Electric motor test & repair guide:
This article describes A/C electrical motor troubleshooting: here we provide an electric motor diagnostic table, a troubleshooting guide that helps diagnose and repair most electric motor problems for motors found on HVAC equipment in buildings such as air conditioners, furnace or air handler blower fans, oil burner motors, well pumps, and condensate return pumps.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
In this article we provide a diagnostic guide to determine and repair problems with electric motors. The page top photo was taken of of an oil burner electric motor not an air conditioning blower fan motor or pump motor, but you'll see that all of these electric motors look a lot alike.
At left our photo illustrates the motor as typically found in a direct-drive HVAC blower or air handler assembly. (BLOWER FAN OPERATION & TESTING)
Fatal Shock Hazard Warning: Inspecting electrical components and systems risks death by electrocution as well as serious burns or other injuries to the inspector or to others. Do not attempt these tasks unless you are properly trained and equipped.
See DMMs VOMs SAFE USE OF for help in making safe use of electrical test equipment before you start poking your meter probes into anything.
A switch will open ("throwout") at about 2800 rpm for a 3450 rpm electric motor, and the centrifugal switch will open at about 1400 rpm for a 1725 rpm electric motor.
Watch out: This table describes "offline" - power off, disconnected - inspections and tests used to diagnose electric motor problems & failures and also limited Online tests (online MCA) such as measuring current and voltage properties when a motor is running. [37]
Table A: 14 Things to Check (in this order) if an A/C Electric Motor Will Not Start
|
||
---|---|---|
Motor Trouble Cause | Diagnostic Procedure - Offline Motor Circuit Analysis (MCA) | Repair Procedure |
1: Electrical Power is Off to the electric motor or system | Check that all service switches for the equipment are in the "on" position. Check for voltage at the pump motor or pump controls. If no voltage is found, check for voltage at the electric panel. If power is on to the building, check fuse or circuit breaker serving the electric motor that won't run. Check for local reset button on the motor (popped out = off ) - see step 3 below. Check for other power reset or power off buttons such as an access door compartment safety switch that turns off power to the equipment (found on A/C blower compartment doors) |
Turn on "off" switches. Replace bad fuse. Reset circuit breaker; if necessary replace bad circuit breaker. Let hot electric motor cool down, then push in its reset button. Be sure all safety interlock switches such as on compartment doors are depressed and that the doors are securely shut. Replace a bad safety switch. See ELECTRICAL POWER SWITCH FOR HEAT |
2: Blown fuse, tripped breaker on electric motor circuit | Replace the fuse or re-set the breaker - does the electric motor now run and keep running normally? If the fuse/breaker blow/trip problem repeats check for abnormal current draw (Table B), binding mechanical parts, damaged electrical wiring, internal short in motor, seized electric motor (such as an air conditioner compressor). |
Be sure proper breaker or fuse size in ampacity is installed At CIRCUIT BREAKER FAILURE RATES we provide an example of a failure traced to the breaker itself. At BURNED-OUT COMPRESSOR we explain that the compressor motor itself may be seized |
3. Tripped thermal overload reset switch on electric motor | Ambient temperature may be too high, or other failure conditions (defective control switch, loss of well water for well pumps, binding driven mechanical components, low voltage) can cause the motor to run too hot or too long leading to overheating. | Some motors such as submersible pumps include an automatic self-reset once the motor cools down. Other motors use a manual button that must be reset. ELECTRIC MOTOR OVERLOAD RESET SWITCH for how to find and reset this button. In that article we also list the reasons that a motor may have shut down on thermal overload. BURNED-OUT COMPRESSOR diagnostic of cooling down a hot A/C or heat pump compressor with water from a garden hose Detailed diagnosics for overheating motors are at ELECTRIC MOTOR OVERHEATS |
4: Low voltage to the electric motor | Check the line voltage at the motor with VOM or DMM motor or its control switch or at the motor wiring. Incorrect voltage can prevent motors from starting or may cause slow "weak" electric motor operation or may prevent the motor from starting at all. Typically an electric motor requires that voltage remain within 10% of the voltage rating given on the motor's data tag. Frequent operation at low voltage can damage some motors. DMM DIGITAL MULTIMETER HOW TO USE |
Be sure the proper size of wire is used for the ampacity and length of circuit; Test for low voltage to the building. Example: At WATER PUMP REPAIR GUIDE we describe weak well pump operation due to low voltage or due to a partial short to ground in the pump wiring. |
5. Lost phase in power supply to a multi-phase motor | If the motor is a three phase unit check that power is being delivered on all power wires. Note: some electric motors designed for multiple phase power will run on a single phase but run hot and at reduced power. |
|
6: Loose, improper, or broken electric motor hook-up wire | Check wiring against the motor installation manual diagram, check all connections to the motor for tightness, shorts, burns, damage |
Rewire or repair or replace wiring |
7: Bad electric motor control switch | Check the control switch contacts for burning or wear. Example: If the electric motor control is a well pump pressure control switch,check the pressure control switch settings - cut-in and cut-out; inspect for burned, pitted switch contacts or for dirt or wear. |
For motors having trouble starting see CAUSES of HARD STARTING ELECTRIC MOTORS where we explain how a failed starting capacitor OR depending on the motor design, a bad centrifugal switch can prevent a motor from starting. For water pumps, adjust or replace the pressure control switch. Temporary emergency repair by cleaning the switch contacts may be possible. |
8: Bad electric motor control switch or control sensor | A control that is intended to turn the motor on or off may itself be defective, such as a failed or mis-wired thermostatic control, timer, or pressure control switch. Try temporarily bypassing the control switch to assure that power is being delivered to the motor. Clean, repair, or replace the switch. Example: Clogged or leaky tubing connecting a water pump pressure control switch to the water system results in failure to properly sense and respond to water pressure. Example: debris clogging can also occur in the bottom of a water pump pressure control switch where it mounts or connects to the tubing.
|
Check and clear tubing blockage (blow air through tubing). Or install new tubing. Be sure tubing is proper diameter and type to seal properly with other fittings. Tighten tubing fittings to be sure there are no water or air leaks. Soap solution may help find air leaks in tubing fittings. Clear or replace clogged pressure control switch if the bottom sensor opening is clogged and cannot be cleared. |
9: Bad mechanical parts being turned by the electric motor - e.g. blower assembly or well water pump impeller | Turn off electric power to motor, and disconnect the motor from whatever mechanical assembly it is driving. 1. Failing electric motor bearings or motor shaft - the motor turns but runs hot, noisy, with vibration, and/or has trouble starting. The motor may show these symptoms: motor noise hot or overheated motor bearings vibrations at the motor may indicate failing bearings or drive shaft damage sparking at the brushes (not all motors have this component) ultimately a seized motor drive shaft See if you can move the motor shaft. 2. If the electric motor shaft won't turn at all, the motor has bad bearings, dirt in the bearing or slipring, the motor has otherwise become jammed or damaged 3. If the electric motor shaft will turn when disconnected from whatever it is driving, then look for a binding or bearing or damage problem in the driven mechanical parts such as a water pump impeller assembly or a furnace blower fan assembly. |
1. For a frozen electric motor itself, replace the motor 2. Remove obstruction in mechanical components, inspect for and replace damaged parts |
10: Bad electric motor starting capacitor Or Bad Run Capacitor |
Single-phase electric motor hums but won't start on its own. Use a VOM in ohms setting to check resistance across the capacitor. When the motor is switched "on" the ohms reading should immediately drop to zero then slowly climb again towards infinite resistance. If the meter does not move (no current flows) the capacitor is "open". If there is very low or zero resistance the capacitor is shorted. Note: not all electric motors use a starting capacitor. Multi or three-phase motors won't have a starting capacitor. |
Replace the starting capacitor. See TEST a MOTOR START or RUN CAPACITOR how-to Also see HARD STARTING COMPRESSOR MOTORS See CAPACITORS for HARD STARTING MOTORS |
11: Resistance or Ohms Tests Bad or sparking brushes Other internal wiring damage How to distinguish bad electric motor bearings from bad driven mechanical components from an electrical problem such as open or shorted electric motor windings
|
Watch out: To avoid risk of shock or death, turn off electric power to motor, and disconnect the motor completely from any power source as well as disconnecting it physically from whatever mechanical assembly it is driving. See: DMM DIGITAL MULTIMETER HOW TO USE VOLTS / AMPS MEASUREMENT EQUIP TEST EQUIPMENT, ELECTRICAL GUIDE to Visually inspect the motor for evidence of overheating or burning, such as discolored paint, and check for external damage (loose motor mount, broken parts) as well as for dirt or debris that may also enter the motor assembly. When the motor is running, (or was running) did you see sparking at the brushes? See if you can move the motor shaft 1. Jammed electric motor / bad bearings: If the electric motor shaft won't turn the motor has bad bearings or has otherwise become jammed or damaged. If the motor turns with difficulty and/or makes grinding or scraping noises there is internal damage to the motor or its bearings. If the motor shaft wobbles the bearings are shot; if the motor shaft will move back and forth (at right angles to the direction of rotation) more than about 1/8" there may also be internal bearing or shaft damage. Electric Motor Winding Tests Watch out: First turn off electrical power & then remove all external wires connected to the motor. 1.a. Shorted motor windings: Check the motor for shorted windings; typically if the motor windings are shorted to the frame or shorted together the motor will draw very high amps and usually will trip a circuit breaker or blow a fuse when you try to turn it on - Row J in this motor diagnostic table. 1.a.1 Motor windings shorted internally: With the VOM DMM set to measure resistance (Ohms) check for continuity between the motor treminals. Make a note of the resistance that you read. You will need the motor brand, model, possibly serial number, and then with that data you will need to check with the motor manufacturer to see what is the proper resistance across the motor windings. Zero resistance or infinite resistance across the motor windings are easy to diagnose: 1.a.2. Motor windings shorted to ground: With the VOM/DMM set to highest resistance scale and set to measure resistance (Ohms) if you find that there is zero resistance (continuity) between the each individual motor power lead and the motor case or ground connection (test one lead at a time) then a winding is shorted to ground. 3 phase motor leads are numbered T1, T2, T3 etc. - If you see very high resistance, say 500,000 ohms or more, the motor may be OK. 1.b. Open motor windings: Many (not all) single phase and 3-phase electric motors such as those used in equipment and appliances found in homes can be tested "across the leads" for an open winding in the motor. If a motor winding has broken or is "open" there will be no electrical continuity across the winding wires. Check the motor for an open winding - a wire has broken inside the motor but has not shorted to the motor case or to ground as follows: With the VOM or DMM set to its lowest resistance setting and to measure Ohms if you see very low resistance, close to zero but not actually zero, the windings may be OK. If you see higher resistances there is a problem in the motor's windings.(Check the wiring diagram to confirm that the meter is measuring across each winding.) If you see infinite resistance then the winding is definitely "open" or "broken". Watch out: this "static test" of an electric motor's windings can miss a broken wire inside the motor that opens (fails) only when the motor is spinning. Note: an electric motor may have both open winding and shorted winding damage at the same time - something that can happen if the motor's internal parts are internally damaged e.g. by debris falling into the motor. 2. Jammed external driven parts: If the electric motor shaft will turn freely and without wobbling or scraping when disconnected from whatever it is driving, then look for a binding or bearing or damage problem in the driven mechanical parts such as a water pump impeller assembly or a furnace blower fan assembly. |
When an electric motor won't start and we have confirmed that power is being delivered, usually we suspect that the motor windings or the start switch have failed.[1] Be sure you've checked for thermal overload first. Normal electric motor winding resistance: At BASIC ELECTRICAL TESTS for BURNED OUT COMPRESSOR MOTORS we discuss Ohms measurements across the windings terminals of a good electric motor such as is used in an air conditioner or heat pump system where you should see approximately: Pin 1 to Pin 2 – 3 ohms, Pin 2 to Pin 3 – 6 ohms, Pin 1 to Pin 3 – 9 ohms The lowest electrical resistance reading should be below 10 ohms (this is the electric motor run winding). The second highest reading should be about 2-4 times higher than the lowest reading (this is the motor start winding). The highest reading should be the sum of the resistance read across the two smaller motor windings Watch out: a motor winding wire may be damaged but may "open" or "break" only when the motor is trying to spin or only when the motor gets up to full speed. For a frozen electric motor itself, or for a motor with open or shorted internal windings, replace the motor If the mechanically driven components are not jammed or binding, and if the motor does not use a start/run capacitor, or if it uses a start / run capacitor and you have replaced that device without solving the problem, it is possible that an internal wire or winding is open in the motor. If or restoring power the motor runs, this is most likely the case. Order a new motor and replace the old one the next time that the motor won't start. - thanks to Paul Galow for these notes For sparks at the electric motor see SPARKING ELECTRIC MOTOR See these electric motor diagnostic articles BASIC ELECTRICAL TESTS for BURNED OUT COMPRESSOR MOTORS CAPACITORS for HARD STARTING MOTORS |
3. Sparking electric motor brushes: if the motor uses brushes and you see a shower of sparks from the brush/armature area when the motor is running the cause may be Worn brushes: some electric motors have replaceable brushes. If the brush is worn down to a short stub or such that its spring is contacting the rotor, that could be the trouble. To inspect the brush(es), remove the setscrew covering the brush assembly and remove each brush (typically there are at least 2). Replace worn or damaged brushes with a matching brush unit. Brushes are worn unevenly and are jamming in their moving sleeve; replace the brushes and check that the brush moves freely in the sleeve. You may need to clean the sleeve opening. I use a q-tip. A worn or broken brush spring can also cause brushes to jam. A worn, corroded, or broken slip ring can cause sparking at the brushes An overloaded electric motor can result in rapid rush wear, burning, sparking A damaged rotor that is gouged, has worn shaft ends, or has lost a balancing weight (on larger electric motors) will vibrate and can cause brush wear and sparking; that rotor will need to be balanced or repaired. |
Inspect the brushes for wear, damage, sticking, bad springs. Inspect the rotor for vibration, lost weight, out of balance, damage. Check the motor capacity against its load. |
|
4. Sparking electric motor due to burned or scored armature assembly If you see sparks spewing from the electric motor (we often see this on electric drills and circular saws) the motor brushes are probably being damaged by a burned, scored commutator. |
Remove the part, clean and remove scores, replace the motor brushes. |
|
12: Electric motor is shorted out, jammed, burned out, or defective | Fuse blows or breaker trips as soon as the motor tries to turn on. Also see the electrical diagnostic suggestions in row 10 above. See: DMM DIGITAL MULTIMETER HOW TO USE VOLTS / AMPS MEASUREMENT EQUIP SAFETY for ELECTRICAL INSPECTORS TEST EQUIPMENT, ELECTRICAL GUIDE If the external wiring is ok (no short circuits) the motor is shorted internally or has suffered internal mechanical damage. Check that the pump pressure control switch is trying to turn on the pump and that there is voltage at the pump wiring |
For electric motors that operate additional mechanical assemblies, such as a well pump motor that drives a pumping impeller assembly, before condemning the electric motor itself, separate the motor from the components that it drives and check for damaged mechanical parts that are binding the motor. Replace the electric motor or have it repaired and rebuilt by a specialist |
13: Bad or incorrect starter coil on electric motor | Wrong starter coil for the power supply can prevent the motor from starting. | Replace the coil or motor |
14: Bad electric motor centrifugal switch | Check out the rear bell housing of the motor to see if the motor uses a centrifugal switch to switch the start / run capacitor or other windings in and out of the circuit at a specific RPM. If a centrifugal switch is present, check that its switch contacts are not welded closed or contaminated with dirt and grease. The switch mechanism should can move freely. - WikiHow [36] |
See ELECTRIC MOTOR CENTRIFUGAL SWITCH or PTC PRD See OR depending on the motor design, a bad centrifugal switch can prevent a motor from starting. Replace the centrifugal switch assembly if the switch is damaged or not moving freely. |
15: Bad or jammed internal TEFC electric motor cooling fan | TEFC electric motors use a totally-enclosed fan for cooling. The fan blades are behind metal guard on the back of the motor. The fan itself should be securely fastened to the shaft, should not wobble nor be bent or damaged, and the cooling air inlet openings should not be clogged. A bad cooling fan on an electric motor or clogs that prevent cooling of the motor can lead to motor failure. - WikiHow [36] |
If the motor has not already failed, clean the motor fan and fan air inlet openings if clogged and observe whether or not this solves a motor overheating problem. If the motor has not already failed, replace the fan assembly if it is bent, damaged, jammed, will not spin freely - or replace the entire motor assembly. |
16. Noisy electric motor | Various possible causes of electric motor noise include: loose mounts, bad bearings, loose couplings, defects in the driven-assembly or part. If pressing the reset button starts the motor but it runs hot or noisy see the motor noise diagnostic article at right. Check for high current draw in a binding motor - see the amps measurement methods article at right. If the motor hums and is not starting, turn it off right away and see the causes of electric motor not starting listed earlier in this table. |
Using a well pump motor as an example, most of these troubleshooting tips pertain to other electric motor applications in buildings too such as in an air conditioning air handler blower compartment.
Note that DC motors have different operating properties, so while some of the test procedures listed here will help troubleshoot a DC electric motor, other test procedures such as resistance measurements and distinctions between brushless and brush type electric motors may be different. Some of the electric motor troubleshooting suggestions in this list pertinent to well pump problems are from Betta-Flo Jet Pump Installation Manual, National Pump Co. [38]
Electric motor repair general note: on HVAC equipment the electric motor is not normally field repaired. The motor is replaced as a non-serviceable item. However in the hands of an expert, most electric motors can indeed be repaired.
Some of the electric motor troubleshooting suggestions in this list are adapted from and can be found at the Betta-Flo Jet Pump Installation Manual from the National Pump Co.
Also see Electric Motor Startup Ddiagnosis flowchart, Koldwater Training Software, retrieved 2016/11/06, Tel: 1-573-547-5630 Email: support @ koldwater.comoriginal source: http://koldwater.com/electricmotortroubleshooting.html
...
Continue reading at ELECTRIC MOTOR OVERLOAD RESET or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see ELECTRIC MOTOR DIAGNOSTIC FAQs - questions and answers posted originally on this page.
Or see these
ELECTRIC MOTOR DIAGNOSTIC GUIDE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.