Air Conditioning Troubleshooting & Diagnosis FAQs (list of frequently asked questions about air conditioners)
These questions & answers about fixing problems with air conditioners & heat pumps were posted originally on the air conditioning & heat pump home page.
Typical air conditioner concerns include compressor or blower assembly noises, failure of air conditioners to start or to keep running, inadequate cool air flow or air quantity, loss of air conditioner cooling capacity, reduced air conditioning output temperatures, loss of cool air supply, or even loss of air flow entirely.
Also discussed are various electrical wiring, fusing, overcurrent, and thermostat or control defects on air conditioners.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions & answers about diagnosing trouble with air conditioners and head pumps were originally posted at AIR CONDITIONING & HEAT PUMP SYSTEMS
A good place to look for diagnostic procedures is DIAGNOSTIC GUIDE A/C or HEAT PUMP.
Also see this series of A/C & Heat Pump Diagnostic FAQs sorted by major topic area are given at AIR CONDITIONING & HEAT PUMP SYSTEM FAQs
On 2017-07-27 (mod) said: no air flow and icy coil in new AC system from Sears
Sounds like an ice-blocked coil, perhaps from low refrigerant, improper charge or a refrigerant leak or an improperly-set thermostatic expansion valve . Call your service company for repair and let me know what you're told. Read more by using the search box above to find our article on COOLING COIL ICE BLOCKAGE.
On 2017-07-27 by Vin
I bought a new AC system from Sears bout no air flowing and ice formed on com pressure and copper tubing on Atic coil?
On 2017-07-26 by Robin Macera
I have what I believe to be a 1965 International Oil Burner Company heating and cooling unit. Heat quit working this past winter and cooling system comes on but isn't cooling.
On 2017-07-18 by Eric
The question i have is the condensate line for my a.c.is ran directly into my shower where it is coming out of a p.v.c.pipe about ten to twelve inches off the floor of my walk -in shower is this a proper disposal location i notice that the front of my shower is always slimy and discolored and i have been having problems with my feet peeling that i never had before.thank you for any help you can provide in this question
On 2017-07-13 by (mod) Goodman hp 410 suction 200 lbs head 300 suction line slightly cool comp noisey
Seems like rather low pressure on the high side; is refrigerant lost or is the compressor not working?
On 2017-07-13 by mike
Goodman hp 410 suction 200 lbs head 300 suction line slightly cool comp noisey
On 2017-07-09 by (mod)
Susan
If the outside (compressor/condenser) fan never shuts off AND your thermostat is continuing to call for cooling and the compressor is running, then the condition is normal and should be OK.
If your thermostat is set to above room temperature, so that it stops calling for cooling, and still the outside unit or its fan never shuts off (say for hours) then a control, relay, or wiring is damaged and needs repair. In that case I'd turn off the system.
About your "prompt reply" demand, please try to find patience: we have over 200 million readers in 50 countries, so sometimes it's a bit difficult to give an immediate answer to every question. Apologies, we'll continue to try to be as responsive as possible. In a life-threatening or other dire emergency readers are also welcome to try contacting the editors directly using our page top or bottom CONTACT link.
On 2017-07-09 by Susan
Will it hurt if my outside unit fan won't shut off? Inside unit is working fine. Do I need to shut it all off until repair man comes in two days?
On 2017-07-05 by (mod) When I turn on my A.C. my heat comes on the furnace
Rachel,
First let's be sure that all of your thermostat switches are properly set. For example be sure the thermostat is switched to cooling mode.
Then if when you lower the temperature on your thermostat the heat runs instead of the air conditioning, then commom causes include
The thermostat is defective
the thermostat wiring is shorted, or it is miswired.
A control board or relay for the air conditioning system could be defective
On 2017-07-05 by Rechel
When I turn on my A.C. my heat comes on the furnace and all any suggestions?
On 2017-06-27 by Robert
Morning Dan,
So I got new condensor fan engine but this upgrade has four (plus ground) wires so the store which sold me it said I need additional capacitor.
I have absolutely no clue how to instal it, but after looking on the internet it seems that heaving two capacitors is not a great idea.
Is there something that could help me?
Thank you!
On 2017-06-26 by Duane Smith
Thanks for getting back to me. I know I have a confusing problem and do agree that we are not going to spend a lot on this 10 year old R22 system.
On 2017-06-26 by (mod) 10 year old 3 ton heat pump in Arizona not cooling adequately
Duane,
Climate change and very hot temperatures in AZ indeed are showing up in many areas from cancelled air flights to failures in older or marginal air conditioning systems.
You offer a good and also frustrating example of a shotgun approach to HVAC system repairs.
I am reluctant, with even less information than they had, to second guess the service tech's.
I would call the repair company, speak with the service manager, explain that you are getting rather inconsistent diagnosis and repair advice, then ask for help from their most experienced senior repair tech.
In my opinion I would be reluctant to order a very costly repair on a now obsolete R22 based system.
On 2017-06-26 by Duane Smith
I don't know if you can help me. I have a 10 year old 3 ton heat pump in Arizona.
Last spring, before the hot weather came, we had the spring checkup done and the tech came off the roof and said we needed a new capacitor and fan motor to the tune of $900.
We told him to go ahead and a month later when it got time to run the AC, it would not work. The company sent out another tech and he said the capacitor was bad and exchanged it.
The unit then ran fine until we got the record heat of 118 a few days ago and the unit quit putting out cool air and the inside temps rose 5 degrees or more until evening when the unit started cooling.
We called the company again and the tech came and said we needed a new metering valve to the tune of $2500. He took the bulb sensor off the suction line and said that would make the unit let max Freon through all the time and it would work until we decided to have the valve replaced or get a new unit.
After that, we got a second opinion and this tech said removing the bulb sensor would not make any difference and he put it back in place.
He said the compressor amps seemed low when it was running and with the high ambient temperature, it should be running about max amps.
The compressor was getting very hot and that is why it was shutting down. He said it indicates the compressor is wearing out and not operating efficiently anymore. We are setting the thermostat to 75 to cool the house down from 5 PM until noon the next day, which lets the compressor rest during the highest temps of the day and then back to 80 at noon until 5 PM.
That has been working well and the temperature inside will pretty much hold until 5 when we turn it back to 75.
I know this may not be enough information for you to give me any advice but maybe you can possibly tell me which tech is on the right track. I think the first one was just trying to make a big sale because of the high price of replacing the metering valve. By the way, this is an R-22 unit.
Thanks, Smitty
On 2017-06-22 by (mod) enclosed the compressor/condenser of a walk-in refrigerator
I would check with the equipment manufacturer, but it seems likely to meet up the duct system with you describe is going to be undersized and we'll both reduce the effectiveness of the cooling system and shorten it's life
On 2017-06-22 by Richard U
I have a walk in refrigerator with a condenser compressor unit on the top, the ceiling was cut out to accommodate the condenser compressor placing it in the attic. The attic has now been renovated into living space and the heat from the condenser compressor on a warm day is unbearable.
So I enclosed the condenser compressor and ran a 10'x6" insulated duct from a shroud over the intake end of the condenser coil to the exterior to supply fresh air, I also ran a 16'x6" duct from the top of the enclosure to the exterior for exhausting the heat.
There is a fan behind the condenser coil that pulls air thru the condenser and blows on the compressor only for the length of time the refrigerator calls for cooling.
The shroud is not a tight fit over the front of the condenser about a 1" gap around the edges. I thank that I need a 6"duct booster fan on the intake duct to ensure adequate air flow and direction over the condenser coil to be controlled by a temperature sensor with contacts to control the booster fans on off time and to turn it on if residual heat builds up in the enclosure, also in the winter "Northern Wisconsin" to prevent it from getting to cold.
I don't want to reduce the efficiency by allowing the equipment enclosure to get to cold in winter or to hot in summer and create a damaging environment. I have not found information on the temperature range necessary to accomplish this.
I could use some advice on this situation,
Thank You
On 2017-06-16 15:18:10.942664 by Robert
Dan,
I have changed the capacitor, but it did not fix the situation. Now I guess it is time to change the fan motor.
Before I do this could you please look into the video. I would like to get your go ahead before I embark on the motor swapping.
Thank you very much
On 2017-06-13 by Anonymous
Dan, thank you. we will look itno your advice. My husband said that it's more like a whistling sound.
On 2017-06-13 by (mod)
Rose
I don't quite understand the situation but I think you're hearing a duct noise that you didn't hear during the last cooling season. I'd inspect the full run of the duct system for crushed, collapsed or damaged ductwork.
Start at the air handler and be sure that the air filter is in place and undamaged. (We don't want to draw an air filter into the blower as that could cause a fire)
On 2017-06-13 by Rose
my home central air conditioning system, turned on after a long winter, now makes a sound from the vents as if the vents are closed and the air is trying to push out. the vents are all open. it is a whooshing sound. thank you.
On 2017-06-11 by Phil
Hi, My AC comes on normally and runs between 15 and 30 mins. Then my compressor makes a weird noise and everything loses power without tripping the breaker. The display goes off and the compressor will not turn on. After about an hour everything comes back on and the cycle continues. Please help me.
On 2017-06-11 by Anonymous
Thank you , I will do what you suggested.
Yes. I am sure compressor works (because it cools), I tried the AC Unit today and it was cooling for 20 minutes.
Since fan works fine for first 150-20 minutes I dont think it is blade or obstruction.
I am lucky because I have two floor house so I have another unit that cool upstairs, and I am using this one currently.
I will keep you posted after I change the start up capacitor..
Again, thank you!
Robert
On 2017-06-07 by (mod)
Robert
Sorry I missed it, please send me the video link by email found at our page bottom contact link.
Once an air conditioning system has shut down in most systems the pressure equalizes across the high and low sides.
If you're sure it's the fan not the compressor,
1. leave the equipment off to avoid further damage and unsafe conditions
2. Look for a loose fan blade on the shaft, an obstruction hitting the fan
3. Look for or just replace the fan motor start-run capacitor - search InspectAPedia for MOTOR START CAPACITOR for details.
On 2017-06-05 by Robert
Outside unit starts fine. After few minutes of work fan start making terrible noise, fan slows, speed up again ,and then completely stops. Condenser still works.
What would you make out of it? Thank you!
On 2017-06-04 by Mike
Split unit is just blowing hot air
On 2017-06-02 by satyamthetrue
Ok.
1. Is it possible for TEV to remain open for few minutes after units are shut down.
2. It's been more than 10 days since i encountered the problem and still there is no problem with the cooling.
If possible check my video.
On 2017-06-01 by (mod)
Satya.
Because the thermostatic expansion valve on an air conditioning or heat pump system opens and closes in Cycles, it is not quite correct to assume that bubbles in the system will be heard continuously.
On 2017-06-01 by satyamthetrue
If it were a leakage the sound would come continuously but it is not so.Sound comes at certain interval,continues for around 2 to 3 min then stops and if units are turned off during that sound is live then it(sound)continues for few min but if turned off when no sound then everything happens in a normal way.
You would understand it in a better way by watching the video..Link already provided.
Thanks
On 2017-06-01 by (mod)
re-posting without link - for security
Satya
It's possible that you are hearing gas bubbles in the refrigerant line - an indicator that there is a leak in the system.
On 2017-05-13 by (mod)
With the warning that I'm speculating beyond my expertise comma I'm considering your thoughts that the thermostat is defective.
It's generally easy enough to rule out both the thermostat and the thermostat wires as being a problem Source. Simply go to the other end of the thermostat wires, recognizing that for call for heat or call for cooling the thermostat is basically operating as an on-off switch.
So you want to be able to remove the thermostat wires and connect the two thermostat terminals for heating or Cooling.
Since you're not getting Cooling if you jump the cooling terminals I would expect the compressor condenser to run outside as a heat pump in cooling mode as long as the outdoor temperature is not too low.
On 2017-05-13 by Jim Brooks
I don't think the contactor is bad as it operates when I request heat. Just not when cooling is selected.
Do you know how the furnace and heat pump are cotrolled for cooling.
I guess operating the fan control turns the furnace blower on and whether or not the heat output is activated determines whether the furnace make heat or not.
My suspicion is the thermostat is bad given the fact from what I understand the thermistor/outside air temp sensor controls whether the heat pump comes on.
It's weird that the cool indicator is flashing indicating the thermostat is calling for cooling but neither the heat pump nor the furnace fan come on.
This is why I think it's the thermostat.
I bought a honeywell control but it does not have a sensor input.
On 2017-05-13 by (mod)
Jim I can but guess from the position of great distance and not much information, but to me this sounds like a bad control board or contactor.
On 2017-05-13 by Jim Brooks
I have a carrier heat pump/aux heat system . Recently it has stopped cooling.
It will heat and the pump comes on.
When cooling is selected at thermostat, I hear a click in the thermostat and the revering valve is operated outside
The internal fan does not come on and the heat pump does not start.
If I operate the contacter on the heat pump, the heat pump starts.
The system has an outside air temp sensor that connects to the thermostat.
Previously, the thermostat reported an OAT sensor fault.
I checked at the sensor and get about 3.7V with ambient about 10C.
I also measures the sensor resistance when disconnected. About 15K and going down when you hold it.
I measures the voltage at the sensor pin from the thermostat with sensor disconnected and read +5V.
Any thoughts suggestions?
THanks.
On 2017-05-01 by Michael Riley
I have a Fedders A/C unit on my coop roof and an air handler in the apt. Lately when the A/c comes on there is a loud clanging noise about 10 secs after that in the refrigerant line that comes into the apt that lasts about 5 secs. The unit cools fine. Should I be concerned?
On 2017-04-28 by (mod)
We're in heat mode, right? Are you running in backup heat? If so the compressor/condenser would probably stop.
When no air is delivered then the air handler or its controls are not working properly in that I'd not expect it to shut off before the thermostat set temperature is reached UNLESS the air handler's heat exchanger in backup mode is overheating.
On 2017-04-28 by steve
i have a carrier heat/ac unit o o ntop of my house and the heater works fine, but it shuts off before the temperature is reached and I can hear the heat pump still working , but, no air is coming out or heat ..,
i usally pull the fuse on the unit and this fixes it temporarily, could it be the ignighter that or a photo scenser thats not cleaned off.
need a professnal opinion thank you steve in redding ca
On 2017-04-27 by Brian
@Mike, It sounds like the contactor has the contacts stuck closed. This is a common problem.
On 2017-04-26 by (mod)
Mike
Check out the diagnostic and repair advice at FAN WONT STOP - LIMIT SWITCH - inspectapedia.com/heat/Furnace_Fan_Wont_Stop.php
it could be a bad fan control or even just shorted thermostat wires
On 2017-04-26 by Mike
The fan on my AC unit won't cut off. The blower fan cuts on and off as you would expect with the thermostat, and it is cooling the house fine.
When I looked at the unit yesterday, the refrigerant line and the compressor were covered in ice. I shut everything off and let it melt off, but when I turned it back on today, the unit can still won't turn off. I can't find my information online on this particular problem, so I don't even know wheee to look.
On 2017-04-26 by (mod) Trane single packaged 3 ton heat pump fan randomly cycles on and off
KR
I would look for
- a loose wire at the thermostat or between thermostat and the air handler
- a failing fan control or switch
- a fan whose wiring, control relay, or start/run capacitor is failing
BUt the fact that the fan behaves badly only in OFF suggests the first of these: a loose or shorting wire, or perhaps a bad thermostat
On 2017-04-26 by Krjune
Any ideas why fan behaves this way. Have a Trane single packaged 3 ton heat pump that when the heat/cool switch set to off, the fan randomly cycles on and off.
If the switch is set to either heat or cool, the fan turns on and off with the cycles properly. Fan switch is set to Auto.
On 2017-04-12 by (mod) fence around my outdoor HVAC air unit
BJ
I certainly doubt that the ONLY air circulation path at your compressor/condenser unit is "from the top" - air has to move IN, across the condensing coil and OUT.
Blocking either inlet or outlet will increase cooling costs and reduce the life of the compressor/condenser unit.
On 2017-04-09 by BJ
I am replacing the fence around my outdoor HVAC air unit. It gets circulation from the top. I want to build the fence with a 12" clearance on just one side, more clearance on the other sides. Is this an acceptable installation for zip 34231, Sarasota County, Florida?
On 2017-03-11 by (mod)
I took a look at (and downloaded to examine) your photo - I see what looks like light corrosion on copper refrigerant tubing and rust on the galvanized metal frame that holds the cooling coil.
It would be no surprise that there would be more corrosion lower on the coil - as in the photo - as more condensate will tend to accumulate lower on any sloped coil;
These diagnostic questions occur to me, and others might be raised by other HVAC service techs
1. most important, and not easily seen, is there corrosion, damage, or blocking to the cooling fins in the cooling coil body: depending on the severity, including more severe than what I see in your photo, that may mean end of life of the cooling coil and on a 20 year old system, possible system replacement as I noted earlier. With a light and inspection mirror it may be possible to get a look at the coil condition through the small triangular openings at the ends of the A-coil frame.
2. if during system operation we can see ice or frost forming on the coil sufficient to block air flow then I suspect low refrigerant, and thus a refrigerant leak that needs attention; again depending on leak severity and where it is occurring, that could also precipitate a more costly air handler and possibly compressor/condenser unit replacement.
3. Stains on the cleaning instructions label on the condensate collection tray suggest that there may have been tray overflow in the past; A service tech would check that the condensate drain is not blocked and that condensate leaks have not damaged the heat exchanger of the furnace presumed to be below the cooling coil in the photo - as serious rust or damage to a heat exchanger may make the furnace unsafe.
The replacement question arises because while it makes sense to do inexpensive repairs to keep using equipment as long as feasible, at some point we don't want to start throwing much good money after bad.
(with your permission I'll find a place to post the image and this discussion, so you might use our CONTACT link to contact me by email).
On 2017-03-11 by (mod) corrosion around the ends of the evaporator coils
re-posting
info said:
It was on the copper tubing. There is a photo at this link
On 2017-03-10 by (mod)
Interesting question, Jonathan, perhaps other readers will comment. Was the corrosion on fins or on the tubing? Was the tubing copper or aluminum?
Indeed a badly corroded coil may precipitate a complete AHU system replacement since replacing the coil alone on a 20 y.0. sysetm that is using an obsolete refrigerant may not make economic sense. It'd make sense to issue that near-end-of-life warning.
On 2017-03-10 by Jonathan Quigley
I recently performed an inspection of a forced air furnace with heat pump. I noted corrosion around the ends of the evaporator coils, most notably near where the condensate is collected. Is there a common diagnosis for this condition? The unit is about 20 years old
On 2017-01-28 by Bill
Daryl it sounds like you have a stuck relay.
On 2017-01-28 by Bill heat strip relays short out and it blew the Air handler board
Heat pump question. I had heat strip relays short out and it blew the Air handler board. I replaced the board and relays and now the heat pump works and blows warm air but I get no 24v at the heat strip relays. (When I checked I was getting 2.5 volts). What could be the problem keeping the board from turning on the heat strips?
On 2017-01-24 by Daryl
Any ideas where to START LOOKING ?
2 weeks ago it was 70% outside, front door was open and windows too, my furnace came on (set at 35%) and heat would not shut off.
On 2017-01-24 by Daryl
my electrical furnace of a 1999 Fleetwood double wide will not shut off by thermostat, only by shutting off main circuit breaker. Replaced new thermostat and still will not go off. thermostat is not hooked up and just turned breaker back on and furnace came on and still running, is it a short in wiring ? can't have furnace running all the time !!
On 2017-01-21 by (mod)
Sorry Anonymous, and Sorry Mukesh Punia,
our security won't permit posting of advertising links in comments, even though certainly we know that people in South Delhi need electrical and air conditioning repairs. You can, however contribute technical content, critique, reviews of the material you find at InspectApdeia.com and that enables us to cite and link to technical contributors/reviewers. - Editor - See more at: https://inspectapedia.com/aircond/Air-Conditioning.php#FAQ
On 2017-01-18 by Bobby
My frigitare ac/heater compressure keeps running when I power down the unit . To get it to stop is to use the breaker switch on the head of the cord! Any ideas?
On 2016-12-2 by (mod) remote control reads 17 degrees celsius while the indoor unit is reading 24 degree celsius
Perhaps the remote is in a different location than the wall unit.
On 2016-12-19 by Solomon
an air conditioner remote control reads 17 degrees celsius while the indoor unit is reading 24 degree celsius instead of the 17 degree celsius set on the remote. What could be the cause?
(Feb 1, 2015) Avery said:
You've got everything covered except the price? How much does it cost?
Avery,
I'm not sure what "it" is in your question. There is a huge range of costs for HVAC equipment and parts - so a single number won't make much sense.
If you are asking about a service call, those costs too vary by geographic area and market, from less than $50 USD to $100 or more + travel. There is also quite a range of markups that service companies apply to products that are used for repair or replacement.
What we might do is check the purchase price of specific parts used in a repair, but then too we need to consider how the HVAC service company prices their service business.
(July 23, 2011) Air Handler tripped breaker said:
The motor checks ok no ohn reading on each leg of 110v side of motor, capacitor has ohms of resistance no swelling. Either the mother board or the relay.
With power off, check first for shorted electrical wiring, next for a seizing motor or a motor with a bad start capacitor.
(July 29, 2011) Charles Gullette said:
I recently had a new 3 ton 13 seer unit installed. It included a new compressor, condenser, and cooling coils and digital non programable thermostat. The existing 3 ton blower and heater unit were reused.
After installation the blower unit starts, runs about 15 sec and then restarts. there is no effect on the compressor unit. My tech. says the blower is starting on the heater relay and then shifting to the cooling relay on the blower control board. He claims this is not a problem but that the board may need changed in the future. I did not have this problem prior to the new unit installation. Could it be the thermostat wiring or is my control board going bad??
Charles, I wonder if the new thermostat was wired exactly the same as the old one? And I agree that the circuit board could otherwise be the problem. I also agree that it's curious to have to change a circuit board after other components were swapped out unless either there is a compatibility issue (sounds wrong) or an accidental short circuit, or some mechanical disturbance that just pushed a failing component over its edge.
(Aug 27, 2011) AC making "revving up" sounds ev said:
When my AC (Trane) is running is sounds like someone is revving an engine every few minutes. The indoor part of the system is in the attic and when the "revving" noise happens the sound below, in the house, is like a "Blue Northern" strong wind.
Any thoughts? Thank you! NF
AC making revving up sounds
Please see
I'm not sure about revving up - perhaps a cycling of a motor trying to start? or a loose fan blade hitting something? AC making revving up sounds
(Jan 2, 2012) george said:
Hi new goodman h/p getting 0 psi on high side? help
sounds as if the compressor motor is not working at all
(Mar 24, 2013) james said:
i put t-stat in cool 24 volt transformer blew what caused this
James
Perhaps a short circuit in the thermostat wiring
janie said:
my air condition is leaking water out of it
Janie,
Look for a condensate drain clog or pan leak.
For diagnostic help see BLOWER LEAKS, RUST & MOLD
12/12/12 janie said:
my air condition is leaking water out of it
Janie,
Look for a condensate drain clog or pan leak.
See
inspectapedia.com/aircond/Air_Handler_Leaks.php
(July 11, 2014) Dave in Toronto said:
Singer incremental under window electric unit.
Compressor over heated and has seized. Tried Super Capacitor with no effect.
Replaced compressor. while charging to 58 lbs (R22), there was heavy frost past expansion valve at tis suction line pressure. No sweating of suction line. Compressor overheating. Changed filter/dryer installed a few years earlier. Retested. No change. Resting pressure was 250 psi. Changed expansion valve for new one. Much less frosting, but still evident at 58 lbs pressure after recharging. Now has new compressor, filter/dryer and expansion valve. No other components to change other than C coil. What's going on?
Dave, contamination may be fouling the TEV causing it to open or close erratically.
(July 12, 2014) Anonymous said:
My central air will go on than turn off in about an hour without cooling house down to set temp. There's a new motor, fan and pump.
Liz V
Liz
Try the diagnostic procedures at
(July 19, 2014) Anonymous said:
question:jus changed the circuit board in my system...everything seems to be ok
except tht im not getting temperature control...checked room temp. using 2 different
thermocouples from digital meters...room temp stabilises at 20 degrees..upping set
temp.to 28 degrees and compressor keep
s running...temp.records at 20degrees on both meters..possible problem...can it be the evaporator sensor?
Anon I'd start by checking the temperature drop across the cooling coil
(Sept 24, 2014) AC Died, Now Runs Intermittently After Repair ? said
AC died in the middle of this horrendous hot spell. Ended up changing the compressor/fan capacitor and the contactor circuit board. Unit fired immediately when turned on and was putting out cold air. Unfortunately it will run for a couple of minutes then it shut down and will not restart until it sits for awhile. Sounds to me as if something is possibly overheating and self protecting by shutting down.
From just your note, AC, I can't make a useful guess. It's time to call a trained HVAC technician. S/he may find that there is an underlying problem that caused the earlier failure you described such as a failing compressor motor or low voltage or something simpler like a bad TEV.
(Oct 7, 2014) Joe Rouse said:
I have a Whirlpool Room Air Conditioner model WS092LW. Even if Whirpool no longer sells this model, where can I get info on the unit? Mine is moaning and ciculating HOT air! Suspect it's in need of coolant, but open to insight on this.
Joe, your AC unit may have indeed lost refrigerant. Don't just add more without also finding and fixing the leak.
12/4/2014 Anonymous said:
when I turn on my ac instead of cooling the heat comes on. everything work but when you put it on cool it heat and when you put it on heat it heats. is it my thermostat inside or something in the heat pump outside?
Anon if you are sure your thermostat switches are correctly set then I suspect a wiring error or a control board failure.
(Aug 7, 2014) tommy said:
the outside the fan motor stopped working after over heating so after putting in a new fan motor and capasitor i still have the same problem motor overheats then turns off repairman can't understand why this did not solve the problem
Tommy
Check for low voltage, a control board or relay failure, or a wiring mistake.
Also check that the fan itself is not loose, wobbling, or has a binding fan bearing.
Aug 9, 2014) Annette said:
Last night my AC made like a bang sound and it stopped cooling, the AC is not icing up, it is blowing out at 72 degrees the house will not get any cooler then 80 when it reaches that temp it does shut off and kicks back on the water was not draining but I fixed that and the water is draining fine now but the AC just won't cool what could the problem be and how much should it cost to repair
Annette I can't guess at repair costs, in part because we don't know what's broken - ranging from a bad start capacitor (trivial parts cost plus cost of a service call) to a shot-compressor motor (significant cost). I'd give your service company a call. Let us know what you're told. Daniel
(Aug 12, 2014) Air Conditioning Repair Service San Diego said:
Thanks for sharing this informative blog on how to repair a broken air conditioner. This would help a lot.x
AC there are articles in this series that describe repair processes, basically beginning with accurate problem diagnosis. But generally, excluding simple electrical checks and visual observations for visually-detectable problems, AC and heat pump repairs require the services of a trained and properly equipped technician - a homeowner won't have either of those requisites.
Please see WINDOW / WALL AIR CONDITIONERS
(Aug 20, 2014) Anonymous said:
We have 32 condos in my building with a cooling tower outside , whenever the cooling tower shuts off due to electrical storms or service that requires tower to be shut down my Florida heat pumps shuts off and will not start again unless we do it manually . Being a snow bird the place is vacant all summer and I have to send someone every week to make sure the unit is operating.The unit is 3 yrs old and works well
(Sept 6, 2014) Nick Stull said:
Our townhome furnace/AC (gas heat, electric cooling) is not working properly, and the landlord has sent people out at least once to check this, and nothing is fixed. We turn it on, it kicks on and the outside fan and inside blower seem to be working properly. A couple of hours later, the unit will have cooled our place a total of a couple degrees (from 78 to 76 in one run), before it stops cooling. After that, the temperature in our place gets stuck, and the airflow in the downstairs vents slows to basically non-existent, and we have absolutely no airflow in the upstairs vents. Any advice on what I could tell them to check for? And while it is a complete waste of money, is there any harm in me keeping the A/C on so they actually experience the problem, or will this aid at all in diagnosing the issue?
(Sept 9, 2014) Anonymous said:
A/C is not cooling...Compressor is running...pressures are all reading good...inside coil is clean but not getting cold...low side Freon line is not getting cold or sweating...high side line is warm...any idea what the cause is..??
Look for a refrigerant leak, low refrigerant, ice-clogged cooling coil
(Sept 7, 2014) Nick Stull said:
Additional information, which may or may not narrow down the problem: After leaving it off for a while (hoping it would start working after giving it a break), we can hear (intermittently) water dripping down the drain pipe, at times a somewhat significant amount. But even if it was ice clogging the cooling coil, that would only indicate another set of issues it could be, among which would be either low or leaking refrigerant, right?
Reply:
Nick
Your note further suggests ice-blocked cooling coil troubles.
(Sept 9, 2014) Anonymous said:
I have had a brand new 4 ton heat pump 15 seer unit installed. I had a 4 ton 12 seer 20 year old unit removed. My new unit is costing more per month than the old unit. had a new thermal expansion value installed ,did not solve problem . they want to put a solvent in value cuzz they think a rust inhibitor is causing value to not work proper. Am going on 4 months can't afford electric bill.Should I go with another unit or try the solvent
Start by getting an accurate diagnosis of the trouble: the behaviour of the cooling system, its ability to bring the house down to the set temperature, and don't forget to check for any and all problems that could be interfering with its operation. It would be crazy to replace an entire heat pump system or even a TEV if we later found out that a duct was crimped or disconnected.
(Sept 21, 2014) Anonymous said:
the air conditioning run well in winter mod but not in sumar
in sumar mod the compressor Heats up and stop work no Noise Not used
r 22
(Nov 26, 2014) Michelle said:
Heat mode works fine.
In cooling mode, air is blowing but not cooling.
Can reset breaker even though it isn't tripped and will start cooling again.
Noticed more frequently as outside air temperatures got cooler.
Seems to happen daily or every couple days, but all I do is reset the breaker and it works again
(Dec 27, 2014) scott said:
AC cooling works fine. Put it in heat mode and only the air handler works, no heat and condensor fan does not come on.
Sounds like a control board problem or thermostat not set correctly
Michelle
When the air handler blows warm air in cooling mode
1. check that the aux heaters are not stuck "on"
2. check for a warm cooling coil - which in turn means lost refrigerant or a refrigerant metering problem or a failed compressor
When re-setting a breaker is "fixing" the problem I suspect a failing compressor motor.
Scott
If the outside heat pump unit is not turning on there may be a failed control, relay, or even thermostat wire connection.
(Sept 24, 2014) Anonymous said:
for 2 days the lights in the house dimmed for longer then normal before compressor kicked in 3 day no cool air?
Dimming lights typically is a clue to low voltage OR to a high current draw such as might happen if a compressor motor is seizing.
(Sept 25, 2014) ron said:
thanks danjoe . the unit is only 5 years. iam hopeing its not the compressor but something causing the low voltage. thanks again ron
Reply:
Ron
Thanks for the follow-up. If you monitor voltage right at the meter or panel that can confirm low voltage from the electrical company. Rule that out to start. You might get the motor running with a new start/run capacitor.
(Sept 26, 2014) Anonymous said:
thanks for the info dan. the ac guy showed up yesterday took the cover off went directly to the run cap. put a new in checkd Freon 20 min. later handed me a bill for 172.50 had I known I could have done it myself. knowledge is power. and MONEY. still not sure they go out thanks again.
(Sept 26, 2014) Anonymous said:
thanks for the info dan. the ac guy showed up yesterday took the cover off went directly to the run cap. put a new in checkd Freon 20 min. later handed me a bill for 172.50 had I known I could have done it myself. knowledge is power. and MONEY. still not sure they go out thanks again.
Sept 29, 2014) Roger said:
We have a 'heat pump', the outside unit starts up when required, how ever, the inside blower does not always come on. It works ok sometimes, but not always. When working normal, the temp is great.
(Oct 9, 2014) Ronda said:
We have a heat pump/ air conditioner unit. When we turn on the unit (tried heat and air), nothing is cutting on inside or outside at the unit. We have a Honeywell RTH6350D programmable theromstat and changed the fan from auto or on and even that is not working. Any suggestions on what could be the problem?
Ronda
I'd start by confirming that there is electrical power to the devices. Also check for an open blower door or a condensate overflow pan that is full.
(Dec 8, 2014) Sharon L said:
Hi, I have a 10+ year old York electric ac/ heat pump. My heat was on (but the "heat on" notation on my thermostat didn't read that it was on and the fan kept running for hours. Is this normal? I am just wondering why the fan kept running while the house was not being heated---or not according to my thermostat anyway.
Sharon if the heating system fan runs indefinitely I suspect that at the thermostat or at a fan limit switch the fan was set to ON rather than AUTO, OR the system was unable to reach the thermostat set temperature - a problem that deserves a service call.
(Dec 16, 2014) Andy said:
We have an ac/heat pump. Condensation is running down the side of the unit from about 3/4 way up, then running off the roof, so much so it leaves a lg puddle on the patio. When the unit runs and shuts off this stream is constant but slows to a drip if the unit has not run in a while.What could be the problem or is this normal. I don't recall this happening in prior yrs
Andy it sounds as if the normal condensate handling system of your unit is not working, perhaps due to a clog or a rust perforation. It's not normal to see water running on the outside of the unit. Ask your HVAC service company to take a look. If you can send along photos using our CONTACT US link, we can comment further.
(Jan 5, 2015) George Kubo said:
Heat Pump fan comes on when you turn on the thermostat for heat but goes off after a minute. There is 24 volts on contractor relay coming from the control board when the fan is on BUT there is not 24 volts coming out of the control board to the contractor relay when the fan turns off. Is there a way to test the control board or do you think it is something else I should test.
Thanks,George
George
I agree that it sounds like a control board problem. For someone not an HVAC tech a reasonable start is a close visual inspection of the board for loose or burned components.
(Jan 5, 2015) kevin said:
Hello.
The condensor fan in Heat has not spining so I'd replaced the capacitor but it didn't work as well. So I tested it in Cool and it blowed a cool air. I assummed that the air conditioner would not work as well. I am confused what's happing on my heat pump. Thanks for in advance.
Kevin I'm confused too. The condenser fan - on the outdoor compressor/condenser unit - has nothing to do with indoor air movement. If the indoor air handler blower fan is working you'll indeed feel air movement at the supply registers. The temperature of that air depends - if your system is a heat pump and if there is backup heat that takes over in very cold weather, then in heating mode you'd expect to feel warm air at the supply registers.
(Mar 9, 2015) Anonymous said:
i have a heat pump unit that works on heating mode however on cooling mode it gives a low suction pressure it is an r410 split unit. eventually icing up the evaporator coil
...
Continue reading at DIAGNOSTIC GUIDE A/C or HEAT PUMP or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
REPAIR & DIAGNOSTIC FAQs for A/C-#2 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.