InspectAPedia®

Neutral joined with ground in sub panel (C) Daniel Friedman Loss of the Neutral Connection in a Sub Panel Led to a Dangerous Electrical Shock

  • POST a QUESTION or READ FAQs about neutral wire troubleshooting: what can happen when the neutral connections are lost or weak at a building?

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Lost neutral wire - lost grounded conductor wire:

Lost neutral or weak neutral wire electrical connections at a building: what can happen?

This document describes a case history of loss of the neutral connection in an electrical panel combined with failure to isolate the neutral and ground buses leading to an electrical shock.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Case History of an Electrical Ground Failure - Loss of a Neutral Connection in an Electrical Sub Panel Badly Shocks a Homeowner

Burned ground wires in a badly wired sub panel (C) Daniel Friedman

Building owner gets a nasty electrical shock: In an electrical failure case which we investigated, a building owner asked us to determine why he had received a severe electrical shock when he touched his metal work bench located in a detached garage.

Here is what we found in the electrical sub panel in the detached garage: 

[Click any image in these articles to see an enlarged, detailed version.]

Loose neutral connection in a sub panel (C) Daniel Friedman

Our photo at left has a black arrow pointing to the incoming neutral wire in the sub panel. The neutral wire looked connected, but it was not.

Technical note: as reader Jim Benson pointed out, the proper and electrical-code term for the popularly-referred-to "neutral wire" is "grounded conductor wire".
See DEFINITIONS of ELECTRICAL TERMS for details.

Question: What did all of these sub panel neutral and ground wire problems & electrical wiring errors mean?

When the air compressor motor was running it was producing a significant current on the compressor's neutral circuit.

The garage neutral circuit had no connection back to the main building (where it would have been connected to earth in the main panel, but because the owner had (improperly) bonded together the ground and neutral bus in his garage sub panel, the garage neutral circuit was indeed finding a path to earth through a small diameter (and thus overheated and dark) copper ground wire and a local grounding electrode.

Bud, a master electrician from Minnesota points out that in the 2005 NEC there are 2 ways to connect a subpanel in a detached garage. In both methods grounding electrode(s) are required at the garage.

  1. Hot-hot-neutral-ground are run to the garage. The neutral bar is isolated. Separate ground bar. The grounding electrode(s) connect to the ground bar.
  2. Hot-hot-neutral are run to the garage (NO ground). This is connected like a service. A “main bonding jumper” is installed to connect the neutral bar to the enclosure. The grounding electrodes are connected to the neutral (or ground) bar. (This method is no longer allowed in the 2008 NEC.)

The description of the garage event above is a case of example #2 above - there needs to be a MBJ [jumper wire] to connect the neutral and “ground”. The connection was not an error. Without the Neutral-to-Ground bond there is no metal return path for ground fault currents back to the utility transformer. The path would depend on an earth connection, which is not effective and is not allowed. (This is the same error as in my original complaint.)

Normally the neutral-to-ground bond is made in the main electrical panel and not in sub panels, lest grounding conductors end up carrying current during normal operations - a shock hazard. As Bud describes above, in the now obsolete, not allowed case, it was possible to wire a remote outbuilding sub panel as if it were a "main", with no ground returning to the actual remote main panel, and with a neutral-ground bond in the sub panel plus an effective local grounding electrode. We do not recommend this obsolete wiring approach. - Ed.

The problem in this case is the loss of the feeder neutral.

Summarizing some key observations in this lost neutral sub panel case:

  1. Neutral wire between sub panel & main panel was not connected; there was a loose, bad connection in sub panel
  2. The only grounding in this outbuilding was a local ground rod (maybe ineffective?)
  3. A 3-phase compressor was "DIY" wired to run 240V - something fishy there
  4. The compressor circuit included two "hot" wires (black and neutral - the upper right two-pole breaker in the page top photo), and a bare ground wire that was overheated and burned.
  5. A metal workbench was connected to subpanel ground and was "live" when the compressor was running - owner got shocked
  6. Wires to circuit breakers in the panel were overheated (feeding the compressor)
  7. The internal bus in the panel was overheated (behind the CBs)
  8. Ground wires were overheated and burned (and were new at the outset) at the sub panel
  9. No mis-wiring nor overheating related to this case were observed in the property's main electrical panel
  10. In the sub panel, the neutral bus and ground bus were connected, so any neutral circuit current that should have traveled back on the main neutral to the main panel was forced to travel on the local ground wiring and grounding conductors.

Summarizing our conclusions (we will amend if with readers we develop a different analysis of this case):

A combination of missing main neutral in sub panel back to main panel, connecting neutral and ground buses in the sub panel, local ground at the sub panel, connection of metal work bench to panel ground bus, and modified 3-phase compressor in operation produced an electrically live workbench (owner was shocked), and conspired to visibly overheat grounding conductors, hot wires to the panel, panel bus behind the breakers, and grounding wire to the local electrode.

Additional photographs from this case are shown just below. Thanks to reader Randy Gardner for discussing this lost neutral case and opening an argument for clarification of just what was going on.

Below left: metal workbench that was connected to ground wire bus in the sub panel. Below right: overheated corroded main bus connections in the sub panel.

Lost neutral short and shock (C) Daniel Friedman Lost neutral short and shock (C) Daniel Friedman

Below left: 3-phase compressor "re-wired" to run on 240V (we suspect that a 3rd leg was connected to a neutral or ground wire at this hookup. Below right: overheated wires in the sub panel at circuit breakers (we suspect these were powering the compressor motor).

Lost neutral short and shock (C) Daniel Friedman Lost neutral short and shock (C) Daniel Friedman

See also

Why Do Electrical Power Surges or Lightning Strike Current Go to Ground While Short Circuits Follow a Path to the Utility Ground?

Question: We were a little unclear as to why surges find their way to the local earth connection (higher resistance path) while in an emergency such as a short circuit hot to neutral or hot to ground wire, the current does not.

Answer: Bud continued this helpful explanation:

It is a question of what is path is necessary to complete the circuit.

If you want to trip a circuit breaker the fault is hot to “ground” you must complete a path back from “ground” to the transformer neutral. If you wan t to trip a breaker, the path must be metal. That requires a N-G bond and return on the service neutral.

For lightning, you accumulate a different charge between the cloud and the earth. The path is then to the earth to neutralize the charges. (A service panel surge suppressor would have current hot-to-ground/earth.) (Any surge current on the neutral connects to earth through the N-G bond.)

The next most major cause of surges is probably utility switching (normal and abnormal). Switching power factor correction capacitors can be a major source. There the path is probably hot to neutral. (A service panel suppressor would have current hot-to-neutral.)

If there is a utility short that causes a fuse to open, there is high current through the inductance of the power wires that stores energy in a magnetic field. When the fuse opens, the current falls causing the magnetic field to collapse which produces a high voltage. Surge current is probably hot to neutral.

If a high voltage distribution wire falls on the wires to a house, the path needs to be back to the high voltage transformer. The path is likely through the earth, but could be through the service neutral if there is a path (there is probably a continuous neutral connection between transformers that feed houses).

Question: Isn't it the case that current always prefers the path of least resistance and that the current can actually be calculated to flow on two (for example) different paths as a direct function of the relative resistance of each path?

Answer: Nicely stated, particularly the end. And in the case of the ground fault tripping a breaker there will be some current through the earth, just like there is some normal neutral current through the earth. But the resistance of the service neutral is far lower than the earth.

The root causes of this electrical shock were:

Neutral should not be  joined with ground in sub panel (C) Carson Dunlop Associates

Because the garage electrical system was carrying current that should have been flowing only on the insulated neutral wires in the building, when the owner touched his grounded metal work bench and was also touching a damp floor, current flowed through the ground wire, through the metal work bench, through the owner, to earth.

Sketch courtesy of Carson Dunlop Associates.

Our case study of a DOUBLE FAULT involving loss of both the utility company ground and the local building ground shows how power can simply be lost in a building due to grounding system defects.

See LOST ELECTRICAL GROUND

...


Continue reading at FALSE NEUTRAL CONNECTIONS or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see FALSE GROUND at RECEPTACLES

Or see ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR - home

Or see LOST NEUTRAL LIGHT FLICKER for a field report of flickering lights traced to a bad utility company neutral wire

Suggested citation for this web page

LOST NEUTRAL SHOCKS HOMEOWNER at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman