InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
AIR CONDITIONING & HEAT PUMP SYSTEMS

A/C - HEAT PUMP CONTROLS & SWITCHES
  Outside Switches, Fuses, Breakers
  Inside Switches,Components
  Air Handler / Blower Switches
  Blower Door Switches
  Backup Heat Controls
  CAPILLARY TUBES
  CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
  Compressor Condenser Switches, Controls
  Condensate Overflow Switch
  CONTACTOR RELAY DIAGNOSIS & REPAIR
  CONTROL CIRCUIT BOARD, A/C
  FAN, COMPRESSOR/CONDENSER UNIT
  Duct System Switches
  Duct System Filters
  OPERATING CONTROLS, A/C & HEAT PUMP
  Starter Capacitors
  Thermostats & Controls
  Thermostatic Expansion Valves
  Motor Overload / Overheat Reset Switch
  Pressure Controls & Safety Switches
  Zone Damper Controls
A/C DATA TAGS
A/C - HEAT PUMP CRITICAL DEFECTS
A/C DIAGNOSTIC FAQs
A/C REFRIGERANTS
A/C TYPES, ENERGY SOURCES

AGE of AIR CONDITIONERS & HEAT PUMPS
AIR CONDITIONER BTU CHART
AIR CONDITIONER COMPONENT PARTS
AIR CONDITIONER TYPES, ENERGY SOURCES
AIR CONDITIONER NOT WORKING

AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
ANIMAL ALLERGENS / PET DANDER
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKUP HEAT for HEAT PUMPS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BOOKSTORE - Air Conditioning "How To" Books

CAPACITORS for HARD STARTING MOTORS
CAPILLARY TUBES
CHINESE DRYWALL HAZARDS
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
CLEANING & Legionella BACTERIA
COMBUSTION GASES & PARTICLE HAZARDS

COMPRESSOR & CONDENSING COIL, A/C

CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS
CONDENSING COIL

CONTROLS & SWITCHES, A/C - HEAT PUMP
COOL OFF HEAT Thermostat Switch
COOLING CAPACITY, RATED
COOLING COIL or EVAPORATOR COIL
COOLING LOAD REDUCTION by ROOF VENTS
CRITICAL DEFECTS on A/C SYSTEMS

DATA TAGS on AIR CONDITIONERS
DEFINITION of Heating & Cooling Terms

DEHUMIDIFICATION PROBLEMS
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DUCT SYSTEM & DUCT DEFECTS
DUCTS - Asbestos
DUCT INSULATION, Asbestos Paper
DUCT INSULATION for SOUNDPROOFING
DUCT SYSTEM NOISES
DUCTS, Asbestos Transite Pipe
DUST CONTAMINATION FROM HVAC?

EDUCATION, HVAC SCHOOLS
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATOR COIL or COOLING COIL
EVAPORATIVE COOLING SYSTEMS
EVAPORATOR COIL or COOLING COIL
EXPANSION VALVES, REFRIGERANT

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES
FURNACES WARM AIR HEATING SYSTEMS

GAS EXPOSURE EFFECTS, TOXIC
GAS DETECTION & MEASUREMENT
GAUGE, REFRIGERATION PRESSURE TEST

HEAT LOSS (or GAIN) in buildings
HEAT LOSS (or GAIN) INDICATORS
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS
HEATING SMALL LOADS
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET

INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSPECTION CHECKLIST - OUTDOOR UNIT
INSPECTION LIMITATIONS, A/C SYSTEMS

LOST COOLING CAPACITY

MANUALS & PARTS GUIDES - HVAC
MOTOR OVERLOAD RESET SWITCH
MOLD in AIR HANDLERS & DUCT WORK

ODORS in AIR HANDLERS & DUCT WORK
OPERATING COST
OPERATING DEFECTS
OPERATING TEMPERATURES

NOISE AIR CONDITIONER / HEAT PUMP
NOISE / SOUND DIAGNOSIS & CURE

PORTABLE ROOM AIR CONDITIONERS
PRESSURE READINGS, REFRIGERANT

REPAIR GUIDE, AIR CONDITIONERS / HEAT PUMPS
REPAIR & DIAGNOSTIC FAQs for A/C

REFRIGERANTS
REFRIGERANT PIPING & DISTANCES
REFRIGERANT PRESSURE READINGS
RETROFIT SIZING for A/C or HEAT PUMPS

SEER RATINGS & OTHER DEFINITIONS
SOLAR ENERGY SYSTEMS
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
SWAMP COOLERS
SYSTEM OPERATION
  OPERATING CONTROLS
  SAFETY CONTROLS

THERMOSTATS, HEATING / COOLING
THERMOSTATIC EXPANSION VALVES

WATER COOLED AIR CONDITIONERS

More Information

Photograph of  this unusual attic air conditioning system is an example of
the range of human creativity observed during a career of building inspections Air Conditioning A/C System Operating Controls & Overcurrent Protection
InspectAPedia®  -      

  • Air conditioning system operation controls: thermostats, zone dampers, electrical switches
  • Air conditioning safety switches
  • Rules of thumb for sizing air conditioner fuses or circuit breakers

This article explains the basic air conditioning system operating controls, air conditioning operating defects, and both normal and abnormal air conditioner operating temperatures and how to measure them. We also review the basic air conditioning safety switches.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

Also see A/C - HEAT PUMP CONTROLS & SWITCHES and THERMOSTATS. This chapter is part of our more extensive air conditioning inspection, diagnosis, & repair document which describes the inspection, diagnosis, and repair of residential air conditioning systems (A/C systems) for home buyers, owners, and home inspectors.

If your air conditioning or heat pump system has lost its cooling capacity or won't start see REPAIR GUIDE for AIR CONDITIONERS. See How to determine the cooling capacity of air conditioning equipment if the system seems to be working but is inadequate to cool your building. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

OPERATING CONTROLS - Air Conditioning System Operating Controls

Basic air conditioning inspection and inspection report information for A/C controls:

  1. Thermostats: The air conditioning system is operated by thermostat in the living area. If multiple air handling units and compressors are installed you should find a thermostat for each area served by that equipment. See THERMOSTATS for details about thermostatic controls. If your Air conditioner or heat pump won't turn on or off properly this is a good place to start. Also see A/C - HEAT PUMP CONTROLS & SWITCHES

  2. Air conditioning system zone dampers: Some air conditioning system designs may use a single air handler and compressor, but may add zone dampers in the duct work to provide individual "zoning" of cool air distribution. In this case each zone thermostat both calls for the system blower/compressor to operate and also causes a motorized zone damper to open to direct cool air to a particular portion of the building. An ordinary home inspection is unlikely to address proper operation of motorized zone dampers. See ZONE DAMPER CONTROLS for details about automatic and manual heating and air conditioning air zone controls.

  3. Manual duct dampers may also be present in duct work to manually balance air distribution among building areas. Be sure to look for these when diagnosing poor cool air delivery to an area.) Also see our note below about the presence of multiple switches and controls. See ZONE DAMPER CONTROLS for details about automatic and manual heating and air conditioning air zone controls.

  4. Electrical switches for air conditioning systems will often be found as follows: (some of these may be absent on some systems). For details see A/C - HEAT PUMP CONTROLS & SWITCHES

    • Electrical panel circuit breakers or fuses will be provided separately to control the air handler (blower system) circuit and the compressor/condenser circuit. Of these the compressor is usually supplied by a 240V circuit and the air handler by a 120V circuit.

    • Compressor safety shut off switch outside at the compressor/condenser. The switch may be a circuit breaker, fuse, or a simple "pull-out" disconnect located close to the compressor.
    • Air handler service switch inside on or close to the air handler unit itself
    • Air handler blower compartment safety switch: a safety interlock that will turn off electricity to the air handler or blower unit if the blower compartment door is not securely shut. If your air conditioner blower will not start this switch and the blower compartment doors should be checked. See BLOWER FAN OPERATION & TESTING
    • Air conditioner/heat pump contactor relay switch: turns on high amp drawing equipment such as the compressor motor. See CONTACTOR RELAY DIAGNOSIS & REPAIR
    • Air conditioner or heat pump pressure control safety switch: turns off the system at excessive refrigerant pressure and in some systems at too-low pressure. Also used in automotive air conditioning. See A/C - HEAT PUMP CONTROLS & SWITCHES

SAFETY CONTROLS - Air Conditioning Automatic Safety Controls - Cooling System Fuse or Circuit Breaker Size Requirements

Electric Power Controls - Safety Disconnects for Air Conditioners

Photograph of the outdoor safety switch for an air conditioning residential systemSafety disconnects should installed outside next to the compressor/condenser unit and are often also installed next to or mounted on the air handler/blower unit.

If you cannot find an outside electrical disconnect one should be installed. These controls are recommended for safety to reduce the temptation to open the cabinet and work on the equipment with power on.

Working on electrically "live" cooling equipment risks both shock and mechanical injury such as being cut by the fan if the motor starts unexpectedly. Safety shutoffs are required for new equipment.

See A/C - HEAT PUMP CONTROLS & SWITCHES for details.

How to Specify the Breaker or Fuse Size for Air Conditioning Circuits

Electrical panel circuit breakers (C) D Friedman

Our photograph of a modern circuit breaker panel (left) shows where your search for the air conditioning or heat pump system main circuit breakers would typically begin. Look for two control circuits for the air conditioner or heat pump system that will typically include:

  1. A circuit, 120V or 240V serving the indoor air handler
  2. A circuit, usually 240V, serving the outdoor compressor/condenser unit.

The Amperage Rating of safety disconnects and A/C or Heat Pump circuit breakers

The safety switch on newer equipment may be a simple pull-out fuse-block type power disconnect, leaving circuit protection to be provided only at the circuit breaker or fuse for the A/C circuit where it originates in the electrical panel. Where the actual overcurrent protection is provided (at older circuit breakers used as auxiliary safety disconnects at the equipment, and at the main panel at the origin of the cooling circuit for the compressor/condenser unit) electrical overload protection size (circuit breaker or fuse amperage rating) for modern A/C equipment is specified by the manufacturer.

The Maximum Fuse or HACR type Breaker: specifies the maximum overcurrent protection or MOP to be used to protect the equipment. The permitted ampacity of the equipment electrical circuit protection (fuse or circuit breaker amps) expressed as MOP or Maximum Overcurrent Protection. If MOP is specified, the breaker or fuse protecting the equipment should match this number.

As we explained at the beginning of this document, a hermetic compressor draws varying amounts of current (measured in amps) as its internal pressure changes during operation. We said that current draw is higher when starting the motor than when the system is in steady state operation.

Current draw is highest if the motor is starting against its highest back pressure such as if the air conditioning system has been turned off and then back on in the middle of operation. Because fusing an air conditioning compressor at the minimum level can result in blown fuses or tripped breakers during these intervals of heavy current draw during compressor startup, compressors are either protected by a slow-blow fuse or a somewhat larger than minimum circuit breaker.]

Rules of thumb for over sizing air conditioning system breakers or fuses:

On some older equipment MOP is not specified. Only when MOP has not been specified can the overcurrent protection required be determined by alternative means such as [RLA OR BCSC whichever is greater x 175%], or if the compressor keeps tripping that device or blowing that fuse, RLA x 225% might be used.

The National Electrical Code (NEC) specifies the degree to which a breaker or fuse may exceed the RLA. [For example, if the MOP or fuse size is specified by the manufacturer to be 40 amps, then a 40 amp breaker must be installed with no increase or change in that rating.]

Multiple switches are often present on cooling systems. As we reminded in the previous chapter, if the air conditioning system won't run, before requesting a service call check all of the switches as well as the thermostat for proper settings.

Air Conditioner Fuse or Circuit Breaker Size Details

Generally, what is the ampacity we see in the field when inspecting an air conditioning compressor circuit?

When the air conditioning system is running, if you measured the amperage, it would be roughly 80% of the RLA. The breaker size is typically about 125% of the total of the compressor RLA and the condenser fan FLA (full load amperage).

We are referring here to the main circuit breaker that controls the air conditioner compressor/condenser unit - a switch that is typically located in the main electrical panel or in a sub-panel serving the air conditioning or heat pump equipment.

 


Photograph of the outdoor safety switch for an air conditioning residential system, shown here with the cover open

Our photo at left shows a different switch: an outside service switch that incorporates a circuit breaker next to the compressor/condenser.

This circuit is for use by the service technician and because it is downstream of the wire bringing power to the compressor/condenser unit, it is not protecting that wire from an overcurrent. While both of these circuit circuit breakers must be properly served, don't confuse their role nor their location.

The rationale is that the circuit breaker protecting the air conditioner compressor unit should trip in the event of a locked rotor [the revolving axle of a compressor motor, for example] or some significant electrical event, but should not trip during start up loads which, as we know can be significantly higher than the RLA momentarily [as the compressor motor draws higher amperage to get itself started].

Why can we put an "oversized" fuse or circuit breaker on an air conditioning compressor circuit?

An air conditioning electrical circuit is different than a general household circuit in that we have a known current load.

[There is only one device connected to the air conditioning electrical circuit, and we can read its operating characteristics.] We are not worried about an overload situation where people plug several appliances into receptacles on a single circuit. Generally speaking, the amperage draw is fine or is way too big.

Code Citatin: Section E3602.10 of the IRC says,

Branch circuits for air conditioning and heat pump equipment. The ampacity of the conductors supplying a multi motor and combination load equipment shall not be less than the minimum circuit and capacity marked on the equipment.

The branch-circuit overcurrent device rating shall be the size and type marked on the appliance and shall be listed for the specific purpose." In short, do what it says on the data plate.

Thanks to Alan Carson for these details.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

AIR CONDITIONING & HEAT PUMP SYSTEMS

A/C - HEAT PUMP CONTROLS & SWITCHES
  Outside Switches, Fuses, Breakers
  Inside Switches,Components
  Air Handler / Blower Switches
  Blower Door Switches
  Backup Heat Controls
  CAPILLARY TUBES
  CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
  Compressor Condenser Switches, Controls
  Condensate Overflow Switch
  CONTACTOR RELAY DIAGNOSIS & REPAIR
  CONTROL CIRCUIT BOARD, A/C
  FAN, COMPRESSOR/CONDENSER UNIT
  Duct System Switches
  Duct System Filters
  OPERATING CONTROLS, A/C & HEAT PUMP
  Starter Capacitors
  Thermostats & Controls
  Thermostatic Expansion Valves
  Motor Overload / Overheat Reset Switch
  Pressure Controls & Safety Switches
  Zone Damper Controls

A/C DATA TAGS
A/C - HEAT PUMP CRITICAL DEFECTS
A/C DIAGNOSTIC FAQs
A/C REFRIGERANTS
A/C TYPES, ENERGY SOURCES

AGE of AIR CONDITIONERS & HEAT PUMPS
AIR CONDITIONER BTU CHART
AIR CONDITIONER COMPONENT PARTS
AIR CONDITIONER TYPES, ENERGY SOURCES
AIR CONDITIONER NOT WORKING

AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
ANIMAL ALLERGENS / PET DANDER
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKUP HEAT for HEAT PUMPS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BOOKSTORE - Air Conditioning "How To" Books

CAPACITORS for HARD STARTING MOTORS
CAPILLARY TUBES
CHINESE DRYWALL HAZARDS
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
CLEANING & Legionella BACTERIA
COMBUSTION GASES & PARTICLE HAZARDS

COMPRESSOR & CONDENSING COIL, A/C

CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS
CONDENSING COIL

CONTROLS & SWITCHES, A/C - HEAT PUMP
COOL OFF HEAT Thermostat Switch
COOLING CAPACITY, RATED
COOLING COIL or EVAPORATOR COIL
COOLING LOAD REDUCTION by ROOF VENTS
CRITICAL DEFECTS on A/C SYSTEMS

DATA TAGS on AIR CONDITIONERS
DEFINITION of Heating & Cooling Terms

DEHUMIDIFICATION PROBLEMS
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DUCT SYSTEM & DUCT DEFECTS
DUCTS - Asbestos
DUCT INSULATION, Asbestos Paper
DUCT INSULATION for SOUNDPROOFING
DUCT SYSTEM NOISES
DUCTS, Asbestos Transite Pipe
DUST CONTAMINATION FROM HVAC?

EDUCATION, HVAC SCHOOLS
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATOR COIL or COOLING COIL
EVAPORATIVE COOLING SYSTEMS
EVAPORATOR COIL or COOLING COIL
EXPANSION VALVES, REFRIGERANT

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES
FURNACES WARM AIR HEATING SYSTEMS

GAS EXPOSURE EFFECTS, TOXIC
GAS DETECTION & MEASUREMENT
GAUGE, REFRIGERATION PRESSURE TEST

HEAT LOSS (or GAIN) in buildings
HEAT LOSS (or GAIN) INDICATORS
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS
HEATING SMALL LOADS
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET

INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSPECTION CHECKLIST - OUTDOOR UNIT
INSPECTION LIMITATIONS, A/C SYSTEMS

LOST COOLING CAPACITY

MANUALS & PARTS GUIDES - HVAC
MOTOR OVERLOAD RESET SWITCH
MOLD in AIR HANDLERS & DUCT WORK

ODORS in AIR HANDLERS & DUCT WORK
OPERATING COST
OPERATING DEFECTS
OPERATING TEMPERATURES

NOISE AIR CONDITIONER / HEAT PUMP
NOISE / SOUND DIAGNOSIS & CURE
  Air Leak Noises
  AIR CONDITIONING & HEAT PUMP NOISES

PORTABLE ROOM AIR CONDITIONERS
PRESSURE READINGS, REFRIGERANT

REPAIR GUIDE, AIR CONDITIONERS / HEAT PUMPS
REPAIR & DIAGNOSTIC FAQs for A/C

REFRIGERANTS
  GAUGE, REFRIGERATION PRESSURE TEST
  REFRIGERANT CHARGING PROCEDURE
  REFRIGERANT DRIERS & FILTERS
REFRIGERANT PIPING & DISTANCES
REFRIGERANT PRESSURE READINGS
RETROFIT SIZING for A/C or HEAT PUMPS

SEER RATINGS & OTHER DEFINITIONS
SOLAR ENERGY SYSTEMS
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
SWAMP COOLERS
SYSTEM OPERATION
  OPERATING CONTROLS
  SAFETY CONTROLS

THERMOSTATS, HEATING / COOLING
THERMOSTATIC EXPANSION VALVES

WATER COOLED AIR CONDITIONERS

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Complete List of Air Conditioning & Heat Pump Design, Inspection, Repair Books at the InspectAPedia Bookstore.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Modern Refrigeration and Air Conditioning, A. D. Althouse, C.H. Turnquist, A. Bracciano, Goodheart-Willcox Co., 1982
  • Principles of Refrigeration, R. Warren Marsh, C. Thomas Olivo, Delmar Publishers, 1979
  • "Air Conditioning & Refrigeration I & II", BOCES Education, Warren Hilliard (instructor), Poughkeepsie, New York, May - July 1982, [classroom notes from air conditioning and refrigeration maintenance and repair course attended by the website author]
  • Refrigeration and Air Conditioning Technology, 5th Ed., William C. Whitman, William M. Johnson, John Tomczyk, Cengage Learning, 2005, ISBN 1401837654, 9781401837655 1324 pages
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment ($69.00 U.S.).
  • Air Conditioning Inspection, Diagnosis, Repair, Efficiency all the basics for home owners, inspectors, new repairmen
  • NewAir Conditioning SEER - New DOE Air Conditioner and Heat Pump Efficiency Standard
  • Asbestos HVAC Ducts and Flues field identification photos and guide
  • Fiberglass: Indoor Air Quality Investigations: Fiberglass in Indoor Air, HVAC ducts, and Building Insulation
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com