Air conditioner or heat pump refrigerant problem diagnosis & repair procedures: types of HVAC refrigerant problems.
In addition to giving an index to our air conditioning or heat pump refrigerant problem diagnosis and repair articles, we explain what happens if the refrigerant charge in an A/C or heat pump system is leaking, under-charged, over-charged, or if the technician used the wrong type of refrigerant.
Understanding what's wrong with the refrigerant in the system can explain temperatures that are too low, too high, or it may explain refrigerant line and cooling / evaporator coil icing - too-cold, too-warm or too-weak air flow in the system.
This article forms part of our series on how to diagnose an air conditioner or heat pump that is not cooling: this article explains how to diagnose and correct air conditioning problems like lost or reduced air conditioner cooling capacity, reduced or no cool air flow, reduced or no actual lowering of the air temperature, or an air conditioner that won't start
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Refrigerant problems: Improper air conditioner refrigerant charge - too little, too much, too leaky: an air conditioner system which has lost some (but not most) of its refrigerant
will sometimes run too cold at the evaporator coil, leading to coil icing and loss of cool air delivery in the home.
If the filters are
clean and the coil ices-up this condition may be present. A service technician will need to evaluate and test the system and if needed,
adjust the refrigerant charge.
(May 9, 2015) Blaine said:
my heat pump is low on Freon...can I use a can of auto ac Freon to boost it up?
Blain:
No you should not use auto refrigerant to try to re-charge a leaky central air conditioning or heat pump system.
The proper repair is to first find and fix the leak. Trying to adjust the charge as you describe is improper, cannot provide the proper charge quantity as you don't know what's needed nor how much you've inserted, may use the wrong refrigerant type, and further risks introducing air or other contaminants into the system, and is not something you suggest.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2019-06-16 by (mod) - no refrigerant but system ran: damage?
Nevertheless there was a leak. It could have been a leak anywhere in the system or even a valve that was dirty in the valve seat or otherwise left open.
On 2019-06-15 by Anonymous
Our brand new air conditioner installed October 2018 never cooled when system was turned on 3 weeks ago and our home was vacant..
Technician said there was no refrigerant at all and he could find no leaks. He filled it with refrigerant.
What could have caused this if no leaks could be found.
Will the fact that it was running for weeks without refrigerant cause damage to the system.
On 2018-09-24 by (mod) -
Albert:
what leak? condensate or refrigerant?
If I assume you mean refrigerant, the lines could be damaged or leaking somewhere but most often the leak is at a connection.
Leaks occur at the cooling coil too but not so likely with a brand new unit.
Usually one can spot leaks by using a leak detector.
On 2018-09-20 by Albert
Just finished purchasing a new unit, I being experiencing problems with the unit leaking and not cooling. The company says I have a leack in the lines, they checked condencer and evaporator and the problem they say is on the lines. And that they need to replace lines. My question is could this be possible .
On 2018-08-01 by (mod) -
RE-posting without dis-allowed self-advertising link. However we welcome content suggestions & contributions or critique and are happy to cite and link to such contributors. - Ed.
Alex Stanford said:
Just adding refrigerant to the unit is not a real solution. It might feel right, but it isn’t. The amount of refrigerant in the unit must be very precise and exactly match the manufacturer’s specification. Understand that an undercharged installation is rare, and if your AC unit s low on refrigerant, a leak is most likely the problem and needs to be fixed immediately. You need to figure out why your AC is leaking and what you can do to fix it.
Thanks Alex,
We don't recommend that any homeowner try to add refrigerant themselves: there is virtually no chance that it will be done correctly and the risks add to the above that of damaging the equipment.
We agree completely that simply adding refrigerant without finding and fixing the refrigerant leak not only wastes money, it continues to contaminate the environment by releasing refrigerant to the atmosphere.
However I've also been disappointed to find that some techs scrimp on the re-charge, basing it only on temperature measurements and not on adding enough refrigerant to reach the full refrigerant charge quantity specified by the manufacturer. The result is an expensive service call that leaves the consumer feeling short-changed.
IMAGE LOST by older version of Comments code - now fixed. Please re-post the image if you can. Sorry. Mod.
On 2016-09-28 by (mod) - ac does not cool will the heat still work this winter.
Julian:
No and sort-of but not in a way you'll like. If the A/C doesn't cool then the heat pump won't heat either. A heat pump in heating mode is simply running its refrigerant in the opposite direction, moving heat in the opposite direction.
So when the heat pump is in HEAT mode and isn't producing heat, your system will either automagically or manually switch into BACKUP HEAT mode. That'll probably run electric heating elements in your air handler and give you heat, but at a higher cost.
On 2016-09-26 by Julian
I have a heat pump and the ac does not cool will the heat still work this winter. There appears to be a coolant leak. The fan works fine
On 2016-04-02 by (mod) -
stuck TEV ??
On 2016-04-02 by Shaunoffshoreair@Gmail.com
Did a startup. on Thursday Friday unit was making loud noise and showing 240 psi on both high and low side,what could cause this in less than 24hrs
On 2016-03-17 by (mod) - is an air conditioning refrigerant liquid or a gas?
James: depending on where the refrigerant is in the system it is a liquid OR a gas. The refrigerant changes state - or has its state changed by the compressor and the condensing coil from a gas to a liquid and in the evaporator coil where cooling takes place the refrigerant changes from a liquid to a gas.
Refrigerant systems in good working order are sealed systems, there is not refrigerant leakage. If refrigerant is leaking, say from corrosion or mechanical damage to refrigerant tubing or to one of the system coils, the system needs to be repaired: and you'll know it because the system will stop cooling.
On 2016-03-16 by james
is an air conditioning refrigerant liquid or a gas? are there any concerns with a leakage of a window ac unit?
...
Continue reading at A/C REFRIGERANT LEAK DETECTION or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
REFRIGERANT PROBLEM TYPES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.