InspectAPedia®

Photograph of an air conditioning thermal expansion valve for a heat pump Thermostatic Expansion Valves (TXVs or TEVs)
& Other Refrigerant Metering Devices

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


HVACR Thermostatic Expansion Valves - TEVs:

This air conditioning repair article series explains the function and installation of all types of refrigerant metering devices, beginning with the most-common thermostatic expansion valve or TEV (or thermal expansion valve) that controls release of refrigerant into the evaporator coil of an air conditioning or heat pump system.

We define and explain other refrigeration equipment metering devices including AEVs (Automatic Expansion Valves), manually adjusted expansion valves, capillary tubes and Low Side or High Side refrigerant float valves.

Also discussed: Thermostatic expansion valve installation instructions, inspection and testing; How a TEV regulates or meters refrigerant in an air conditioner or heat pump; Guide to all refrigerant metering devices for air conditioners, heat pumps, refrigerators, freezers: TEVs, Automatic Expansion Valves AEVs, Float Valves, Manual Valves, Capillary Tubes.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Guide to Expansion Valves for Refrigerant Metering on Air Conditioners & Heat Pumps: Definitions of AEVs, TEVs, Manual Valves, Cap Tubes

Thermostatic expansion valve schematic (C) Carson Dunlop Associates

This article describes how TEVs work, where and how a thermostatic expansion valve is installed on an air conditioner or heat pump, and how the TEV may be adjusted.

[Click to enlarge any image] Schematic of a thermostatic expansion valve courtesy of Carson Dunlop Associates.

We also list possible errors in TEV installation such as improper positioning of the TEV sensor bulb.

Most of our discussion below focuses on TEVs (Thermostatic Expansion Valves) as these refrigerant metering devices are most widely used on residential air conditioners and heat pump systems.

Article Series Contents

All types of refrigerant metering devices are discussed in this article. Photograph of the thermostatic expansion valve at page top is courtesy of Alan Carson, Carson Dunlop Associates in Toronto.

Definition of TEV - Thermostatic expansion valve: An air conditioner thermal expansion valve or "TEV" or just "expansion valve" (tan colored device in the page top photo) is a device located at the cooling coil and connected between the incoming liquid refrigerant line and the refrigerant inlet to the cooling coil in the air handler.

A temperature sensor mounted at the end of the cooling coil controls the rate at which the TEV releases refrigerant into the coil - hence the term "thermostatic" expansion valve.

It's an "expansion" valve because by controlling the release of refrigerant into the coil the expansion valve releases high pressure refrigerant into the low pressure environment of the cooling coil, causing the refrigerant to expand and evaporate - cooling the coil.

The actual operation of a TEV is detailed at HOW TXVs WORK. We explain this concept in more detail at REFRIGERATION BASICS.

Definition of EEV - Electric exansion valve or electronic expansion valve: an air conditioner, heat pump or other refrigeration system refrigerant metering device that is controlled electronically by the combination of a separate electronic control unit, temperature sensing thermistors, pressure transducers, and an electrically-operated stepper motor that adjusts refrigerant flow rate through the valve.

Like a TEV, an EEV is also located at the cooling coil and connected between the incoming liquid refrigerant line and the refrigerant inlet to the cooling coil in the air handler.

Details are at TEV Compared to EEV ELECTRIC EXPANSION VALVES.

Other types of refrigerant expansion valves control refrigerant by various means other than sensing coil temperature.

For completeness in this article we also define and explain other refrigerant metering devices including

Refrigerant expansion valves or metering components are used on both air conditioning systems and on heat pumps as well as on dehumidifiers; heat pumps are essentially the same in components as air conditioners except for additional control features to permit refrigerant to circulate in either direction in the system, moving heat outside (air conditioning) or moving heat inside (heat pumps).

On residential refrigerators and freezers, room and portable air conditioners, and dehumidifiers a simpler (and not adjustable) CAPILLARY TUBES may be used for refrigerant metering.

Refrigeration Basics: Why we need a refrigerant metering device like a capillary tube or thermostatic expansion valve

Before we explain how refrigerant metering devices work in detail it's useful to get a most basic view: the refrigerant metering device provides a restriction in the flow of liquid refrigerant from the compressor/condenser into the evaporator coil.

It is this restriction that, by limiting the flow rate of refrigerant into the evaporator, allows the compressor (a pump) to raise the refrigerant pressure on the high side (condensing it into a liquid) and drop the refrigerant pressure on the low side (evaporating the liquid back into a gas in the cooling coil).

The state change (vaporization from liquid to gas in the cooling coil) is what cools the coil and thus cools indoor air air blown across the cooling coil. But that state change is not enough. To get our refrigerant gas back to a liquid state (to continue the cycle) we need to be able to raise the temperature at which the refrigerant gas will change back to a liquid. It is the high pressure provided by the compressor that accomplishes this step.

It is the flow restriction provided by a cap tube or by an expansion valve such as a TEV in the refrigerant piping system that allows the compressor pump to raise the system pressure and thus increase the temperature at which the coolant changes state. Raising the coolant temperature above outdoor ambient temperature causes heat to flow from the coolant into outdoor air.

So in sum the TEV or cap tube allows the compressor to reduce pressure on the LOW side of the metering device and raise pressure on the HIGH side of the metering device.

Expansion Valves & Thermostatic Expansion Valves for Refrigerant Metering Actually Work

TEV valve © D Friedman at InspectApedia.com All cooling and refrigeration systems and heat pumps using refrigerant gases make use of some type of expansion valve or refrigerant metering device, of varying complexity.

Even a simple window air conditioner or a refrigerator make use of an expansion valve [shown at left] or a small-diameter CAPILLARY TUBE or "cap tube" which meters refrigerant into the cooling coil. How do these refrigerant metering devices actually work?

Step 1: Expansion valve meters liquid refrigerant into the cooling coil: Inside of the thermostatic expansion valve (TEV) or other metering device the refrigerant passing through is mostly liquid.

The refrigerant metering device is the "doorway" between the refrigeration system high side (compressor output) and low side (cooling coil interior) as it releases liquid refrigerant into the cooling coil at a controlled rate.

Step 2: Liquid refrigerant boils to a gas in the cooling coil: Inside the cooling coil, the liquid refrigerant being metered in through the TEV (or equivalent metering device) converts increasingly to a gas (it "boils" and changes state from liquid to gas) as it enters and then flows down through the evaporator coil, until the refrigerant is totally in a low-pressure, low temperature gaseous state by the time it reaches the end of the evaporator coil.

The energy absorbed by the change in refrigerant from a liquid to a gas inside the cooling coil is what absorbs sensible heat and chills the indoor air handler cooling coil so that the coil cools air blown across it.

Step 3: Low pressure refrigerant gas is drawn back into the compressor/condenser unit: This low pressure, low temperature refrigerant gas present at the end of the cooling coil or "evaporator coil" is then drawn back into the compressor via the suction line connecting the evaporator coil outlet to the compressor inlet port.

Step 4: Low pressure refrigerant gas is compressed to high temperature/high pressure gas and then condensed back to liquid refrigerant out in the compressor/condenser unit (typically located outdoors). It's the high temperature of the gas entering the outdoor condensing coil that allows heat to ultimately be transferred into outdoor air (or into water if we're using a water-based air refrigeration system).

Our photo (above left shows another tan TEV.

The very thin coil of copper tubing connects the TEV to its sensor bulb that appears to be taped to the refrigerant suction line just outside of this air conditioning air handler.

The TEV shown in this photo is used on a heat pump system so it includes extra tubing so that with a REVERSING VALVE on HEAT PUMPS the TEV can permit the refrigerant to reverse its flow of direction when changing from cooling mode (move indoor heat to outdoors) to heating mode (collect and move outdoor heat to indoors).

The larger diameter copper tubing feeds liquid refrigerant into the TEV from the compressor/condenser unit (the left side of this valve) and the copper tubing on the right side of the valve loops up and into the air handler where inside the unit you'd see it entering the top of the cooling coil. In this photo you cannot see the adjustment point on the bottom of this valve. We say more about the proper position and location of this valve below.

The TEV valve maintains the pressure difference (high and low) at the entry point to the cooling coil, thus assuring that as the high-pressure refrigerant enters the low pressure space of the cooling coil, it can "evaporate" from a refrigerant liquid to a gaseous form, thus producing the temperature drop that cools the cooling coil itself.

The thermostatic expansion valve is a refrigerant metering control device, and it is not a control or switch which can be directly operated by the user when using an air conditioning system, but it is a critical control needed for metering refrigerant into the cooling coil.

Exactly how the Thermostatic Expansion Valve Works to Control Refrigerant Release into the Cooling Coil (Evaporator Coil):

When the pressure sensed by the TEV sensor bulb (P2) is less than or equal to the pressure in the TEV bottom (P1) then this condition allows the spring inside the TEV to close the valve.

When the pressure sensed by the TEV sensor bulb (P2) [and transmitted to the TEV valve top by the sensor tubing] is greater than the pressure in the TEV bottom (P1) then this condition allows the valve to open [the cooling coil temperature is up] thus allowing more refrigerant to enter the cooling coil, thus boiling more liquid refrigerant, thus dropping the cooling coil temperature back down.

Our sketch also show the two bellows on the typical TEV control (circled in red). The bottom bellows are adjusted by the TEV adjustment screw, and the top bellows are adjusted by the temperature sensing bulb and copper tubing (purple) that connect that bulb to the TEV top cap.

The high pressure line is shown in red. A dryer is shown in green. [Click any image to see an enlarged, detailed version.]

Superheat

This definition and discussion have moved to SUPERHEAT DEFINITION

Subcooling

This definition and discussion have moved to SUBCOOLING DEFINITION

Subcooling temperatures are measured on the refrigerant line just ahead of (supplying refrigerant into) the TEV.

External Pressure Equalization type Thermostatic Expansion Valves

For completeness we include this helpful note also from Danfoss, describing the requirement for external pressure equalization type expansion valves:

Expansion valves with external pressure equali- zation must always be used if liquid distributors are installed.

Typically, the use of distributors gives a pressure drop of 1 bar across distributor and distribution tubes.

Expansion valves with external pressure equalization should always be used in refrigeration systems with small compact evaporators, e.g. plate heat exchangers, where normally the pressure drop will be greater than pressure corresponding to 2K.  - Danfoss (2005) 

What's the difference between a TEV (Thermostatic Expansion Valve) and an AEV (Automatic Expansion Valve) ?

TEV function sketch © D Friedman at InspectApedia.com A THERMOSTATIC EXPANSION VALVE [discussed in this article] or TEV is similar to

an AUTOMATIC EXPANSION VALVE [discussed in this article] (AEV) but unlike the single-bellows internal design of the AEV, a TEV has a second bellows on the top of the valve along with a tube (purple) that attaches the TEV valve top bellows to a temperature sensing bulb mounted at the end of the cooling coil.

[Click to enlarge any image]

Our sketch, adapted from notes taken in refrigeration class back in the 1980's shows a simplified air conditioning compressor or heat pump components and the movement of refrigerant through the system.

The sensor or sensing bulb (yellow rectangle) of a TEV (purple rectangle) measures the superheat1 across the cooling coil (light blue) regardless of the actual refrigerant pressure inside the coil and uses that information to maintain the frost line at the end of the evaporator coil.

In contrast, the AEV regulates refrigerant just by pressure - it does not include the sensing bulb control.

Our TEV operation sketch (above left) illustrates the placement of the sensing bulb and its small diameter tube attached to the TEV top (purple) that controls the TEV release of refrigerant into the cooling or evaporator coil. You'll also see the temperature numbers written along the evaporator coil (blue coil at left side of sketch) showing the likely increase in temperature as we get close to the end of the evaporator coil.

Note 1: Superheat gives an indication if the amount of refrigerant flowing into the evaporator is appropriate for the load. If you want to know more about superheat see SUPERHEAT DEFINITION.

Thermostatic Expansion Valve Type & Model Identification

at REFERENCES we provide links to examples of TEV identification catalogs and labe decoding details for several manufacturers of thermostatic expansion valves, along with company contact information. Most TEVs include a label on the expansion valve round head or attached to the valve body.

This label includes the brand and TEV model identification. You may need to consult the manufacturer's specific catalogs to decode this data, though if you are simply replacing an existing thermostatic expansion valve you can simply bring the old valve or its label information (take a photo) to your HVACR equipment distributor.

The TEV Label will identify the thermostatic expansion valve type, the evaporating temperature range in which the valve will operate, the MOP point, the refrigerant gas, a maximum test pressure, PB/MWP.

Example TEV Data Label Decoding for Danfoss: Example: TEV Model TEX2

TE = Expansion Valve

X = Refrigerant, where these refrigerant codes apply (other manufacturers may use different encoding)

Additional data will be encoded on some TEV components. For example the orifice assembly for a Danfoss TE/TE2 thermostatic expansion valve is stamped with:

What's the Difference Between a Thermostatic Expansion Valve (TEV) & an Electronic Expansion Valve (EEV)

A traditional TEV or thermostatic expansion valve is controlled by a spring, bellows, and pushrod. Adjustment of a TEV of that design means changing the pressure of the spring against the bellows to release refrigerant at the proper rate to maintain constant "superheat" across the coil, that is the cooling coil will be properly chilled along its entire length.

Pressure from the temperature sensing bulb connected to the top of the TEV (also called TXV by some) operates to open the valve. The spring inside the TEV pressing on the opposite side of the bellows or diaphragm plus pressure from the evaporator side (cooling coil side) of the valve operates to close the valve.

On a "balanced port" design TEV pressure of the liquid refrigerant from the condenser unit that would also tend to open the valve is cancelled out or "balanced" by the balancing port. You can recognize a traditional TEV of this design: it will have no electrical wires attached.

Electronic expansion valve (C) InspectApedia.com  - this device is sold online by http://www.partstown.com

In contrast, an electronic expansion valve or EEV is a more sophisticated refrigerant metering device. A stepper motor rotates its drive shaft in one or more increments that open or close the expansion valve in small increments (as many as 1596 "steps" at 200 steps per second) as directed by an electronic controller that in turn is monitoring the system temperature.

A gear train connects the stepper motor's drive shaft to a pin that moves up or down, closing or opening the size of the port through which liquid refrigerant is being passed.

The EEV shown above, a Master-Bilt Electric Expansion Valve Model 19-13773 ser-6 is sold online by http://www.partstown.com and is also available from your local HVACR supplier.

[Click to enlarge any image]

Stepper motors in EEVs operate very precisely and their controller is smarter than I am, able to remember motor positions and to make precise and rapid adjustments to refrigerant flow, seeking the same goal: maintaining a constant superheat across the cooling coil.

Stepper motor for an electronic expansion valve (C) InspectApedia.com  - this device is produced by Trane, EEV MOT15214 and was found for sale on eBay; availale from Trane or from HVAC suppliers.

The EEV stepper motor shown above is produced by Trane, EEV MOT15214 and was found for sale on eBay; available from Trane or from HVACR suppliers.

The controller for an EEV is in turn informed by one or more temperature sensors, normally a thermistor (search InspectApedia for THERMISTORS to read details) mounted in the path of air flow in the system. In some HVACR designs the EEV controller may also be informed by pressure transducers.

A change in pressure is translated by the pressure transducer to a corresponding change up or down in voltage sent to the controller.

The EEV controller uses that voltage change to obtain or actually calculate the [theoretical and close to actual] refrigerant temperature in the system and then uses that data to adjust the EEV metering of refrigerant to seek the desired temperature (or pressure).

Experts note that an advantages of EEV controllers in HVACR systems include an improved ability to protect the compressor from refrigerant floodback, precise temperature and pressure control of the system, and the ability through controller programming to design customized or special-application use of refrigerant metering and refrigeration systems.

Where to find information about the installation, adjustment & operation of electronic expansion valves EEVs

Excellent information about EEVs is provided by ACHR News, a publication of the refrigeration industry, including this source for the above:

Thermostatic Expansion Valve (TEV) Installation, Inspection, Diagnosis & Testing

Thermostatic expansion valves (TEVs) are designed to meter refrigerant into the cooling coil at the proper rate. This design can keep the proper dose of refrigerant entering the cooling coil for maximum air conditioning or heat pump system operating efficiency. TEVs are similar to automatic expansion valves (AEVs) discussed below, but incorporate the signal from a temperature sensor mounted at the end of the evaporator coil

Details: If you are diagnosing a problem with an air conditioner or heat pump and the TEV appears to be involved, check the TEV installation details against the information we list in detail in a separate article at TEV INSTALL & REPAIR

Example Refrigeration Equipment Field Diagnosis & Repair: Thermostatic Expansion Valve Inspection, Testing, Experiments with TEV and Pressure Control Switch

How to Adjust the Thermostatic Expansion Valve

For most TEVs, adjusting the thermostatic expansion valve woks as follows:

Field Notes from TEV Adjustment

The following are from my [DF] notes from a refrigeration service call [1982] VERY early in my [DF] refrigeration training:.

Case outline & initial observations: Commercial cooler running too warm - (WACOOP), hermetically sealed compressor, Kramer W14, unknown refrigerant (thought from a label maybe it should be R22 but someone may have charged with R12), cooler running too warm, need to diagnose cooling coil and fan operation and control settings on an old, used cooler just brought in. Very common on old equipment like this: no labels, no data tags, not much information at all.

Fanco refrigerant pressure switch: found set at 35# and 10# differential, connected improperly to the low side service port, cannot fully shut off the service port as a result - maybe leaking?

Compressor pump: running continuously.

Ambient temperature about 90 DegF; R12 in my service canister is at 100 psi static.

Low side refrigerant pressure: measured 40 psi. If there is R12 in the system I'd expect about 45 deg. temp at proper charge, and if R22 in the system I'd expect about 20 degF temp at proper charge and operation. But there were NO frost lines on the equipment, so I know that there is little or no liquid refrigerant and the system is operating at about 45 degF so must be filled with R12.

Actions and Tests:

Set the TEV 8 quarter turns more open - out and down, to see what happens.
With the fan off the Low Side goes to 25 psi and 25 degF.

The frost line moved at least to the se3nsor bulb and the pump (compressor) shut off. The low side pressure went up to 36 psi and then the pump restarted. This is telling me what the pressure control switch is doing.

Further actions and observations:

Opened the TEV 1/4 turn more to see the effect.
System shut off at 23# and came back on at 37#

Turned the blower cooling fan back on since the Dx was iced coil. Low side went up to 50, then dropped to 39# and stabilized.

Kept a series of observations from 10:55 PM to 12:42 AM (service call made during hours the business was closed to avoid disruption)

5 then 9 more turns opening the TEV, low side up to 75# & can see gas in the SIGHT GLASS in the refrigerant line - this is "wide open" TEV setting

9 turns closing down the TEV to almost shut - so there are about 10 turns from wide open to fully shut on this TEV. At 9 turns towards shut from wide open, the low side pressure falls FAST!

9 turns back open at the TEV confirms gas bubbles again in the sight glass and 70# pressure.

Closed the TEV completely (about 9+ turns to the right or "up" or "in"). Suction lines closed, no gas in the sight glass, rapid low side pressure drop to 26#, compressor turns off at 20#.

I am convinced the pressure control switch is working properly, that is it does what it's pressure settings say it should be doing.

Set the TEV to 12 1/4-turns (in other words 3 full turns) open from fully shut. Suction line very cold, low side goes to 30#. 2 more turns open, low side goes up to 34#.

Finally decide to run the system with the TEV open 3 quarter-turns (about 3/4 of one turn) from fully shut. The system stabilizes with the cooler (a refrigerator) in the mid to upper 40's, no more oscillating, no coil frosting.

If I set the cut-in pressure way down the cooling coil ices over and the compressor will run continuously without cooling anything. See frost moving down the low side line. So that's not the right "fix".

I could set the pressure switch to 12.5 psi, left the TEV alone, and got the cooler down to our target of 32 degF.

The HI event sets the defrost cycle by setting the cut-in. The low event sets the cutout and therefore the lowest temp we will reach. A bigger low event means a lower target temperature, but the risk is that if you set it too low the compressor will run continuously and ice up the coil without ever running a defrost cycle.

The TEV seemed to be sometimes sticking. The low side pressure would hang at 28# or rise only very slowly as if the TEV was not opening when I expected it to. Have to be sure the blower fan is also running when checking this performance.

Final resolution of the cooler operation troubles:

Ultimately I replaced the TEV with a Singer TXV223FA 1/2 with a TE value of 9 (heat delta), installed a filter dryer (#082 PN 2003), set the pressure control to 35# on and 20# off. adjusted the system to get NO frost on the suction line near the compressor. Final pressure switch settings were 33# and 18# hi and low. We were able to get the cooler, charged with R12, to hold a stable 34 degF at cutoff, rising to 39 degF at which point the compressor would cut back on.

Guide to Other Types of Refrigerant Metering Devices besides TEVs: AEVs, Cap Tubes, Float Switches, Manually Adjustable Refrigerant Metering Valves

Capillary Tubes - a simpler method for metering refrigerant

Separately at CAPILLARY TUBES. we explain how capillary tubes are used to meter refrigerant in air conditioners, dehumidifiers, refrigerators, & freezers. We include a description of the operating properties of cap tubes, we contrast their use and function with thermostatic expansion valves or similar devices, and we include cap tube problem diagnostic tips for air conditioning service and repair purposes.

What's the Difference Between a Refrigerant Capillary Tube or "Cap Tube" and a Refrigerant Expansion Valve or TEV / AEV?

Thermostatic expansion valve © D Friedman at InspectApedia.com As we detail at CAPILLARY TUBES, compared with a capillary tube, the TEV or AEV adds a level of control - the TEV / AEV or even float valves and manually and adjustable refrigerant metering valves can open or shut in response to an attached bulb or pressure sensor (AEVs) which actually monitors temperatures in the refrigerant tubing.

Capillary tubes are found on residential refrigerators, dehumidifiers, and many window air conditioners. TEVs are found on larger air conditioners and central air conditioning systems where more control is needed.

In our TEV sketch (left) the small diameter tube at the top of the thermostatic expansion valve is connected to a temperature sensing bulb (not shown) that is located at the outlet end of the cooling or evaporating coil in the air handler.

The tubing at the left and right permit liquid refrigerant to flow into the valve from the compressor/condenser and, metered by the TEV, onwards into the evaporator coil. The large nut on the bottom of this TEV covers an adjustment screw that can change the latent heat settings and thus the behavior of the valve once it is installed. (Normally you should leave the valve at its factory setting.)

"Non-Adjustable" & Manually Adjustable Expansion Valves: How they are Set

Singer and other manufacturers point out that TEVs are adjusted at the factory before shipment. The factory setting of a thermostatic expansion valve is printed on a label found on the head of the valve and for most installations the factory superheat settings should be left alone.

How & When to set "Non-Adjustable" Thermostatic Expansion Valves

Non-adjustable TEVs (such as Singer TEV models 226, 326, 426) can actually be adjusted before the valve is installed, by turning an adjustment screw through the valve outlet opening. Once these valves have been installed, however, adjusting the valve would require removing it from the system, thus also requiring an evacuation and recharge of system refrigerant - not something to do casually.

How to Set Manually Adjustable Thermostatic Expansion Valves

Manually adjustable TEVs permit the device to be set to continuously maintain the proper refrigerant level entering the evaporator coil or cooling coil. Automatic expansion valves are discussed below.

Automatic Expansion Valves for Refrigerant Metering - AEVs

Automatic Expansion Valves for Refrigerants © D Friedman at InspectApedia.com Automatic expansion valves used to meter refrigerant into a cooling system are similar to Thermostatic Expansion Valves (discussed above) but AEVs do not use a temperature sensing device mounted on the cooling coil.

Rather the automatic expansion valve is mechanically set by adjusting a screw that presses a spring that presses a diaphragm that regulates refrigerant release by constant pressure.

[Click to enlarge any image]

Automatic Expansion Valve (AEVs) (center of sketch at left)

In normal operation the adjusting screw (see our sketch) is set to maintain a given pressure on the low side of the refrigeration system.

During system operation the Automatic Expansion Valve pulsates - it opens and closes constantly.

Diagnosing AEV trouble: AEVs can close up (stop working) if you add extra load to the refrigeration system - because of the extra heat load - the system will appear to run as if it were short-charged. So automatic valves are used on systems where the load is more consistent.

[Click any image to see an enlarged, detailed version]

Automatic Expansion Valves (AEVs) are repairable. These devices are most often used on constant-load refrigeration systems such as restaurant coolers.

Avoiding Trouble with Adjustable Expansion Valves

Watch out: on AEVs that have an accessible adjusting screw, it's important to keep the protective rubber cap on the device. The cap provides insulation to prevent the water produced during TEV defrost cycle from seeping into the bellows of the device where it can freeze and rupture the bellows.

Also review our advice on Adjusting the Thermostatic Expansion Valve - if you don't allow sufficient time for the system to stabilize after each turn of the TEV adjusting screw you can easily over adjust and lose control of the system.

Commercial Refrigeration Equipment Devices for Metering Refrigerant: Low Side & High Side Floats

On many commercial air conditioning and larger refrigeration systems you may see a large canister on top of the equipment (sketch at above) that acts as a refrigerant reservoir or receiver. Vapor exits at the top of the reservoir and liquid refrigerant enters lower in that canister, typically from a side port.

A float with a needle valve allows liquid refrigerant to enter the canister to replace refrigerant that has boiled off and exited out of the upper valve as a gas. Float type refrigerant metering systems are used on refrigeration systems in which the evaporator is the "flooded type" - always kept full of refrigerant down to the end of the coil.

Low-Side Float Refrigerant Metering Devices

Low side float refrigerant metering © D Friedman at InspectApedia.com

Low-side float refrigerant metering devices, installed on the low-pressure side of the refrigeration system, are used mostly on SO2 refrigerant systems.

A low-side float receiver will show up as a large canister atop a refrigerator that uses this type of refrigerant.

Inside the low side float refrigerant metering device a float combined with a needle valve permits liquid refrigerant to enter to replace refrigerant as it boils off and exits out of the upper exit valve - shown at the top left of my class-notes sketch.

Watch out: If arefrigeration system is using SO2, experts recommend that you do not attempt to repair this device.

[Click any image to see an enlarged, detailed version]

High-Side Float Refrigerant Metering Devices

High side float refrigerant metering © D Friedman at InspectApedia.com

A high side float refrigerant metering device is illustrated in our sketch.

As our drawing notes explain, the float is located on the HIGH side of the system. A high-side float-metered refrigerant system will show three different refrigerant pressures:

  1. Operating or release pressure between the high side float metering device and the inlet to the PRV
  2. Low side pressure on the PRV outlet side and between the PRV outlet and the compressor motor inlet.
  3. Compressor outlet pressure betrween the compressor outlet and the High Side Float Device Inlet.

A pressure-regulating valve prevents frosting at the receiver outlet (PRV in in the sketch at top center).

Frost will appear on the refrigerant tubing from the outlet side of the PRV (pressure regulating valve) onwards towards the compressor.

With proper refrigerant metering frost will disappear from the refrigerant tubing before the tubing enters the compressor motor.

Watch out: Like the low side float refrigerant metering device, a high-side float-type refrigerant control is not field-repairable.

Problems with Thermostatic Expansion Valves

Details are at TEV INSTALL & REPAIR - separate article. In addition the following articles will be helpful:

...


Continue reading at TEV INSTALL & REPAIR or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see CAPILLARY TUBES

Or see REVERSING VALVE on HEAT PUMPS

Or see REFRIGERANT PRESSURE READINGS & CHARTS - home

Suggested citation for this web page

THERMOSTATIC EXPANSION VALVES, REFRIGERANT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Questions & answers or comments about refrigeration controls: TEVs, AEVs, Capillary Tubes, Float Valves, & Other Refrigerant Controls

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman