Photograph of an air conditioning system data tag or sticker showing the manufacturer's specifications Air Conditioning & Heat Pump Data Tag FAQs
Questions & answers on de-coding HVAC data tags

HVAC data tag decoding questions & answers:

Frequently asked questions and answers on how to decode the information on air conditioner or heat pump data tags to read BTUS, cooling capacity, wiring and fusing requirements, refrigerant requirements and more.

This article series explains and translates all of the data found on information tags and stickers used on air conditioning and heat pump equipment. This article series answers most questions about air conditioning systems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Air conditioner & heat pump data tag de-coding FAQs

AC data tag (C) InspectApedia.com

Recently posted questions & answers about decoding air conditioner & heat pump data tags. These questions and replies were posted originally at DATA TAGS on AIR CONDITIONERS - how to decode data tag information.

On 2019-07-17 by (mod) - When the data tag is lost, damaged, not readable

Erika

Great question.

When the data tag is lost and we want to know the age on a heat pump we have a few options:

1. how old is the building - that sets a limit on the heat pump age

2. are there any service records for the unit? If there are just one or two service or installing companies where you live you can also give them a call to see if they installed the unit

3. is there an installation manual left with the unit - often there's an installation date written there

4. did anyone pen an install date inside the cover

5. Identify the brand, take photos, ask the manufacturer for a clue - e.g. there may be a serial number on the compressor motor or other major parts

On 2019-07-17 by Erika

My. Serial number is gone on my heat pump so now how do I no how old it is?

On 2019-06-02 by (mod) - If you can find the brand of your equipment on the data tag

If you can find the brand of your equipment on the data tag that combined with the serial number that you already have will allow you to look up the age decoder in this article series

On 2019-05-31 by Sheila

Age of unit? Model can 36-1 serial 28707197040..Addison..thank you

Wondering she of my unit ? Model qch 36-1 serial 28707197040..thank you

On 2016-07-16 by (mod) - Electrolux decodign information?

I can see why you're asking: going to a U.S. or Indian Electrolux website and looking at their "CONTACT ELECTROLUX" information leaves you with all of the contact details I show between the two dashed lines below:

------
------

That's right, Nothing. You might dig deeper and find a U.S. telephone number or you can fill in a question form at http://www.electroluxappliances.com/

The manufacture date is typcially coded into the serial number. I see that "97" at the end of the S/N that might be a year-clue.

As manufacturers do not enjoy following an industry-wide age encoding standard, each company may use different encoding in the serial number - we give some sources of decoder guides in the article above.

As I'm traveling and don't have my Carson Dunlop data tag decoder book in my backpack, I'm left having to guess.

More speculatively for Electrolux you could guess and decide if the guess is reasonable week 16 of 1997, and week 24 of 2007.

On 2016-07-16 by John Kay

I am tring to date my AC
Electrolux Indoor ESD24HRA S/N 64051697
Outdoor ESD24HRA S/N 64002407

On 2016-06-20 by (mod)

Jim

You'll see examples in the article AGE of AIR CONDITIONERS & HEAT PUMPS : the age is usually encoded or sometimes even given clearly in the serial number of the HVAC component. Check the data tag. You'll see that different manufacturers use differing systems such as

straightforward encoding: 1995010312345 1995 May 03 12345

encoding by serial day of the year such as YYYYnnn or just YYnnn

encoding by letter codes such as A=1995

On 2016-06-20 by jim

where can I find age, life expectancy, etc if I want to put in the model and serial number of hvac systems

On 2016-05-25 by (mod) York A/C unit model numbers are in this format:

York A/C unit model numbers are in this format:

XXX 12 C-3

XXX 12 C-3A

XXXX Y123ZZ

where the first two numeric digits are Mbtuh

or A1BC2345678

where
A = product type, e.g. E = heat pump outdoor unit

1 = generation number

BC = product identifier, e.g. UF = upflow flattop

234 = cooling capacity in BTUH or CFM, e.g. 012 = 12,000 BTUH, or D06 = 600 CFM direct drive

5 = refrigerant connection type, e.g. A = quick connect

67 = voltage if present, e.g. 06 = 208/230-1-60

The Carson Dunlop Technical Reference Guide we cite at AGE of AIR CONDITIONERS & HEAT PUMPS gives exact details for all of the encoding characters, but this will show you the usual model number formats

On 2016-05-25 by glenn

this is a York package heat pump with faded tag model number that can be seen is 026p06082bb.what is the correct model and serial number

only numbers showing on the faded tag model number is 026p06082bb trying to find the correct model and serial number

On 2016-02-03 by coldairresource

Typhoon air conditioning division of HUPP CORPORATION
Model# 207 LSU
Serial# 8L-106743
HELP

On 2016-02-03 by chad

Typhoon air conditioning division of HUPP CORPORATION
Model# 207 LSU
Serial# 8L-106743
HELP

On 2015-11-07 1 by (mod)

I don't know the brand.

On 2015-11-05 by Anonymous

Hello, could you please tell me how old my gas water heater is: MODEL # RP50-45FV ITEM # 910510408 SERIAL # 0106J14836. This was manufactured by Rheem Guardian System. Thank you.

On 2015-10-13 by GARY

TRYING TO ID AGE OF THIS HVAC SYSTEM...UNABLE TO DETERMINE THE MANUFACTURER...
SERIAL NO. IS GBF080404426
MODEL NO. IS GB5BM-T30K-B
THANK YOU.

On 2015-09-18 by Brandi

I forgot to add my name below. Also, I believe the unit is a frigidaire, but not sure.

On 2015-09-18 by Anonymous

I am trying to figure out how old this ac unit is: Model # CR22kFPFV230 Serial No. 00JM6718H and how much it is worth today if in fair condition.

On 2015-09-15 by Julia Dodge

I'm trying to locate a model/serial number for a condenser coil in my outdoor condensing unit in my mobile home. Manufacture date of mobile home is 1/29/2002. By looking at compressor number a fried suggested condenser coil may have been made by Comfortmaker. But not sure.

Have the compressor model/serial numbers by Copeland: Model: CR38K6-PFV-130; Serial: 02J03603H. The Fan model is by Emerson: K48HXFCM-3726. Also have a torn label for outdoor ambient temperature reading with a style number: NAC042.

The other label deals with electrical connection and is partially hidden and cannot see. I would appreciate the help if you can find out. thank you.

On 2015-08-06 by (mod) Goodman Air Conditioning contact information

Sure, Anon, your best bet to get exactly the correct data is to give Goodman Air Conditioning a call directly.

From within the United States and Canada, you can contact Goodman at 1-877-254-4729
By Mail to
Goodman Air Conditioning and Heating
7401 Security Way Houston, TX 77040

On 2015-08-06 by Anonymous

our office has a Goodman ARUF46016BA unit. I'm not at the location and need to know the factory charge capacity is so I can determine what the max pounds of R-22 is. Can anyone help me? Jill D.

On 2015-08-01 by Edrees

we have air condition that both in indoor and outdoor unit its written the power is 1300W! what is the difference is the indoor unit also consume too big power ?

On 2015-06-25 by Jean

I'm trying to determine the age of my a/c unit. The serial # is 1601F26891. Can you help with this/

Question:

(Jan 24, 2014) Jill Holstein said:
HOW CAN I GET ONE OF THESE ? Carson Dunlop provides a manual that decodes more of that data so that you can know the age of the compressor or air handler. That is, the date of its manufacture,

Reply:

Jill contact information for Carson Dunlop Associates data tag decoding book is given in the article AGE of AIR CONDITIONERS & HEAT PUMPS as well as at the Citations at the end of this article.

Click the "Click to Show or Hide Citations and References" at the end of this article.

Scroll down to the second major bullet where we describe "Carson Dunlop Weldon & Associates'Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment
" - the company's contact and sales information is there as a hyperlink, and they have generously provided a code (capital letters, bold face) that will get you a small discount on the price of that manual.

Question: various data tag decoding numbers that can be found in the references cited in the article above

(Aug 13, 2014) bill english said:
I am trying to determine the nominal capacity of an old Inter City air conditioner. The model number is CA5536UKC1.

(Sept 15, 2014) Kevin said:
Looking for the age of a Sanyo Model # CL2412 Serial # 0036604 ?

(Oct 12, 2014) Carol said:
Looking for size of singer AC model ACR50029

(Nov 25, 2014) David said:
Looking for the age of a Versatec Heat Pump model# 036A100NMT1SSA - serial # UH2316 and VXV030A100NMT1SSA -serial #UF1199. Any help would be much appreciated!

(Apr 2, 2015) Anonymous said:
Looking for ton size of Trane XE 1100 Model TTN036C100B3

Reply:

Sorry but we can't answer all data tag look-up requests. Please try the web articles and references listed in AGE of AIR CONDITIONERS & HEAT PUMPS

On 2013-01-16 by allan

it is true that units capacity is calculate by compressor LRA Compressor? which we received model number # SM125S4CA, LRA-120 requested existing Compressor model # SM125S4CC, LRA-260. can it be used even LRA are different but BTU are the same?

On 2012-12-18 by connie

My Data Plate is Gone how do I obtain one for a county inspection

On 2012-09-28 0 by (mod) -

Rocky,

Sorry, no, refrigerant capacities are not in the guide. It is used for product identification to year etc. Some model codes indicate refrigerant type but not the charge quantity - that is installation dependent, for example because piping length and thus charge volume will vary from job to job.

On 2012-09-18 by Rocky Germani

I am interested in knowing if the Carson Dunlop Technical Reference Guide covers Commercial Carrier AHU's RTU's and FCU's.

Also does it include refrigerant type and capacities for each unit. If not is there a site that does have the information. I am working for a college and am in need of this type of information if available. I am also interested in report writing.

On 2012-07-20 by (mod) -

KeviP

Normally we'd look up the Magic Chef model number decode for your unit in our copy of Carson Dunlop's Technical Reference Guide (listed in the references section at the end of this article) but I'm working on assignment out of office for a time. You can

- contact Magic Chef and ask them directly
- pick up a copy of Carson Dunlop's Technical Reference Guide (recommended)
- pick up a copy of Preston's HVAC decoding guide (absurdly expensive, more details)

Typically on older Magic Chef AC equipment the year and place of manufacture are in the end of the serial number; the BTUH capacity is in the model number but may be encoded.

On 2012-07-19 by KeviP

trying to find out size of AC from lable off coil Magic Chef MODEL YA583T-2 COIL NUMBER AT582-2 SERIAL NUMBER A 07212KCC

On 2012-06-01 by (mod) -

Andy, the compressor type may be coded in the model number for some manufacturers. If you pass on that data to me, better yet, with a sharp focus photo of the data tag(s) I'll see what I can find.

On 2012-05-08 by Andy Tran

Hi Dan. Great Info. Do you know if there is way to determine whether the compressor is a 2 stage or 1 stage unit based on looking at the data plate? Thanks a lot, Andy - Carson Dunlop.

On 2011-09-20 by Mike

What is the calculation for the additional charge of R410A for a sanyo SPWUR484GXH56 outdoor unit with pipe runs as follows:1" - 56M/0.375" - 31M and 0.25" - 9M

On 2011-09-01 by (mod) -

John that's an interesting question. The LRA is the current drawn just for a moment at startup; But if your generator cannot handle that brief surge the A/C may simply fail to start.

On 2011-08-31 by john

Do I need to consider the full LRA when choosing a generator for back up power?

On 2011-08-04 by georgec5370@gmail.com

love this site lots of helpful information. thanks for putting it up.


...

Continue reading at DATA TAGS on AIR CONDITIONERS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

DATA TAGS on AIR CONDITIONERS FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...