InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

ACOUSTICAL SEALANT CHOICES
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
ATTIC LEAKS, CONDENSATION & MOLD

BATHROOM VENTILATION
BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BLOWER DOORS & AIR INFILTRATION
BRICK LINED WALLS
BRICK VENEER WALL AIR LEAKS
BUCKLED FOUNDATIONS due to INSULATION?

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CRAWL SPACES
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS

DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in BUILDINGS
HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET

INDOOR AIR QUALITY & HOUSE TIGHTNESS
INSULATION INSPECTION & IMPROVEMENT
INSULATION R-Values & Properties

LEED GREEN BUILDING CERTIFICATION

MOISTURE CONTROL in BUILDINGS

NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE

RADIANT BARRIERS

SOUND CONTROL in buildings
STAIN DIAGNOSIS on BUILDING INTERIORS

THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

VAPOR BARRIERS & CONDENSATION in buildings
VENTILATION in BUILDINGS

WALL CONSTRUCTION BARRIER vs CAVITY
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

  (C) Daniel Friedman Guide to Superinsulation Retrofit Information for Existing Structures
     

  • How to adapte superinsulation techinques to an existing building in an insulation retrofit project
    • Books & conference proceedings on superinsulation building retrofits
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
  • Questions & answers about how to superinsulate an existing building
  • References

Click to Show or Hide Related Topics

  • INSULATION IDENTIFICATION GUIDE - home
  • INSULATION INSPECTION & IMPROVEMENT - home
  • INSULATION LOCATION - WHERE TO PUT IT - home
  • AIR LEAK SEALING PROCEDURE
  • BASEMENT HEAT LOSS
  • BLOWN-IN INSULATION
  • BUCKLED FOUNDATIONS due to INSULATION?
  • CATHEDRAL CEILING INSULATION
  • CEILINGS, DROP or SUSPENDED PANEL
  • CRAWL SPACE INSULATION RETROFIT
  • FRAMING DETAILS for BETTER INSULATION
  • FREEZE-PROOF A BUILDING
  • HEAT LOSS in BUILDINGS - home
  • ICE DAM PREVENTION
  • INSULATION LOCATION - WHERE TO PUT IT - home
    • INSULATION LOCATION & QUANTITY for ATTICS
    • INSULATION LOCATION for BASEMENT FLOORS
    • INSULATION LOCATION for BASEMENT WALLS
    • INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
    • INSULATION LOCATION for BRICK VENEER WALLS
    • INSULATION LOCATION for CAPES, CRAWLSPACES
    • INSULATION LOCATION for CATHEDRAL CEILINGS
    • INSULATION LOCATION for CRAWL SPACES
    • INSULATION LOCATION for GREENHOUSE or SOLARIUM
    • INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
    • INSULATION LOCATION & EXTENT for SLABS
    • INSULATION LOCATION for SOUND CONTROL
    • INSULATION LOCATION for SUSPENDED PANELS
    • INSULATION LOCATION for SWIMMING, INDOOR
    • INSULATION on HOT WATER PIPING
    • INSULATION ON HOT WATER TANK
  • INSULATION MOLD
  • INSULATION R-Values & Properties
  • RADIANT BARRIERS
  • REFLECTIVE INSULATION
  • SLAB INSULATION, PASSIVE SOLAR
  • SOUND CONTROL in building
  • THERMAL IMAGING, THERMOGRAPHY
  • THERMAL TRACKING Heat Loss
  • VAPOR BARRIERS & CONDENSATION in BUILDINGS
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

This article discusses sources of information on adapting superinsulation techinques to an existing building. For a detailed superinsulation study of an older home see ENERGY SAVINGS RETROFIT CASE STUDY. Sketch at page top and accompanying text are reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Where to Find Information on Superinsulation Retrofits

The question-and-answer article below paraphrases, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.

Superinsulation Retrofit

Question:

Where can I obtain data on adapting superinsulation techniques to existing structures? - L Benson, Woodland ME

Answer:

The goals of superinsulating an existing building are the same as for new construction, but the problems are different.

The biggest challenge in adapting superinsulation methods to an existing structure is making the vapor barrier and insulation continuous between floors and between rooms.

  • Probably the best source of information we have come across is Superinsulated Retrofit [at Amazon.com] by Brian Marshall and Robert Argue, published by Renewable Energy in Canada.,
  • Also good, particularly on insulation theory, is Charles Wing's From the Walls In, [at Amazon.com] Little, Brown, and Co., Boston.
  • A third source, a collection of related pamphlets bound into a three-ring binder, has one very good pamphlet on superinsulation retrofitting: Major Energy Conservation Retrofits, [at Amazon.com] National Center for Appropriate Technology, Butte MT.

Also see

  • Super-Insulated Retrofit Book: A Homeowner's Guide, Robert Argue
  • The Super-Insulated Retrofit Book: A Homeowner's Guide to Energy-Efficient Renovation, Brian Marshall, Sun Builders Series
  • Building for Energy Independence: Sun/Earth, Don Booth
  • Superinsulation: a housing trend, Robert Corbett
  • Superinsulation Design and Construction, Linda F Scott
  • Superinsulation Conference Proceedings, Inernational Solar Energy Society (UK Section)
  • Building Insulation Materials: Building insulation materials, Building insulation, Thermal insulation, Spray foams (insulation), Rigid panel, Structural ... Superinsulation, R-value (insulation), Alphascript Publishing
  • Superinsulation for Iowa (EES-46), Laurent Hodges
  • Superinsulation Breakthrough in Housing, James Buesing

  • Our list of books on Superinsulation and Superinsulation Retrofits [at Amazon.com] is at Superinsulation Referencess
  • Be sure to also take a look at ENERGY SAVINGS PRIORITIES and see the many insulation retrofit details described at ENERGY SAVINGS RETROFIT CASE STUDY.

For a detailed superinsulation study of an older home see ENERGY SAVINGS RETROFIT CASE STUDY.

The question-and-answer article above, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.

The link to the original Q&A article in PDF form immediately below is preceded above by an expanded/updated online version

  • Q&A on Superinsulation Retrofit - PDF version, use your browser's back button to return to this page. Original article, Solar Age Magazine, November, 1985, adapted and updated for InspectAPedia.com January 2011..

...


Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Use the search box below to ask a question or to search the InspectApedia.com website.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steve Bliss's Building Advisor at buildingadvisor.com helps homeowners & contractors plan & complete successful building & remodeling projects: buying land, site work, building design, cost estimating, materials & components, & project management through complete construction. Email: info@buildingadvisor.com
    Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.
  • ASHRAE resource on dew point and wall condensation - see the ASHRAE Fundamentals Handbook, available in many libraries. The following three ASHRAE Handbooks are also available at the InspectAPedia bookstore in the third page of our Insulate-Ventilate section:
    • 2005 ASHRAE Handbook : Fundamentals : Inch-Pound Edition (2005 ASHRAE HANDBOOK : Fundamentals : I-P Edition) (Hardcover), Thomas H. Kuehn (Contributor), R. J. Couvillion (Contributor), John W. Coleman (Contributor), Narasipur Suryanarayana (Contributor), Zahid Ayub (Contributor), Robert Parsons (Author), ISBN-10: 1931862702 or ISBN-13: 978-1931862707
    • 2004 ASHRAE Handbook : Heating, Ventilating, and Air-Conditioning: Systems and Equipment : Inch-Pound Edition (2004 ASHRAE Handbook : HVAC Systems and Equipment : I-P Edition) (Hardcover)
      by American Society of Heating, ISBN-10: 1931862478 or ISBN-13: 978-1931862479
      "2004 ASHRAE Handbook - HVAC Systems and Equipment The 2004 ASHRAE HandbookHVAC Systems and Equipment discusses various common systems and the equipment (components or assemblies) that comprise them, and describes features and differences. This information helps system designers and operators in selecting and using equipment. Major sections include Air-Conditioning and Heating Systems (chapters on system analysis and selection, air distribution, in-room terminal systems, centralized and decentralized systems, heat pumps, panel heating and cooling, cogeneration and engine-driven systems, heat recovery, steam and hydronic systems, district systems, small forced-air systems, infrared radiant heating, and water heating); Air-Handling Equipment (chapters on duct construction, air distribution, fans, coils, evaporative air-coolers, humidifiers, mechanical and desiccant dehumidification, air cleaners, industrial gas cleaning and air pollution control); Heating Equipment (chapters on automatic fuel-burning equipment, boilers, furnaces, in-space heaters, chimneys and flue vent systems, unit heaters, makeup air units, radiators, and solar equipment); General Components (chapters on compressors, condensers, cooling towers, liquid coolers, liquid-chilling systems, centrifugal pumps, motors and drives, pipes and fittings, valves, heat exchangers, and energy recovery equipment); and Unitary Equipment (chapters on air conditioners and heat pumps, room air conditioners and packaged terminal equipment, and a new chapter on mechanical dehumidifiers and heat pipes)."
    • 1996 Ashrae Handbook Heating, Ventilating, and Air-Conditioning Systems and Equipment: Inch-Pound Edition (Hardcover), ISBN-10: 1883413346 or ISBN-13: 978-1883413347 ,
      "The 1996 HVAC Systems and Equipment Handbook is the result of ASHRAE's continuing effort to update, expand and reorganize the Handbook Series. Over a third of the book has been revised and augmented with new chapters on hydronic heating and cooling systems design; fans; unit ventilator; unit heaters; and makeup air units. Extensive changes have been added to chapters on panel heating and cooling; cogeneration systems and engine and turbine drives; applied heat pump and heat recovery systems; humidifiers; desiccant dehumidification and pressure drying equipment, air-heating coils; chimney, gas vent, fireplace systems; cooling towers; centrifugal pumps; and air-to-air energy recovery. Separate I-P and SI editions."
    • Principles of Heating, Ventilating, And Air Conditioning: A textbook with Design Data Based on 2005 AShrae Handbook - Fundamentals (Hardcover), Harry J., Jr. Sauer (Author), Ronald H. Howell, ISBN-10: 1931862923 or ISBN-13: 978-1931862929
    • 1993 ASHRAE Handbook Fundamentals (Hardcover), ISBN-10: 0910110964 or ISBN-13: 978-091011096
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Brick nogging used as soundproofing is mentioned in this article on Popular Forest
  • Brick Nogging, Historical Investigation and Contemporary Repair, Construction Specifier, April 2006. Historical use of brick in timber-framed buildings, drawing on the investigations of the Kent Tavern in Calais, VT. "Brick nogging is a European method of construction which was brought to the new world in the early-nineteenth century. It was a common construction method that employed masonry as infill between the vertical uprights of wood framing." -- quoting the web article review.
  • Photo of very rough in-wall brick nogging at an architects website
  • Building Research Council, BRC, nee Small Homes Council, SHC, School of Architecture, University of Illinois at Urbana-Champaign, brc.arch.uiuc.edu. "The Small Homes Council (our original name) was organized in 1944 during the war at the request of the President of the University of Illinois to consider the role of the university in meeting the demand for housing in the United States. Soldiers would be coming home after the war and would be needing good low-cost housing. ...  In 1993, the Council became part of the School of Architecture, and since then has been known as the School of Architecture-Building Research Council. ... The Council's researchers answered many critical questions that would affect the quality of the nation's housing stock.
    • How could homes be designed and built more efficiently?
    • What kinds of construction and production techniques worked well and which did not?
    • How did people use different kinds of spaces in their homes?
    • What roles did community planning, zoning, and interior design play in how neighborhoods worked
  • Energy Savers: Whole House Systems Approach to Energy Efficient Home Design [copy on file as /interiors/Whole_House_Energy_Efficiency_DOE.pdf ] - U.S. Department of Energy
  • "Energy Savers: Whole-House Supply Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Supply_Vent.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11880?print
  • "Energy Savers: Whole-House Exhaust Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Exhaust.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11870
  • "Energy Savers: Ventilation [copy on file as /interiors/Energy_Savers_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Natural Ventilation [copy on file as /interiors/Energy_Savers_Natural_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Energy Recovery Ventilation Systems [copy on file as /interiors/Energy_Savers_Energy_Recovery_Venting.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11900
  • "Energy Savers: Detecting Air Leaks [copy on file as /interiors/Energy_Savers_Detect_Air_Leaks.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Air Sealing [copy on file as /interiors/Energy_Savers_Air_Sealing_1.pdf ] - ", U.S. Department of Energy
  • Falls and Related Injuries: Slips, Trips, Missteps, and Their Consequences, Lawyers & Judges Publishing, (June 2002), ISBN-10: 0913875430 ISBN-13: 978-0913875438
    "Falls in the home and public places are the second leading cause of unintentional injury deaths in the United States, but are overlooked in most literature. This book is unique in that it is entirely devoted to falls. Of use to primary care physicians, nurses, insurance adjusters, architects, writers of building codes, attorneys, or anyone who cares for the elderly, this book will tell you how, why, and when people will likely fall, what most likely will be injured, and how such injuries come about. "
  • Fiberglass: Indoor Air Quality Investigations: Health Concerns About Airborne Fiberglass: Fiberglass in Indoor Air from HVAC ducts, and Building Insulation
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • Ice Dam Leaks in building attics and roof cavities, how to inspect for evidence of leaks, identify causes, and correct bad attic ventilation, improper roof venting, and these causes of attic mold or roof structure damage
  • "Insulation: Adding Insulation to an Existing Home," U.S. Department of Energy - tips on how to do your own check for the presence of absence of insulation in a home
  • Insulation: Selecting Insulation for New Home Construction, U.S. Department of Energy - "Your state and local building codes probably include minimum insulation requirements, but to build an energy-efficient home, you may need or want to exceed them. For maximum energy efficiency, you should also consider the interaction between the insulation and other building components. This is called the whole-house systems design approach."
  • Insulation Types, table of common building insulation properties from U.S. DOE. Readers should see INSULATION R-Values & Properties our own table of insulation properties that includes links to articles describing each insulation material in more detail.
  • The National Institute of Standards and Technology, NIST (nee National Bureau of Standards NBS) is a US government agency - see www.nist.gov
    • "A Parametric Study of Wall Moisture Contents Using a Revised Variable Indoor Relative Humidity Version of the "Moist" Transient Heat and Moisture Transfer Model [copy on file as/interiors/MOIST_Model_NIST_b95074.pdf ] - ", George Tsongas, Doug Burch, Carolyn Roos, Malcom Cunningham; this paper describes software and the prediction of wall moisture contents. - PDF Document from NIS
  • Nogging: See this photo of exposed bricks on a building exterior on a building exterior in Canada. [Thanks to Carson Dunlop, Toronto - see References below].
  • "Weather-Resistive Barriers [copy on file as /interiors/Weather_Resistant_Barriers_DOE.pdf ] - ", how to select and install housewrap and other types of weather resistive barriers, U.S. DOE