InspectAPedia®

Proper routing and support of electrical wire (C) Carson Dunlop AssociatesElectrical Wire Routing & Protection
How to route & locate wires for an electrical plug outlet or wall plug

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

How & where to route electrical wires when hooking up an electrical receptacle or wall plug or electrical outlet.

This article series describes how to choose, locate, and wire an electrical receptacle in a home.

Electrical receptacles (also called electrical outlets or "plugs" or "sockets") are simple devices that are easy to install, but there are details to get right if you want to be safe.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Routing, Securing & Protecting Electrical Wires for a New Receptacle

Proper routing and support of electrical wire (C) Carson Dunlop Associates Proper routing of electric wires in metal studs (C) Carson Dunlop Associates

[Click to enlarge any image]

The electrical circuit wire must be properly routed and secured between the electrical panel and the receptacle location, and must be properly secured at the junction box that is to hold the electrical receptacle.

We secure wires at intervals specified by the electrical code so that it doesn't sag, hang, pull on itself, and become damaged or unsafe. The two sketches below, courtesy of Carson Dunlop, show examples of routing electrical circuit wires through a wood stud wall and through a wall supported by metal studs.

Nail Stop Simpson Strong Tie NS2 16Ga (C) D FriedmanThe electrical circuit wire must be protected from damage. We don't route electrical wires where they can be punctured by someone driving a nail into a wall to hang a picture.

Using Nail Stops to Protect Wiring & Pipes in Walls

Wires running in walls anywhere from floor level to seven feet above the floor (U.S.) or five feet above the floor (Canada) must be protected from nails driven through walls. Our photo (left) illustrates a 6-inch NS-2 Nail Stop produced by Simpson Strong-Tie. Simpson Strong-Tie describes these as Protecting Shield Plate Nail Stoppers.

We are showing the side of the nail-stop that will be in contact with the stud surface when it it tapped into place, providing 5 3/8" of 16-gauge steel that will protect electrical wiring (or plumbing pipes) from punctures by nails or screws driven into the wall when this nail stop has been placed on a wall stud over the point through which an electrical wire (or pipe - see CONDENSATE DRAINS) has been passed.

Nail stops by Simpson Strong-Tie are made of 16-gauge steel, include sharpened protrusions that allow the plate to be tapped into place on stud surfaces, and are sold in 1 1/2" or 5-inch widths and in lengths ranging from 2 1'2" to 16 5/16". The most commonly-seen nail stop we encounter is the NS1 3-inch model.

Nail stops prevent penetration of fasteners into wiring or piping. They are 16 gauge steel to meet the protection requirements of the code and feature a galvanized coating. Install with prongs or 8d common nails.[6]

Simpson Strong-Tie provides a Code Compliant Repair and Protection Guide that describes the company's range of protective and reinforcing steel devices to comply with the various building code requirements to protect wiring and plumbing from nail and screw fastener damage.

Electrical Wire Clearances from Ducts & Pipes

We also don't route wires too close to places where the wires can be damaged by heat from a heating appliance or chimney, flooded, etc. as you'll see depicted in the two Carson Dunlop sketches below. Thanks to Steve for pointing out erroneous illustration link details, now fixed.

Proper routing of electric wires in metal studs (C) Carson Dunlop Associates Proper routing and support of electrical wire (C) Carson Dunlop Associates


Color coding of wires to properly connect an electrical outlet (C) Carson Dunlop Associates

The illustration at left shows the typical wiring of an electrical outlet or "receptacle", courtesy of Carson Dunlop Associates.

Watch out: Electrical components in a building can easily cause an electrical shock, burn, or even death. 

Even when a hot line switch is off, one terminal on the switch is still connected to the power source.

Before doing any work on the switch, the power source must be turned off by setting a circuit breaker to OFF or removing a fuse.

See SAFETY for ELECTRICAL INSPECTORS and ELECTRICAL WIRING BOOKS & GUIDES

Routing Electrical Wiring Through Metal Studs

Reader Question: NMC cable pulled through metal studs without proper protection

Having a hard time with seller who framed the basement with metal studs, and pulled ROMEX through with no grommets or bushings. Tried to explain that that Metal studs are SHARP and will eventually cut through the romex and short it (POW !), or make the studs live (ouch) I will trade pictures with you if you have some that will go with these.

These photographs (below) are from the inspection. - B.S., Professional home inspector, 7/27/2014

Unprotected NMC wiring passing through a metal stud violates electrical code (C) InspectApedia Bob Sisson Unprotected NMC wiring passing through a metal stud violates electrical code (C) InspectApedia Bob Sisson

Reply:

Greenlee wiring bushings for metal studs PN 712A1000 - www.greenlee.com You are correct that wiring passing through metal studs require protection against damage.

There are simple plastic snap-in wiring grommets or "bushings" that offer that protection and that would have been easy to install at the time of wiring and that can doubtless be retrofit now though if the installer has to cut the bushings to insert them around the existing wiring s/he will need to check with the acceptability of that bushing modification by callling the local electrical inspector for the jurisdiction.

Carson Dunlop Associates sketch of wiring passing through a metal stud (used with permision) just above in this article discusses this very topic.

The photo at left, courtesy Greenlee Corporation (www.greenlee.com) illustrates a plastic bushing PN 712A-1000 designed to protect wiring where it passes through metal studs.

Wiring through metal studs is a very common procedure as we know. In addition to using the larger holes shown in your photos, there is a punching tool (a metal stud punch) and plastic grommets to fit the punched holes so that wires can be run exactly where needed.

I'll post your photos along with images of the proper plastic bushings and send you the link.

U.S. Electrical Code for Wiring NMC through Metal Studs

Meanwhile, if we are reduced to having to cite code to tell some goofus what she or he ought to have known and done in the first place, see these NEC sections:

NEC 334.17 Through or Parallel to Framing Members.

Types NM, NMC, or NMS cable shall be protected in accordance with 300.4 where installed through or parallel to framing members. Grommets used as required in 300.4(B)(1) shall remain in place and be listed for the purpose of cable protection.

and see

NEC 300.4(B) Nonmetallic-Sheathed Cables and Electrical Nonmetallic Tubing Through Metal Framing Members.

(1) Nonmetallic-Sheathed Cable. In both exposed and concealed locations where nonmetallic-sheathed cables pass through either factory- or field-punched, cut, or drilled slots or holes in metal members, the cable shall be protected by listed bushings or listed grommets covering all metal edges that are securely fastened in the opening prior to installation of the cable.

Canadian Electrical Code for Wiring NMC through Metal Studs

Canadian Inspectors needing code citations for protection of non-metallic-sheathed wiring will want to see the 12-19-11 Ontario Electrical Safety Code Bulletin

"Bulletin 12-19-11 Non-Metallic-Sheathed Cables (NMSC) wiring methods, [PDF] Rules 2-034, 2-200, 4-004, 12-500 to 12-526, 12-3012 and 12-3022(3)", May 2012, - retrieved 7/27/4, original source http://www.esasafe.com/assets/files/esasafe/pdf/Sample_Bulletins/12-19-11.pdf. It is interesting that Rule 12-520 does not permit cables to be fished where metal joists, metal top or bottom plates, or metal studs are used.

Rule 12-516(2) permits the use of non-metallic-sheathed cable with metal stud construction. Where NMSC is used in metal stud construction the following are installation requirements:

• Approved inserts (grommets) to protect the cable where it passes through the metal stud. The inserts referred to in Rule 12-516(2)(b) must be approved for the purpose and adequately secured in place.
• Round inserts are approved for a given size opening in a steel stud. If inserts are loose fitting or can be easily removed, they are not adequate for that installation and shall be replaced or installed in properly sized holes.
• The improperly installed inserts can lead to cable insulation failures. Installation of NMSC in steel stud construction will not be accepted where the standards of workmanship or the type of inserts used results in the inserts not staying in place.
• The cable must have adequate mechanical protection. Protection plates are required in all loca- tions where NMSC is within 32 mm from the edge of steel studs in accordance with Rule 12-516(1).

Thanks to Mike Holt for help with this topic.

Sources of wiring protection for metal studs

GREENLEE GL-712A100 Bushings for Metal Studs are constructed of PVC (Poly Vinyl Chloride) which is fire and water resistant. The PVC bushings have a smooth finish all around allowing for quick and easy installation of all your cables without inflicting any damage.

Tyco Electronics metal stud bushings sold in round & square shapes, www.te.comNot only does the triple lock mechanism keep these bushings locked to 12 or 24 gauge metal studs but also prevents damage or abrasion from happening when bundling up to 10 electrical cables at once. These insulation rings are UL listed, CSA Certified and come with a 1 year warranty.


Can be used with any type of wire. Use these bushings to comply with paragraph 300-4b(1) of the 2005 NEC code.

 

Unsafe & Improper Electrical Wire Material & Routing - Zip Cord or Extension Cord

Electrical receptacle and zipcord wiring (C) D FriedmanHere is an example of improper and unsafe electrical wiring: lamp cord or "zip cord" has been routed through the building wall.

Our photo (left) shows an electrical receptacle mounted just about 2" above the finished floor - which is ok except for the ADA requirements, but that zip cord wiring that is run into the wall is improper, unsafe, and a fire hazard.

 

...


Continue reading at NAIL STOPS to PROTECT WIRES or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

or see CLEARANCES of WIRES

Suggested citation for this web page

ROUTING, Securing & Protecting Electrical Wires at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman