL GENERATORS
BOOKSTORE - ELECTRICAL
BUILDING SAFETY HAZARDS GUIDE

Cadet & Encore Heater Recall
CIRCUIT BREAKER FAILURE
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
Classified CIRCUIT BREAKER WARNING
CONDUIT, ELECTRICAL
CORROSION in ELECTRICAL PANELS
CORROSION & MOISTURE SOURCES in PANELS
CUTLER HAMMER PANEL FIRE

DEFINITIONS of ELECTRICAL TERMS
DIRECTORY OF ELECTRICIANS
DMM Digital Multimeter, How to Use

ELECTRIC HEAT
ELECTRIC METERS & METER BASES
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRIC PANEL AMPACITY
ELECTRIC PANEL INSPECTION
ELECTRIC PANEL MOISTURE
Electric Power Frequency Table
ELECTRICAL BASICS
EMF RF FIELD & FREQUENCY DEFINITIONS
ELECTRICAL GENERATORS
ELECTRICAL GROUND SYSTEM INSPECTION
ELECTRICAL GENERATORS
ELECTRICAL GROUND SYSTEM INSPECTION
ENERGY SAVINGS in buildings

FEDERAL PACIFIC FPE HAZARDS
FIRE SAFETY Checklist, CPSC

GENERATORS, ELECTRICAL
GFCI PROTECTION,Testing GFCIs AFCIs

HEATING COST FUEL & BTU Cost Table
HEAT, ELECTRIC
HEAT TAPE USAGE GUIDE
Hertz - Definitions of KHz MHz GHz THz

KNOB & TUBE WIRING

LIGHTING, EXTERIOR GUIDE
LIGHTING, INTERIOR GUIDE
LIGHTNING PROTECTION SYSTEMS
LOW VOLTAGE BUILDING WIRING
LOW VOLTAGE TRANSFORMER TEST

MAIN DISCONNECT
MAIN DISCONNECT AMPACITY
MOISTURE SOURCES in PANELS
MULTI-WIRE CIRCUITS
MURRAY SIEMENS Recall

PHOTOVOLTAIC POWER SYSTEMS
PUSHMATIC - BULLDOG PANELS
RUST in ELECTRICAL PANELS
SAFETY: ELECTRICAL INSPECTION SAFETY
  Shock Risk Statistics
  Outside Electrical Inspection
  Electric Meter & Service Entry
  Local Electrical Grounding
  Electrical Panel Interior Inspection
  Removing Electric Panel Covers
  Electrical Panel Cover Screws
  Electrical Panel Interior Hazards
  Testing Main Breakers or Fuses
  Inspect Breakers, Fuses, Circuits
  Testing Receptacles GFCIs AFCIs
  When to Shut Down Equipment
  Touching Electrical Equipment
  Guide to Electrical Test Equipment
  Using DMMs & VOMs Safely
  VOLTAGE DETECTION & MEASUREMENT
  General Electrical Safety Suggestions
  Electrical Inspection Client Safety
SE CABLE SIZES vs AMPS
SQUARE-D RECALLS

UNDERGROUND SERVICE LATERALS

VOLTS / AMPS MEASUREMENT EQUIP

WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING

ZINSCO SYLVANIA ELECTRICAL PANELS

More Information

LARGER IMAGE Electrical Test Tools Choices & Tool Procedures for Electrical Inspectors & Home Inspectors
     

  • Using Electrical System Test Equipment to Check Electrical Equipment, Components or Electrical System Safety
  • First use your head: stop, look listen, before touching anything, use safety equipment
  • Using a Tic Tracer™ to Test for Presence of Electrical Voltage
  • Using Other Non-Contact Voltage Sensing or Voltage Detection Tools
  • Using a Neon Tester to Test for Live Voltage or for Ground Paths
  • Using an Electrical Receptacle Tester to Check for Voltage & Proper Wiring Connections
  • Introduction to Using a DMM or VOM to Check for Current
  • Safe Use of Electrical Test Equipment: DMMs & VOMs - the basics
  • Questions & answers aboutusing multimeters, digital multimeters, and volt-ohm meterrs safely during building electrical systems inspection, testing, diagnosis, or repair
  • References

Click to Show or Hide Related Topics

  • ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR - home
  • AFCIs ARC FAULT CIRCUIT INTERRUPTERS
  • ALUMINUM WIRING HAZARDS & REPAIRS
  • AMPS MEASUREMENT METHODS
  • AMPS VOLTS DETERMINATION
  • BACKUP ELECTRICAL GENERATORS
  • CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
  • CONDUIT, ELECTRICAL
  • CORROSION in ELECTRICAL PANELS
  • DEFINITIONS of ELECTRICAL TERMS
  • DIRECTORY OF ELECTRICIANS
  • DMM Digital Multimeter, HOW TO USE
  • DMM & VOM SAFETY
  • ELECTRIC HEAT
  • ELECTRIC METERS & METER BASES
  • ELECTRIC MOTOR DIAGNOSTIC GUIDE
  • ELECTRIC MOTOR OVERLOAD RESET
  • ELECTRIC PANEL AMPACITY
  • ELECTRIC PANEL INSPECTION
  • ELECTRICAL BASICS
  • Electrical Code Basics
  • ELECTRICAL OUTLET, HOW TO ADD & WIRE
  • ELECTRICAL SPLICES, how to make
  • ELECTRICAL TOOLS BASIC
  • ELECTRICAL WIRING COLOR CODES
  • ELECTRICAL WIRING BOOKS
  • ELECTRICAL DISTRIBUTION PANELS
  • EMF RF FIELD & FREQUENCY DEFINITIONS
  • FEDERAL PACIFIC FPE HAZARDS
  • GFCI PROTECTION,Testing GFCIs AFCIs
  • GROUND SYSTEM INSPECTION
  • GROUND SYSTEM REQUIREMENTS
  • KNOB & TUBE WIRING
  • LIGHTING, EXTERIOR GUIDE
  • LIGHTING, INTERIOR GUIDE
  • LIGHTNING PROTECTION SYSTEMS
  • LOW VOLTAGE BUILDING WIRING
  • LOW VOLTAGE TRANSFORMER TEST
  • MAIN DISCONNECT
  • MULTI-WIRE CIRCUITS
  • MURRAY SIEMENS Recall
  • OLD HOUSE ELECTRICAL WIRING
  • PHOTOVOLTAIC POWER SYSTEMS
  • PUSHMATIC - BULLDOG PANELS
  • SAFETY for ELECTRICAL INSPECTORS
  • SERVICE AMPACITY
  • SERVICE DROP
  • SERVICE ENTRY WIRING
  • SE CABLE SIZES vs AMPS
  • SIEMENS MURRAY Recall
  • SQUARE-D RECALLS
  • TEST EQUIPMENT, ELECTRICAL
  • THERMISTORS
  • VOLTAGE DETECTION & MEASUREMENT
  • UNDERGROUND SERVICE LATERALS
  • VOLTS / AMPS MEASUREMENT EQUIP
  • WIND ENERGY SYSTEMS
  • WIND TURBINES & LIGHTNING
  • ZINSCO SYLVANIA ELECTRICAL PANELS
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Guide to electrical test tools for electricians, service technicians, building inspectors: this article discusses several inexpensive and useful test tools for the electrical inspector, home inspector, or other professionals who examine residential electrical systems. Also see DMM Digital Multimeter, How to Use. Safe electrical inspection procedures and safe use of volt meters, DMMs, multimeters, and similar electrical test equipment are discussed separately in more detail at SAFETY: ELECTRICAL INSPECTION SAFETY and at Using DMMs & VOMs Safely.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Guide to Using Electrical System Test Equipment to Check Electrical Equipment, Components or Electrical System Safety

Fatal Shock Hazard Warning: Inspecting electrical components and systems risks death by electrocution as well as serious burns or other injuries to the inspector or to others. Do not attempt these tasks unless you are properly trained and equipped.

Proceedings of the ASHI Home Inspector Educational Seminar: ASHI-NE Chapter Annual conference, September 22-23, 2008, Randolph, MA. -- Daniel Friedman.

Original text - Daniel Friedman, as ASHI Technical Journal Staff, January 1992,updates February 2006, September 2008. This is the full text version. A powerpoint presentation version of this class is also available. Readers of this article should also see these other building inspection safety articles:  Safety for Building Inspectors and  Septic Inspection Safety and also STAIRS, RAILINGS, LANDINGS, RAMPS - INSPECTIONS, CODES

These electrical inspection suggestions are not a complete inventory of all electrical components that should be inspected; nor have we described all of the electrical test tools popular among home inspectors and electrical inspectors. For example the SureTest® Circuit Analyzer model 61-164 and 61-165 made by the Ideal Corporation is quite popular among many home inspectors. (We'd welcome a contribution on the proper use of this tool.) Sometimes circuit analyzers are misused in testing aluminum wiring, FPE Stab-Lok equipment and AFCIs. Contact Us by email to suggest changes, corrections, and additions to this material.

First use your head: stop, look listen, before touching anything, use safety equipment

Stop, look, listen before touching. More on "just looking" is provided when we discuss opening the electrical panel. Do not rely on touch to determine if electrical equipment is safe.

Details about the hazards of touching electrical equipment and alternative advice for determining whether or not equipment is safe to inspect are provided at Touching Electrical Equipment.

Guide to Using a Tic Tracer™ to Test for Presence of Electrical Voltage

Tic tracer voltage tester (C) Daniel Friedman

This is a superb safety tool for testing for the presence of live 120VAC or 240VAC because you do not actually need to touch the tool to anything - just hold the tool near a source of electrical power and the electrical field produced will cause the tool to generate its tone. Faster "ticking" indicates higher voltage; slow ticking can indicate a wire connected to a live circuit even if the wire is not presently conducting current.

With practice the inspector can guess the voltage level from the tone quality.

We use this tool to check light sockets for power when there is no bulb or the bulb is dark. We also use this tool to look for lost or hidden wiring in walls and ceilings.

Its sensitivity falls off with the square of the distance from the source of electrical power.

Weird and interesting behavior of the TIF Tic Tracer: Some ASHI NE chapter inspectors pointed out that this device can be "fooled" into thinking that a wire scrap is "live" or that even a pipe is electrically "live" when it is not.

If a live electrical wire passes close enough to another metal device such as a pipe, electrical conduit, or armored cable, the metal device, conduit, or cable may pick up the electrical field generated by the "live wire" and appear "live" itself when it is not. (This is a "safe" error in that it errs in the direction of warning that something is live when it is not.)

This tool will also respond to momentary static electricity. In winter, simply rubbing its tip quickly across a wall can produce a momentary sound response. (Which can be fun in certain circumstances.)

The Tic Tracer™ is discussed further along with examples of how this tool is used at TOUCHING EQUIPMENT. Inspectors who object to the "false positive" possibility make use of a light-pen or similar tool which performs similar functions with less sensitivity to false positives.

Guide to Using Non-Contact Voltage Sensing or Voltage Detection Tools

Electrical voltage detector pen (C) Daniel Friedman
Alternative AC and DC non-contact voltage sensing tools
including pen-sized current sensors and even the simple neon-tester, below are available to perform this function.

The Tif™ Tic Tracer™ and other inexpensive pen-type voltage sensors (GB® non-contact voltage sensor, Greenlee Voltage Detector, Sperry® non-contact voltage sensor, Global Cache™, PasPort® and FCB Voltage Pen (Photo at left)), offer the advantage that it is not necessary to actually touch equipment, a surface, or a wire, to sense the presence of live voltage. Some voltage sensing models incude an adjustment to the sensitivity of the device.

SAFETY TIP: Greenlee and other manufacturers recommend that you test the operation of the voltage detector on a known live circuit both before and after using it to test for the presence of electrical voltage at a wire or device.

VOLTS / AMPS MEASUREMENT EQUIP describes other electrical test equipment including the Greenlee GT-16 adjustable voltage detector.

Guide to Using a Neon Tester to Test for Live Voltage or for Ground Paths

Neon TesterA simple neon tester is perhaps a simple, versatile tool for checking for the presence or absence of voltage. It requires touching electrical contacts or grounded surfaces to function.

Just touch one leg of the tester to the surface to be checked (a wire terminal or an electrical panel enclosure).

Touch the second leg of the neon tester to a sure-ground such as a water pipe that you see continues into soil.

If voltage is present within the range of sensitivity of the neon tester's bulb, the bulb will light.

We discuss neon testers for voltage at Electrical Tools Every Homeowner Should Have

Tips for Using an Electrical Receptacle Tester to Check for Voltage & Proper Wiring Connections

Receptacle and GFCI Test Procedure (C) Daniel Friedman

Receptacle testers are used by most home inspectors to check for proper wiring at electrical receptacles as well as to check the function of GFCI's.

For testing AFCI's the only reliable test currently available is the device's own test button.

We provide details about using receptacle testers at Electrical Tools Every Homeowner Should Have

Neither of these neat little electrical test tools can be relied on to report low levels of current leakage.

At an investigation of a garage roof that shocked a crew of builders during reconstruction after a lightning strike, we measured voltage varying between about 38 volts AC and 68 volts AC between some framing components and the earth. We could not detect these conditions with a neon tester. A VOM or DMM was needed.

Introduction to Using a DMM or VOM to Check for Current

VOM in use measuring live voltage (C) Daniel Friedman A simple volt ohm meter volt-ohmeter (VOM) such as the TriplettTM 310 or our little mini digital multimeter (DMM) shown at left can be used to test for unexpected and unsafe voltage at a component.

  1. Set the VOM in the highest AC-voltage range.
  2. One probe is used to contact the surface of the electric panel (or any component to be examined)
  3. The other probe is touched to a reliable ground source, or in the example shown, to the neutral side of the circuit.

NOTE: Once having tested at the highest voltage range, greater accuracy may be obtained by choosing more sensitive ranges which permit readings to be taken in the upper portion of the scale. Disconnect the test probes (or shut off the voltage source) before changing the voltage range setting on the VOM.

Details on safe use of DMM's and VOMs are at Using DMMs & VOMs Safely.

For example, if the meter indicates more than 1or 2 volts between a service panel cover and ground, there's a safety problem. Most low-cost analog-type meters such as the one described provide additional ranges used to read lower voltages with more sensitivity.

Some VOM models provide alligator clips for the ends of the test probes. These clips permit measuring high voltage without handling the probes. Always shut off the power before connecting the alligator clips.

Safe Use of Electrical Test Equipment: DMMs & VOMs

8.3 During an electrical system inspection the inspector is NOT required to
8.3.A. insert any tool, probe, or testing device inside the panels



In some circumstances ASHI inspectors may elect to make current and voltage measurements. For inspectors who elect to use these tools, make sure that the tools themselves do not become a source of damage, or injury.

Use only DMM's (digital multi meters) or VOMs (volt-ohm meters, the analog predecessors to DMMs) designed for high energy measurements.

Details about safe use of VOMs and DMMs are provided at Using DMMs & VOMs Safely.

Readers of this article should continue with a review of  Using DMMs & VOMs Safely .

General Electrical Safety Suggestions describes important basic safety procedures, clothing, and equipment for home inspectors and electrical inspectors.

Details about the hazards of touching electrical equipment and alternative advice for determining whether or not equipment is safe to inspect are provided at Touching Electrical Equipment.


Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Questions & answers or comments about using multimeters, digital multimeters, and volt-ohm meterrs safely during building electrical systems inspection, testing, diagnosis, or repair.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • Electrical shock injury statistics: www.healthatoz.com - September 2008;
  • Daniel Friedman - Publisher & Editor of InspectAPedia.com®
  • [2] N. Srinivasan, MSEE, is a senior member of IEEE with 30 years experience in the electrical industry. Mr. Srinivasan is in Vienna VA.
  • [3] Louis P. Babin generously contributed technical editing about the effects of doubling ampacity in an electrical circuit (September 2007)
  • [4] Digisnap DSA-500 snap-around digital multimeter, A.W. Sperry Instruments Inc., 2150 Joshua's Path, Suite 202, Hauppage NY 11788, Tel: 800-645-5398, Email: cat@awsperry.com, Website: www.awsperry.com
  • [5] Fluke Corporation, 6920 Seaway Blvd, Everett, WA 98203, USA, PO Box 9090 Everett, Washington 98206, Tel: +1(425) 347-6100, Technical support: 1(800) 44-FLUKE (1(800) 443-5853), Website: www.fluke.com,
    Fluke Europe B.V, PO Box 1186 Eindhoven, The Netherlands, Tel: +31 (0)40 2 675 200 +31 (0)40 2 675 222, Website: www.fluke.eu
    • Fluke India: TTL India Pvt. Ltd. (A Fluke Company), Deodhar Center, 424, Marol Maroshi Road, Andheri (E), Mumbai, 400076, Tel: 1 800 209 9110, Email: info.india@fluke.com, Website: http://www.fluke.com/fluke/inen/products/Digital-Multimeters.htm
    • Digital 287/289 Digital Multimeter, Users Manual, retrieved 9/5/21, original source: http://assets.fluke.com/manuals/287_289_umeng0200.pdf, [copy on file as Fluke_287_289_umeng0200.pdf]
  • [6] Simpson Electric, P.O. Box 99, 520 Simpson Avenue, Lac du Flambeau, WI 54538-0099 Tel: 715-588-3311, customer service: 715-588-3947, Email: support@simpsonelectric.com, Website: www.simpsonelectric.com/
    • Simpson 260® Series 6XLM Volt-Ohm-Milliammeter Instruction Manual, retrieved 9/5/2012, original source: http://www.simpsonelectric.com/uploads/File/datasheets/260-6xlm.pdf, [copy on file as Simpson_260-6xlm.pdf]
  • [7] tif 300cc Tic Tracer voltage detector, Tif Instruments Inc., 9101 NW 7th Avenue, Miami, Florida 33150
  • [8] Greenlee® GT-16 adjustable voltage detector, Greenlee Textron Inc., Website: greenlee.com, Tel: 800-435-0786 , Email: echsupport@greenlee.textron.com,
  • [9] Jensen VOMs, no longer available
  • [10] Mastech VOMs and DMMs (made in China), Shanghai Hihua V&A Instrument Company, 881 Ye Cheng Road Jia Ding District, Shanghai 201821, China, Email: mastech@vip.sina.com, Tel: +86 21 69523164 +86 21 69523225, Website: http://www.mastech.com.cn/
  • [11] Equus Multimeters by Innova, Equus Products, Inc., 17352 Von Karman Ave., Irvine, CA 92614, U.S.A., Tel: 714-241-6800, Website: http://www.equus.com/
  • [12] Actron DMMs & VOMs, Website: http://www.actron.com/
  • [13] ExTech DMMs & VOMs, ExTech Corp. a FLIR company, Extech Instruments Corporation, 9 Townsend West, Nashua, NH 03063, U.S.A., Email: support@extech.com, Tel: 877-239-8324 Option 3, Website: http://www.extech.com
  • Carson, Dunlop &
Associates Ltd., TorontoCarson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. The firm provides professional home inspection services & home inspection education & publications. Alan Carson is a past president of ASHI, the American Society of Home Inspectors. Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides:
    • Commercial Building Inspection Courses - protocol ASTM Standard E 2018-08 for Property Condition Assessments
    • Home Inspection Education Courses including home study & live classes at eleven colleges & universities.
    • Home Inspection Education Home Study Courses - ASHI@Home Training 10-course program.
      Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITP in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference Book, a reference & inspection report product for building owners & inspectors.
      Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference eBook, an electronic version for PCs, the iPad, iPhone, & Android smart phones.
      Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter inspectaehrb in the order payment page "Promo/Redemption" space.
    • The Illustrated Home illustrates construction details and building components, a reference for owners & inspectors.
      Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILL in the order payment page "Promo/Redemption" space.
    • The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones.
  • [15] Dr. Jess Aronstein, consulting engineer, Poughkeepsie NY, 1991 protune@aol.com
  • [16] Rex Cauldwell, master electrician and contributor to the Journal of Light Construction on electrical topics
  • [17] New York State Central Hudson Gas and Electric Company, G&E/1-2/85 consumer safety pamphlet
  • [18] Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com 11/06
  • [19] Roger Hankey is principal of Hankey and Brown home inspectors, Eden Prairie, MN. Mr. Hankey is a past chairman of the ASHI Standards Committee. Mr. Hankey has served in other ASHI professional and leadership roles. Contact Roger Hankey at: 952 829-0044 - rhankey@hankeyandbrown.com. Mr. Hankey is a frequent contributor to InspectAPedia.com.
  • [20] Arlene Puentes, an ASHI member and a licensed home inspector in Kingston, NY, and has served on ASHI national committees as well as HVASHI Chapter President. Ms. Puentes can be contacted at ap@octoberhome.com
  • [21] ASHI Technical Journal, Vol. 2. No. 1, January 1992, "Determining Service Ampacity," Dan Friedman and Alan Carson, and the
  • [22] ASHI Technical Journal, Vol. 3. No. 1, Spring, 1993, "Determining Service Ampacity - Another Consideration," Robert L. Klewitz, P.E., with subsequent updates and additions to the original text ongoing to 2/19/2006. Reprints of the originals and reprints of the Journal are available from ASHI, the American Society of Home Inspectors www.ashi.com.
  • [23] Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels
  • [24] "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • [25] "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • [26] "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • [27] "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • [28] "Home Wiring Inspection," Roswell W. Ard, Rodale's New Shelter, July/August, 1985 p. 35-40.
  • [29] "Evaluating Wiring in Older Minnesota Homes," Agricultural Extension Service, University of Minnesota, St. Paul, Minnesota 55108.
  • [30] Jim Simmons: Personal communication, J. Simmons to Daniel Friedman, 9/19/2008. Photographs contributed to this website by Jim P. Simmons, Licensed Electrician, 360-705-4225 Mr. Electric, Licensed Master Electrician, Olympia, Washington Contact Jim P. Simmons, Licensed Master Electrician, Mr. Electric, 1320 Dayton Street SE
    Olympia, WA 98501, Ph 360-705-4225, Fx 360-705-0130 mrelectricwa@gmail.com
  • [31] Kenneth Kruger: Original author of the sidebar on testing VOM DMM condition: Kenneth Kruger, R.A., P.E. AIA ASCE, is an ASHI Member and ASHI Director in Cambridge, MA. He provided basis for this article penned by DJ Friedman.
  • [32] Paul Galow - technical consultant on networking, LAN design, applications support. Galow Consulting Services, 914-204-1749, email: paulgalow@galowconsulting.com
  • "Electrical Systems," A Training Manual for Home Inspectors, Alfred L. Alk, American Society of Home Inspectors (ASHI), 1987, available from ASHI. [DF NOTE: I do NOT recommend this obsolete publication, though it was cited in the original Journal article as it contains unsafe inaccuracies]
  • "Basic Housing Inspection," US DHEW, S352.75 U48, p.144, out of print, but is available in most state libraries.
  • ...

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • ...

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com