InspectAPedia.com InspectAPedia®

Question? Just ask us!

Google
InspectAPedia

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR CHANGE RATE ACH HEAT SAVINGS
AIR CLEANER PURIFIER TYPES
AIR FILTER EFFECTIVENESS
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR FILTERS, SOURCES FOR
AIR FILTERING STRATEGIES
AIR FILTERING CONTINUOUS FAN OPERATION
AIR FLOW MEASUREMENT CFM
AIR HANDLER / BLOWER UNITS
AIR POLLUTANTS, COMMON INDOOR

AIR LEAK DETECTION TOOLS
  ATTIC ENERGY LOSSES - Infra-Red
  BASEMENT ENERGY LOSSES - IR & Visual
  BLOWER DOOR TEST RESULTS
  CONVECTIVE LOOPS & THERMAL BYPASS LEAKS
  DUCT SYSTEM ENERGY LOSSES
  ENERGY RETROFIT BOTTOM LINE
  HEAT LOSS INVESTIGATION SEQUENCE
  HIDDEN AIR & ENERGY LOSS POINTS
  HOUSE DOCTOR, how-to be
  INSULATION AIR & HEAT LEAKS
  SMOKE GUNS for AIR LEAK DETECTION
  LIVING SPACE HEAT LOSSES
  SMOKE PENCIL / SMOKE GUN SOURCES
  THERMOGRAPHY IR Infra Red & Thermal Scanners
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
ALLERGEN TESTS for buildings
ALLERGENS in BUILDINGS, RECOGNIZING
ALLERGY & MOLD IAQ PRODUCTS
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ALLERGENS / PET DANDER
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & MOLD
ATTIC VENTILATION

BACKDRAFTING HEATING EQUIPMENT
BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION
BRICK LINED WALLS
BRICK VENEER WALL AIR LEAKS
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  DRYER VENTING
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING, SOLAR
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in BUILDINGS
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES
ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY
EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD
FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold
FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS
FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GAS EXPOSURE EFFECTS, TOXIC
  Carbon Dioxide - CO2
  Carbon Monoxide - CO
  METHANE GAS SOURCES
GAS DETECTION INSTRUMENTS
  Drager GAS DETECTORS
  COLORIMETRIC GAS DETECTION TUBES
  GAUGE, REFRIGERATION PRESSURE TEST
  TIF 5000 GAS DETECTOR
  TIF 8800 GAS DETECTOR
  GAS DETECTOR WARNINGS
  GAS DETECTOR TUBE WARNINGS

HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
  ATTIC ENERGY LOSSES - Infra-Red
  BASEMENT ENERGY LOSSES - IR & Visual
  BLOWER DOOR TEST RESULTS
  CONVECTIVE LOOPS & THERMAL BYPASS LEAKS
  DUCT SYSTEM ENERGY LOSSES
  ENERGY RETROFIT BOTTOM LINE
  HEAT LOSS INVESTIGATION SEQUENCE
  HIDDEN AIR & ENERGY LOSS POINTS
  HOUSE DOCTOR, how-to be
  INSULATION AIR & HEAT LEAKS
  SMOKE GUNS for AIR LEAK DETECTION
  LIVING SPACE HEAT LOSSES
  SMOKE PENCIL / SMOKE GUN SOURCES
  THERMOGRAPHY IR Infra Red & Thermal Scanners
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
ICE DAM PREVENTION
INSECT INFESTATION / DAMAGE
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LIGHT, GUIDE to FORENSIC USE
LIGHTING, EXTERIOR GUIDE
LIGHTING, INTERIOR GUIDE
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER
MSDS Material Safety Data Sheets

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT RESISTANT LUMBER
ROT, TIMBER FRAME
ROT, TIMBER ASSESSMENT

SAFETY HAZARDS GUIDE
  MSDS Material Safety Data Sheets
  Chemicals, Cleaners MSDS
  Drywall MSDS
  Gases in buildings MSDS
  Heating Fuels, Controls, Oil, Crude Oil, Gas MSDS
  Insulation Products MSDS
  Fiberglass Insulation Exposure Limits
  Mold Related Products MSDS
  Paint / Sealant MSDS
  Septic Dye MSDS
  Septic & Holding/RV Tank/Toilet Chemicals MSDS
  Smoke Generator Chemicals Powders MSDS
  Water Purification Products MSDS
  SAFETY: Elderly & Veterans Home Safety

SMELL PATCH TEST to Track Down Odors
SEARS KIT HOUSES

SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on & in BUILDINGS, CAUSES & CURES
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE
STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STONE VENEER WALLS
STRAW BALE CONSTRUCTION
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
STRUCTURAL DAMAGE PROBING
STRUCTURAL WOOD ASSESSMENT
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

Thermal Expansion Cracking of Brick
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
THERMAL IMAGING, THERMOGRAPHY
THERMAL IMAGING MOLD SCANS
THERMAL MASS in BUILDINGS

THERMAL TRACKING & HEAT LOSS
  Ceiling Thermal Tracking Marks
  Wall Thermal Tracking Stains
  Floor Carpet Thermal Tracking Stains
  Air Bypass Leaks Marks on Insulation
  Thermal Tracking to Diagnose IAQ
  Stains HVAC Supply Registers
  Pet Stains on Floors
  Pet Stains on Walls
  Human Occupant Stains on Walls
  Stains from Candles, Woodstoves, Fireplaces
  Other Stains on Indoor Walls & Ceilings
  What to Do About Thermal Tracking

VAPOR BARRIERS & CONDENSATION in buildings
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  CONDENSATION or SWEATING PIPES, TANKS
  CRAWL SPACE VAPOR BARRIER
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  FELT 15# ROOFING, as HOUSEWRAP/VAPOR BARRIER
  HOUSEWRAP AIR & VAPOR BARRIERS
  HOUSEWRAP INSTALLATION DETAILS
  HOUSEWRAP PRODUCT CHOICES
  HOUSEWRAP at SILLS, SOLES, TOP PLATES
  HUMIDITY LEVEL TARGET
  MOISTURE CONTROL in BUILDINGS
  RAIN SPLASH-UP SIDING DAMAGE
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in buildings
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR BARRIERS, VINYL SIDING
  VAPOR CONDENSATION & BUILDING SHEATHING
  WATER BARRIERS, EXTERIOR
  WOOD SIDING FLASHING DETAILS
VENTILATION in BUILDINGS

WALL CONSTRUCTION BARRIER vs CAVITY
WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE DAMPERS
ZONE VALVES

More Information

Smoke test demonstrating air lea at a door (C) Daniel Friedman Smoke Pens: Where to Buy Smoke Pencils, Smoke Puffers & Smoke Generating Tools
     

  • SMOKE PENCIL / SMOKE GUN SOURCES - Where to buy smoke pencils, smoke pencil sticks, smoke puffers, smoke guns, air current tubes, & energy savings inspection equipment: smoke gun suppliers
    • Companies Producing & Distributing Smoke Pens, Pencils, Bottles, Powder Puffers & other Smoke Generating Equipment
    • Table of Properties, Chemicals, Operating Mechanisms of Smoke Generating & Smoke Testing Equipment & Devices
    • Catalog of Types of Smoke Bottles, Smoke Emitters, Smoke Pens & Pencils, Guns, Smoke Puffers
    • Smoke Gun & Smoke Pen or Smoke Pencil System Safety, Hazards, MSDS Sheets
    • Using smoke emitter pencils, smoke guns, or smoke generators for finding air leaks & building heat loss
    • Building heat loss & energy efficiency tools & procedures: smoke matches, smoke pellets, smoke generators
    • How to find and seal building air leaks, how to find and correct points of un-wanted building heat loss or heat gain
  • Questions & Answers about choosing, buying, & using smoke pens, smoke pencils and related HVAC and building air movement test tools
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
  • References

Click to Show or Hide Related Topics

  • ENERGY SAVINGS in buildings - home
  • AFUE DEFINITION, RATINGS
  • AIR BYPASS LEAKS
  • AIR CHANGE RATE ACH HEAT SAVINGS
  • AIR CONDITIONING HEAT PUMP SAVINGS
  • AIR LEAK DETECTION TOOLS - home
  • AIR SEALING STRATEGIES
  • BASEMENT HEAT LOSS
  • BTU USAGE MONITORS
  • CATHEDRAL CEILING INSULATION
  • COOLING LOAD REDUCTION by VENTS
  • DRYER VENTING
  • DUCT SYSTEM & DUCT DEFECTS
  • ENERGY AUDIT - How to Use a Free One
  • ENERGY SAVINGS MAXIMIZE RETURNS ON  
  • ENERGY SAVINGS PRIORITIES
  • ENERGY SAVINGS RETROFIT CASE STUDY
  • ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  • ENERGY SAVINGS RETROFIT OPTIONS
  • ENERGY STAR PROGRAM
  • ENERGY USE MONITORING, SOLAR
  • EVAPORATIVE COOLING SYSTEMS
  • FRAMING DETAILS for BETTER INSULATION
  • GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  • HEAT LOSS in BUILDINGS - home
  • HEAT LOSS DETECTION TOOLS
  • HEATING COST APPORTIONMENT, BTU MONITORS
  • HEATING COST SAVINGS METHODS
  • HIGH MASS TRADEOFFS, HEATING vs COOLING
  • HOUSE DOCTOR, how-to be
  • INDOOR AIR QUALITY & HOUSE TIGHTNESS
  • INSULATION INSPECTION & IMPROVEMENT
  • INSULATION LOCATION - WHERE TO PUT IT
  • INSULATION R-Values & Properties
  • LOG HOME ENERGY EFFICIENCY
  • RADIANT BARRIERS
  • RADIANT HEAT
  • REFLECTIVE INSULATION
  • RIGID FOAM USE INDOORS
  • ROOF COLOR RECOMMENDATIONS
  • SKYLIGHT ENERGY EFFICIENCY
  • SOLAR ENERGY SYSTEMS
  • THERMAL IMAGING, THERMOGRAPHY
  • THERMAL MASS in buildings
  • THERMAL TRACKING & HEAT LOSS
  • TIMERS for ELECTRIC WATER HEATERS
  • VENTILATION, BALANCED SAVINGS
  • WALL CONSTRUCTION BARRIER vs CAVITY
  • WIND ENERGY SYSTEMS
  • WINDOW EFFICIENCY Features & Ratings
  • WOOD, COAL STOVES & FIREPLACES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Smoke test tools & smoke generators: where to choose & buy smoke test equipment for HVAC & air movement tests in buildings: This article provides sources of smoke pencils and air leak detection tools for building energy savings. Smoke generators of a variety of types have a wide range of diagnostic uses including finding building air flow studies, air leaks or heat loss points, HVAC duct air leaks, heat exchanger leaks, testing for air movement around ventilation hoods, checking for indoor air ventilation in office or test lab spaces, operation of exhaust fans, even leaks in drainage and drain piping systems. The mechanics and chemistry of smoke pens and smoke generators vary widely and some include irritating or even toxic fumes and chemicals while others are safer to operate. We discuss and compare all of those features and uses in this article. Our page top photo shows the website author using a smoke tester to view air movement into an un-insulated wall cavity.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Where to Find & Buy Smoke Pencils for Tracing Air Leaks in buildings

Smoke test for air leaks (C) Daniel Friedman Steven BlissQuestion: source to purchase smoke testing equipment

Where can I buy a smoke pencil ? -- Jerry Fry, Monterey CA

Answer:

Immediately below we provide a list of companies providing smoke guns, pencils, bombs, emitters, puffers and similar HVAC and building air movement test equipment. We also provide links to MSDS and other safety and usage guides for smoke emitting and test equipment.

Our photo (at page top and again at below left) shows a simple smoke generating "pencil" in use to test for air leaks at an opening in an icynene foam insulated crawl space. The glass tube is filled with a chemical that generates a chemical "smoke" when the tube ends are broken off and air is pushed through the tube by the rubber bulb in the website author's hand.

At Smoke Gun for Air Leaks we discuss the use of smoke generators, and smoke guns or smoke pencils in buildings.

Also see Smoke Gun for Air Leaks where we describe how to use a smoke pencil or smoke gun, and also see AIR LEAK DETECTION TOOLS and AIR BYPASS LEAKS as well as HEAT LOSS in BUILDINGS and HEAT LOSS INDICATORS. For advice on sealing against air leans during new building construction, see AIR LEAK MINIMIZATION.

List of Companies Producing & Distributing Smoke Pens, Pencils, Bottles, Powder Puffers & other Smoke Generating Equipment for Various Test Purposes

Gastec 9501 smoke generator (C) Daniel Friedman
  • BJÖRNAX smoke products is the original producer of many of the smoke emitting products listed here and distributed by a wide range of suppliers including Regin in the U.S.. Contact: Björnax AB, Stråssa Företagsby, 71177 Stråssa Sweden, Tel: +46 (0)581 431 50, Fax: +46 (0)581 432 06, Website: http://www.bjornax.se
  • Fire Systems Services, an Australian company, is a large distributor of smoke generators and other fire and fire-fighting-related equipment Contact: Fire System Services, Unit 1, 16 Glasgow Street, Wingfield, South Australia 5013, Mail to: P.O. Box 16, Prospect SA 5082, Tel: +61 8 8445 6300, Website: http://www.firesys.com.au/
  • Gastec, produces a wide range of gas detector tubes. Using the same technology Gastec produces a tube, the Gastec Irritant Smoke Qualitative Fit Testing Kit No. 9501 that operates as a smoke emitter, producing an ultra-fine white tracer smoke" that can be used to observe air movement. See GAS DETECTION INSTRUMENTS for a discussion of how this equipment is used.

  • Kitagawa produces gas detector tubes (for example used with Sensidyne gas detector pumps). their product line may include smoke emitter tubes for use with different instruments.
  • National Draeger, the Dräger Air Current Test Kit is described by the manufacturer - details are in the article below
  • Regin Products for Heating, Air Conditioning, & Special Effects, Regin HVAC Products, Inc. 315 Riggs Street, Unit 1 Oxford, CT 06478 USA, Tel: (203) 881-2600 or (800) 394-2739
  • Smoke Puffer Pencil - see http://www.chimneyballoon.us
  • HVAC equipment & test tool suppliers: check with your local heating, ventilation, and air conditioning contractor suppliers. Some of these are listed following the list of page links, below at References.
  • Home inspection equipment suppliers: check with any home inspection equipment supplier

Smoke test equipment manufacturers can refer you to local distributors for smoke pencils or other smoke testing and air testing or air movement testing equipment.

Also many home inspectors have and use this equipment, as do home energy auditors and "house doctors". (See Directory of Professionals to Inspect or Test a Building and MOLD INSPECTORS & MOLD TESTERS.)

At Basement Energy Losses- IR & Visual we show additional photographs of using a smoke generator tube (smoke pencil) to check building air flow and building air leaks at a basement wall.

At AIR LEAK DETECTION TOOLS we show using a smoke pencil to determine the direction of air flow (under a door) when evaluating return air supply adequacy for an air conditioning system

Table of Properties, Chemicals, Operating Mechanisms of Smoke Generating & Smoke Testing Equipment & Devices

For a list of specific smoke test products, properties, and suppliers see Catalog of Types of Smoke in the next section of this article.

Smoke Device Type Key Ingredients Mechanism Comments
Air current test kit Various Chemicals in one or a series of sealed glass tubes; tube ends are broken open to permit air, moisture etc. to pass through tube, chemical reaction creates "smoke"

E.g. see Air Current Test Kit — Dräger Cat. No. 800-216 (replacement tube 800-25301 ) or the Airflow Indicator Kit — GASTEC Cat. No. 810-500 (replacement tube 810-501 )

Potentially hazardous, not suitable for respirator fit testing

FP Smoke Dimethyl silicone
reaction product
with silica, Calcium Carbonate
Mechanical: a plastic bottle of powder is squeezed to produce a puff of white particles. Bottle orifice determines the size or volume of the puff of test smoke. Rubber bulb squeeze pump device is available from Regin Co.

BJÖRNAX AB & Regin Co.

Not classified as hazardous

Gas tubes Various

Rubber squeeze bulb or pump to which a glas tube is attached.

Chemicals in one or a series of sealed glass tubes; tube ends are broken open to permit air, moisture etc. to pass through tube, chemical reaction creates "smoke"

E.g. see Gastec & see GAS DETECTION INSTRUMENTS

& see air current test kits listed earlier in this table

Potentially hazardous

Qualitative Fit Testing Kit Tin tetrachloride or Stannic chloride (irritating smoke) Tube (ampoule) is broken (flexible plastic tube) and either contains its own bulb-pump at one end, or is inserted into a rubber bulb or hand pump to emit puffs of test smoke for respirator fit testing.

Respirator fit testing. See Nextteq & VeriFit™ Irritant Smoke Generators for Respirator Fit Testing

Smoke Bottles Titanium tetrachloride, releasing Hydrogen chloride (HCl) gas Mechanical: ampoule contained inside a plastic bottle is broken by squeezing the bottle, to emit dense smoke. Stop smoke emission by capping the bottle.

Smoke generation can continue for 24 hours.

Highly toxic, hazardous

Smoke Cans Butane/Propane hydrocarbon blend Aerosol spray used to test smoke alarms;

Home inspection, HVAC testing; typically 300 tests per can; E.g. SmokeCheck™ from HSI Fire & Safety Group LLC.

Potentially hazardous

Smoke Candles, smoke emitter cartridges Titanium tetrachloride ampoules, (
or Potassium chlorate and/or Ammonium Chloride
or
Hydrated zinc chloride, water condensate, carbon monoxide
Chemical reaction, may require ignition, white to gray smoke, burn time varies, as short as 3 minutes.

Operate for 24-hours per ampoule, corrosive irritating smoke. E.g. Superior® Signal 3C Smoke Candles (sold through Grainger et als) can produce as much as 40,000 cu.ft. of smoke.

Potentially hazardous

Smoke Emitter Bottles Titanium tetrachloride ampoules, (or Potassium chlorate and/or Ammonium Chloride) Mechanical, chemical; Ampoule is crushed within a plastic bottle

Operate for 24-hours per ampoule, corrosive irritating smoke

Potentially hazardous

Smoke Guns Various, Typically a rubber bulb attached to a glass tube or vial containing a chemical that reacts with air or moisture in air to emit smoke as "puffs" Potentially hazardous
Smoke Matches Potassium chloride & Ammonium Chloride Solid cartridge is ignited mechanically or chemically;

Short burning, 20 seconds typica.

Potentially hazardous

Smoke Pens, Smoke Pencils

Various including:

Butane/Propane hydrocarbon blend,

Particle size 0.3 to 2.5 microns

A smoke-emitting wick is inserted into the clutch pencil & ignited. Operating like a "mechanical pencil" the wick is adjusted to expose about 3/8" of wick that is ignited to provide a continuous stream of light gray to white smoke.

6 wicks provide up to 3 hours of continuous smoke or 360 - 30 second tests. E.g. HSI SmokeCheck™

Potentially hazardous

Smoke Pencil Puffer Stick Propylene glycol, glycerine, distilled water Battery powered hand-held device puffs vaporized "smoke fluid" or "super fog fluid" chemical. Smoke Pencil Puffer Stick includes a trigger on the smoke stick to release puffs of smoke (instead of squeezing a bottle) to show the direction of air movement.

Low toxicity

Smoke Powders Silica, calcium carbonate Finely ground silica or CaCO3, typically in a plastic squeeze bottle, emits a white puff of "smoke", typically heavier than and shorter airborne time than some other smoke types .

Low toxicity

Smoke Wicks   See smoke pens, smoke pencils Potentially hazardous
 

Catalog of Types of Smoke Bottles, Smoke Emitters, Smoke Pens & Pencils, Guns, Smoke Puffers

Foam insulation air leaks (C) Daniel Friedman


Smoke pencils, smoke guns, smoke matches, canned smoke, and fine powder smoke "puffers" are valuable for detecting where air infiltrates (leaks in) or exfiltrates (leaks out) of buildings or HVAC ducts, can be purchased from a variety of building and environmental test equipment suppliers including those listed below.

Watch out: some smoke tracing emitters produce highly toxic fumes (such as sulfuric acid H2SO4) that can injure lungs, eyes, skin, or even cause death if used at high concentrations in an enclosed space.

  • FP Smoke, a white powder produced by BJÖRNAX AB, (Dimethyl silicone reaction product with silica, Calcium Carbonate) is classified as non-hazardous and produces an airborne white tracer "smoke". Dispensed via a squeeze bottle (choose the bottle top orifice for the smoke application), one bottle can provide up to 300 cubic feet of white "smoke" for tracing air movement.
Gastec 9501 smoke generator (C) Daniel Friedman
  • Gas detector tubes include smoke-emitting tubes. Using the same colorimetric gas detector tube technology Gastec produces a tube, the Gastec Irritant Smoke Qualitative Fit Testing Kit No. 9501 that operates as a smoke emitter, producing an ultra-fine white tracer smoke" that can be used to observe air movement.

    See GAS DETECTION INSTRUMENTS for a discussion of how this equipment is used.

    The Gastec irritant smoke qualitative fit testing kit No. 9501 is designed to meet and be used in accordance with OSHA 29 CFR 1910.134.

    When the ends of the glass tube are cut off, the reagent in the tube reacts with air (squeezed through the tube with a rubber bulb) to produce visible and highly irritating smoke.

    Rubber caps are provided to seal the open tube so that it can be re-used later, but be sure to see our warnings about the corrosivity of these materials discussed below under National Draeger and the Dräger "smoke tube" # CH16631

    Watch out
    : according to the warnings published by Gastec and included with these tubes, the smoke emitted by these tubes is dangerous to life. Read all instructions and warnings before attempting to use this product.
Smoke test example (C) Daniel Friedman
  • National Draeger, the Dräger Air Current Test Kit is described by the manufacturer:

    Often the determination of airflow in HVAC ducts, fume hoods and other ventilation systems is necessary to locate problems. This Air Current Test Kit is a quick and inexpensive way to help make these determinations. It works by creating a highly visible non-irritating dense white smoke that can be followed to determine the airflow direction.

    To use, simply open the ends of the glass tubes with the supplied opener. Insert one end into the aspirator bulb. Squeeze the aspirator bulb to release a plume of smoke. Tubes are re useable until the medium has been extinguished. Caps are provided to cover the tube ends between uses.


    The Dräger Flow Check Airflow Indicator (much more costly), is described by the manufacturer as follows:

    The Dräger Flow Check system produces harmless clouds of smoke for use in detecting the flow of air currents. The system consists of a handheld instrument and a disposable ampoule containing smoke generating fluid. The ampoule fluid is a special mixture of alcohols developed at Dräger that when heated in the instrument, it condenses on contact with the ambient air creating a harmless, environmentally safe cloud of smoke. The flow check is compact and easy to use. Small, single clouds of smoke can be generated with a short press of a button. Continuous production of smoke is possible by locking the button in the on position.
    Contact:National Draeger, PO Box 120, Pittsburgh PA 15230 - 412-787-8383 - 866-905-9793
    See Use of a Drager pump for a discussion of how Draeger equipment is used in the field. Also see Warnings re instruments for detection of gases.

    Watch out: the Dräger "smoke tube" # CH16631 produces a sulfuric acid gas sulfuric acid H2SO4 /SO3 that is dangerous to life and is highly corrosive. Take a look at our copy of the Dräger MSDS for their CH25301 Air Current Tubes. We stored this MSDS in the box with the rubber bulb and tube cutter provided by Dräger. These air current monitoring tubes are provided with rubber caps so that the tube can be "stopped" or shut down when not in use. But the sulfuric acid was so corrosive that it not only caused the rubber caps to disintegrate, it actually "burned" or oxidized our copy of the MSDS paper form! Dräger MSDS for Dräger CH25301 Air Current Tubes, Page 1 and Dräger MSDS for Dräger CH25301 Air Current Tubes, Page 2
  • Nextteq irritating smoke fit testing & airflow or air current analysis kits use the Gastec Irritant Smoke Qualitative Fit Testing Kit No. 9501 discussed above. Nexteq, 877-312-2444 website: www.nextteq.com email: info@nextteq.com. Nextteq explains the use of irritating smoke for [respirator] fit testing as quick, easy to use, economical, and intrinsically safe and ready to use. "Irritating smoke is the only OSHA-accepted qualitative fit testing method that does not rely on the test subject's subjective response. Qualitative fit tests such as banana oil (isoamyl acetate), saccharin, or Bitrex may cause false negative results."

    Watch out: some smoke tracing emitters produce highly toxic fumes (such as sulfuric acid H2SO4) that can injure lungs, eyes, skin, or even cause death if used at high concentrations in an enclosed space. Read all instructions and warnings before attempting to use this product.
  • Smoke bottles: e.g. Regin's Smoke Bottle RFA, S101, Air-Check, 4911C, using Titanium tetrachloride, releasing Hydrogen chloride (HCl) gas, produce a colorless to pale yellow fuming liquid with an irritant odor, very reactive with water, reacts to moisture, extremely toxic if ingested or inhaled, eye and skin contact, toxic to lungs, mucous membranes. Personal protective equipment including MSHA/NIOSH approved respirator, neoprene gloves, splash goggles, use under an approved fume hood or equivalent, wash after handling;
  • Smoke cans: canned smoke: e.g. Smoke Check™ SAT-1, used to test smoke alarms, produced by HSI Fire & Safety Group, sold by home inspection tool suppliers & HVAC suppliers
  • Smoke candles: typically using titanium tetrachloride ampoules, (or Potassium chlorate and/or Ammonium Chloride) operate for 24-hours per ampoule, corrosive irritating smoke (see our MSDS references below). E.g. Miniax™ 45-second, 150cuft. "non-toxic smoke emitter" (gets hot, place on a safe surface, can, or sand) and Fire System Services Smoke Emitter candles, matches, powders including Miniax, Ventilax, Brandax, Datax, white smoke emitter candles discussed above, and coloured smoke emitters such as their AAX18, AX60, and Brandax KSO. Regin Smoke Emitters produce a large volume of "smoke" at a constant rate, using Potassium chlorate and/or Ammonium Chloride.
  • Smoke emitter bottles: As with the smoke candles above,, smoke emitter bottles typically use titanium tetrachloride ampoules, (or Potassium chlorate and/or Ammonium Chloride) operate for 24-hours per ampoule, corrosive irritating smoke (see our MSDS references below).Regin Smoke Emitters produce a large volume of "smoke" at a constant rate, using Potassium chlorate and/or Ammonium Chloride. Other examples: Miniax™ 45-second, 150cuft. "non-toxic smoke emitter" (gets hot, place on a safe surface, can, or sand) and Fire System Services Smoke Emitter candles, matches, powders including Miniax, Ventilax, Brandax, Datax, white smoke emitter candles discussed above, and coloured smoke emitters such as their AAX18, AX60, and Brandax KSO.
  • Smoke guns: E. Vernon Hill, Inc., PO Box 14248, San Francisco CA 94114 - 415-665-6628

Because smoke guns and smoke equipment are widely used by and produced by people involved in both HVAC and indoor air quality work, companies providing those services or who sell equipment to those practitioners can supply smoke testing equipment in a variety of forms such as ultra-fine powder that is "puffed" into the air to detect air movement direction, chemical tubes that generate smoke when opened, and capsules used to generate smoke to test for leaks in furnace heat exchangers.

We (D Friedman) use smoke generating tubes and other gas sampling equipment provided by the two most reliable companies in the world, Draeger-Safety's detector-tubes and Drager accuro™ bellows pump, the Gastec™ cylinder pump and detector-tube system produced by Gastec or Sensidyne, and we also use Sensidyne's Gilian air pump. For broad screening for combustibles and a number of other toxic gases and for leak tracing we also use Amprobe's Tif8850. All of these instruments, their applications, and sensitivities (minimum detectable limits) for specific gases are described in our Gas Sampling Plan online document.

  • Smoke matches: short burning, perhaps 20 seconds, low cost, can be a bit awkward. Suppliers: PH Gas Smatch, container of 75, in U.K., under £4. , Splintax (Regin HVAC Products & Fire System Services in the U.S., & Bjornax AB in Europe and other world locations)[6][9][11]. Smoke matches such as Bjornax's Splintax use Potassium chloride and Ammonium Chloride as a solid cartridge. The company's MSDS warns of this special risk:

    Explosive when mixed with combustible material; harmful by inhalation and if swallowed.
  • Smoke pens & Smoke Pencils: an ignited wick burns 30 minutes, e.g. produced by BJÖRNAX AB. Quoting from the manufacturer:

    The Bjornax reusable Smoke Emitter Pen is the perfect tool to dispense just the right amount of test smoke, when and where it is needed. A patented smoke-emitting wick is inserted into the clutch pencil and ignited. You can adjust the wick to provide a continuous stream of a light gray to white smoke. The Smoke Pen can be easily extinguished by simply replacing the protective cover. Wick diameter is 5.6mm and will burn for approximately 30 minutes each. Distributed by Bjornmax, FireSystemServices & Regin. [6][9][11]
Smoke bottle (C) Daniel Friedman
  • Smoke powders - powder puffer bottle: Ultra-fine powders and smoke-powder puffers: e.g. Micro-Powder Puffer, (pulverized silica and Calcium carbonate powder) from BJÖRNAX AB, & Powder-Puff Silica Smoke S201 from Regin in the U.S. or from Bjornax in Europe, Also distributed by Fire System Services. Smoke powders are typically emitted by squeezing a plastic bottle or using a rubber bulb attached to a specially-designed emitter-bottle. From the Bjornax MSDS:

    Harmful if inhaled. May be harmful if swallowed. Cause eye irritation. Irritating to mucous membranes and upper respirator tract. May cause skin irritation.

    Our photo (left) shows a Regin Powder Puffer "smoke" No. S201 air current tester that uses finely-ground silica (CAS 112945-52-5). Instructions include
  • Shake well

    Squeeze the center of the bottle with a quick firm motion

    Not edible. Do not inhale. Keep out of reach of children. Use only as Directed.

  • Smoke Puffer Pen or Smoke Puffer Pencils: (Propylene glycol, glycerine, distilled water), a battery-operated "pen" or "smoke puffer pencil" vaporizes the ingredients listed to produce, on trigger pull of the "pen", a puff of vaporized glycol and glycerine and water. Low toxicity. Source: Chimney Balloon LLC 706 Brooks Rd Mauldin, SC 29662, Website: http://www.chimneyballoon.us, Tel: (608) 467-0229
  • Smoke wicks: as smoke generators, see smoke pen & smoke pencil just above

Also see the smoke pen or smoke puffer products listed below at Smoke Gun & Smoke Pencil System Safety, Hazards, MSDS Sheets just below

The question-and-answer article about buying smoke pencils to test for air movement in buildings, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.

The importance of setting priorities for sealing these points of energy wasted is emphasized and discussed, and sketches as well as photographs of common points of building heat loss, or unwanted heat gain, and air leaks are provided in the following articles:

Building Heat Loss & Air Leaks

Building Heat Loss & Air Leaks - part 2

Building Heat Loss & Air Leaks - part 3

Building Heat Loss & Air Leaks - part 4

Smoke test for air leaks (C) Daniel Friedman Steven BlissReaders should also see Attic Energy Losses - InfraRed, the previous section of the article series HEAT LOSS DETECTION TOOLS,This article explains how to survey a building for air and heat loss or gain points in basements and crawl spaces and how to correct them. Readers should also see our article focusing on BASEMENT HEAT LOSS.

Beyond simple caulking and weatherstripping, it is important to look at the whole building - moisture and moisture sources, air quality, heating and ventilation equipment, and HVAC controls - in order to determine what steps will be most cost-effective in saving energy for that particular building.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Smoke Gun & Smoke Pen or Smoke Pencil System Safety, Hazards, MSDS Sheets

Watch out: some smoking or fogging equipment uses highly irritating or even toxic gases or chemicals (tetrachloride acid or Titanium tetrachloride, or Hydrogen chloride HCL gas) that can cause eye or respiratory problems or may be poisonous if swallowed. Be sure that you use your smoke product only after having read (and followed) the manufacturer's directions.

See the example smoke pen, smoke pencil, and smoke emitter MSDS sheets below and see our full list at Smoke Generator Chemicals Powders MSDS. The MSDS sheets for these smoke candles, pens, powders, sticks, etc. include hazard warnings, intended usage, and the original manufacturer. Our original source links indicate suppliers who distribute these products in various countries.

  • Brandax VS smoke for airflow studies, leakage testing, original source: http://www.firesys.com.au/Bjornax%20brandax%20vs%20msd.pdf, producer BJÖRNAX AB
  • Datax "pure smoke" generator for airflow studies & leakage testing, original source:
    http://www.firesys.com.au/Bjornax%20pure%20datax%20msd.pdf, producer BJÖRNAX AB
  • Dräger MSDS for Dräger CH25301 Air Current Tubes, Page 1 of 2.
    Dräger MSDS for Dräger CH25301 Air Current Tubes, Page 2 of 2.
    Watch out: the Dräger air current tube or "smoke tube" # CH16631 produces a sulfuric acid gas sulfuric acid H2SO4 /SO3 that is dangerous to life and is highly corrosive. Take a look at our copy of the Dräger MSDS for their CH25301 Air Current Tubes. We stored this MSDS in the box with the rubber bulb and tube cutter provided by Dräger. These air current monitoring tubes are provided with rubber caps so that the tube can be "stopped" or shut down when not in use. But the sulfuric acid was so corrosive that it not only caused the rubber caps to disintegrate, it actually "burned" or oxidized our copy of the MSDS paper form!
  • FP-Smoke, powder smoke for airflow studies, leakage tests, BJÖRNAX AB,. STRÅSSA FÖRETAGSBY, S-711 77 STRÅSSA SWEDEN, web search 08/31/2010, original source: http://www.bjornax.com/MSDS/MSDS_fp_smoke.pdf
  • Gastec Irritant Smoke Qualitative Fit Testing Kit No. 9501 four-pages of 30 safety warnings for respirator fit test
  • Gastec Irritant Smoke Qualitative Fit Testing Kit No. 9501 MSDS (Nextteq Corporation copy)
  • HSI Fire & Safety Group LLC, Smoke Check™ MSDS, HSI Fire & Safety Group LLC, 107 Garlisch Drive, Elk Grove Village IL 60007-1322, 847-427-8340, Manufactured for HSI at Shield Packaging Co., Inc., 50 Oxford Dr., Dudley MA 01571-3262, Tel: 508-949-0900, 24-Hour Emergency Tel: 800-424-9300 (Chemtrec) or 24-hour emergency Tel: 703-527-3887 (Chemtrec)
    • SmokeCheck™ MSDS
  • Miniax white smoke MSDS (by Fire System Services)
  • Powder-Puff smoke powder silica powder puffer, using &quo/hazmatilica" E.g. Powder Puffer S201, Regin HVAC Products, Inc., 315 Riggs Street Unit 1A Oxford, CT 06478, Tel: (203) 881-2600, Emergency Phone: (800) 424-9300, International 2024837616,
  • Pure-AX:3 & Pure-AX:9 "pure smoke" generators for airflow studies, leakage tests, original source: http://www.firesys.com.au/Bjornax%20pure%20AX3%20AX9%20msd.pdf, producer BJÖRNAX AB
  • Regin HVAC Products, 203-323-0115, and Regin Products for Heating, Air Conditioning, & Special Effects, Regin HVAC Products, Inc. 315 Riggs Street, Unit 1 Oxford, CT 06478 USA, Tel: (203) 881-2600 or (800) 394-2739 [11]
    • MSDS for Regin's Smoke Bottle (Titanium tetrachloride, liberates HCL gas) for smoke testing, Smoke Bottle RFA, S101, Air-Check, 4811C. 11/01/2007
    • MSDS for Regin's Smoke Emitter test material (PotassiumChlorate & Ammonium Chloride), 11/05/07
    • MSDS for Bjornax AB's FP Smoke distributed also by Regin, 2010/01/15, "not classifed as dangerous according to Directive 1999/45/EC (EU), (Dimethyl silicone reaction product with silica & Calcium carbonate (CaCO3) [See first aid measures in the MSDS]
    • MSDS for Bjornax AB's Smoke Match (Splintax) distributed also by Regin, 2008/08/03
    • MSDS for Bjornax AB's Smoke Pen, generator for airflow studies and leakage tests, 2007/07/30
    • MSDS for Bjornax AB's Powder Puffer silica "smoke" generator, produced by Bjornax AB, 11/01/07
  • Splintax Smoke Match, original source: http://www.firesys.com.au/Bjornax%20splintax%20msd.pdf, producer BJÖRNAX AB
  • Smoke Check: canned smoke for smoke detector testing, HSI Fire & Safety Group, web search 08/31/2010, original source: http://inspectusa.com/HSI/MSDS/MSDS_25s_smoke_check.pdf - see the warnings!
  • Smoke Powder - AX-Powder Smoke, original source: http://www.firesys.com.au/Bjornax%20ax%20smoke%20powder%20msd.pdf, producer BJÖRNAX AB
  • Superior Signal Smoke Candle, Smoke Cartridge 3C MSDS, screening smoke produced by Superior Signal, PO Box 96, Spotswood NJ 08884, Tel: 201-251-0800, web search 10/5/12, original source: https://www2.itap.purdue.edu/msds/docs/7967.pdf; & http://www.superiorsignal.com/smoke-products/smoke-candles, smoke volume depends on model: Superior#1A - 4,000 cu.ft., Superior #2B - 8,000 cu.ft., Superior #3C & W3C - 40,000 cu.ft.,
  • FP-Smoke, powder smoke for airflow studies, leakage tests, BJÖRNAX AB,. STRÅSSA FÖRETAGSBY
    S-711 77 STRÅSA, Sweden, Tel: 0046-581-43150, 0046-581-43206
  • FP-Smoke, powder smoke for airflow studies, leakage tests, BJÖRNAX AB
  • Regin Smoke-Pen, Smoke Stick, Smoke Wick MSDS (produced by Bjornax AB, Sweden)
  • Regin Powder Puffer bottle (silica) MSDS (produced by Bjornax AB, Sweden)
  • Smoke Stick (smoke pen) for airflow studies, original source: http://www.firesys.com.au/Bjornax%20smoke%20pen%20msd.pdf, producer BJÖRNAX AB
  • Smoke pencil MSDS: Super Fog Fluid water based fogging fluid, web search 08/31/2010, original source: http://www.smokepencil.com/ an example of a food-grade glycol/glycerine-based fogging fluid that appears low in risk, distributed by The ChimneyBalloon
  • Smoke Pen MSDS: BJÖRNAX AB,. STRÅSSA FÖRETAGSBY, S-711 77 STRÅSSA SWEDEN, original source: http://www.bjornax.com/ ISO 14001 Certified with 30 minute burn time per wick.
  • Titanium tetrachloride smoke emitter bottles (manufacturer ID TBD), web search 08/31/2010, original source: http://inspectusa.com/smoke_candles/SmokeBottles-MSDS.pdf Note: this supplier appears to have cut off the page top of the MSDS that may contain manufacturer ID. Hydrogen chloride gas (HCL)
  • Titanium tetrachloride MSDS, Sciencelab.com, 14025 Smith Rd., Houston TX 77396, 800-901-7247, Websearch 08/31/2010, original source: http://www.sciencelab.com/msds.php?msdsId=9925270
  • Ventilax smoke emitter for air flow studies (by Fire System Services), producer: BJÖRNAX, original source: http://www.firesys.com.au/Bjornax%20ventilax%20msd.pdf
  • VeriFit® Irritant Smoke Generator (P/N 50811000-310N), MSDS Nextteq LLC, 8406 Benjamin Rd., Suite J, Tampa, Florida 33634 USA Tel: (877)312-2333 / (813)249-5888,

The link to the original Q&A article in PDF form immediately below is the original article that has since been replaced by an expanded/updated online version of this article (found above).

Q&A on buying Smoke Pencils or smoke guns for air leak testing - PDF version, Use your browser's back button to return to this page

The question-and-answer article below paraphrases, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.


Frequently Asked Questions (FAQs) about smoke guns, smoke pencils, smoke pens and similar test equipment used to check HVAC systems, heat exchangers, and building air leaks or air movement

Question: The Regin Smoke Pen for home use

Do you have information on the Regin Smoke Pen S220? This is for home use. - Thanks. K.N.

Reply:

Sure K. The Regin smoke pen is produced by BJORNAX AB in Sweden and is intended for use in tracing air movement such as in HVAC systems or, used with some expertise, possibly in tracing air leaks in buildings. The pen incorporates a stearic acid wick that is lit by a match or cigarette lighter and extinguished by replacing the pen cap.

We haven't tested the product but from Regin's product literature and photographs it seems that the trace smoke emitted by the pen is suitable for checking direction of air movement such as we discuss in these InspectAPedia articles and useful for checking for air leaks at HVAC systems as well as checking the direction of air flow at building openings, cracks or leaks.

No smoke emitting device is intended to provide a wide-area general building survey for heat loss. For that you'd need to look at IR and similar approaches (HOUSE DOCTOR, how-to be) using thermography and at blower door tests (BLOWER DOORS & AIR INFILTRATION). Also see THERMAL TRACKING & HEAT LOSS for a guide to visual clues that point to air movement in buildings.

Here is what Regin says about this recently-released test device:

The Smoke-Pen ($39. U.S.D.) works like a mechanical pencil. A patented smoke-emitting wick is inserted into the convenient to use pen, adjust the wick to provide 3/8” of exposed wick, light the wick with a match or lighter. The smoke pen will provide a continuous trail of smoke. The Smoke-Pen can be easily extinguished by simply replacing the protective cover. The Smoke-Pen can now be stored and re-used for the next test. The smoke and the wick itself are non-toxic, with no shipping regulations. This cool burning, non-toxic emitter is ideal for air balancing, verifying ventilation, testing smoke alarms, test for negative or positive air pressure. [11]

Like other responsible manufacturers of test equipment, Regan, through their website, provide an MSDS sheet for the smoke pen explaining that the active ingredient is stearic acid. The product is described by Regan as non-toxic. The MSDS warns of eye and inhalation exposures: "Prolonged exposure or misuse can cause irritation."

The Smoke Pen™ by Regan also includes safety advice that in our OPINION was written by lawyers but that is unlikely to describe a problem encountered by most users:

At improper ventilation use a particle filter mask class P2. All kinds of generated smoke consists of solid or liquid particles, why it is recommended to use a particle mask at longer participation in smoke filled rooms.  [11] [12]

Question: can we use incense instead of smoke to find HVAC leaks and trace air movement?

What about using incense instead of these dangerous smoking devices? - Paul - 7/8/2011

Reply:

Paul,

Incense might give an olfactory clue about certain HVAC leaks but it won't produce enough visible smoke for a visual leak test.

I agree that some smoke pens and smoke generation devices can be dangerous and so ought to be used with care.

Question: Information about the Regin Smoke Pen S220

Do you have info on the Regin Smoke Pen S220? - KJ 12/1/11

Reply:

KJ,

Regin smoke pens lead to the company's explanation that they are the U.S. distributor for products made by BJORNAX AB in Sweden, one of the worlds largest manufacturer of smoke products for technical purposes - see footnote [11] below. MSDS for various Regin smoke generating products are listed in the article above beginning at x.

The product you ask about, the REgin Smoke Pen S220 is a Bjornax product and the MSDS is at MSDS for Bjornax AB's Splintax smoke pen, generator.

Question: Is the Regin Smoke Pencil a suitable device in your estimation for putting smoke into bubbles for entertaining children

I am a soap bubble performer for kids. Is the Regin Smoke Pencil a suitable device in your estimation for putting smoke into bubbles without myself having to light up a cigarette and blow through a straw?? - Rick Findley fingerinthenose2004 - 10/5/2012

Reply:

Rick,

I wouldn't use any smoke generating product for entertaining children except one whose MSDS makes perfectly clear that there are not only no chemical or toxic hazards, but no potential irritants to eyes, skin, etc. Also, even relatively harmless products generally include a warning to keep them away from children, especially tots who may try eating or tasting something they shouldn't. Finally, for older kids, and remembering my own playing with matches, cigarettes, fire and smoke as a child, I'd be wary of giving risky ideas to kids in the audience. Something that looks easy and fun like blowing smoke into a bubble makes me worry about what a kid might make of that performance - but then, I'm a paid, professional worrier.

The Regin Smoke Pen (see the MSDS listings in the article above) is described in sales literature as "safe" and "non-toxic" but read the MSDS and you'll be better informed. For example, you'll read that the product uses stearic acid and that "prolonged exposure or misuse can cause irritation" of eyes or skin. Also, quoting:

All kinds of generated smoke consists of solid or liquid particles, why it is recommended to use a particle mask at longer participation in smoke filled rooms. [6,m 1st MSDS]

Which I take to be a poor translation of a statement intended to read:

All types of generated smoke consists of solid or liquid particles or droplets; this is why use of a respirator or other respiratory protection device is recommended for longer exposure or in dense smoke.

My own experience is that some parents or school officials, charged with being cautious, can become quite alarmed, even if actual risks to which their children were exposed were very low or even zero.

If you are going to proceed regardless of my OPINION, there are products listed in our table above as well as in our list of smoke generating products that may be potentially less hazardous or less irritating, such as products that use finely ground silica, dimethyl silicone, calcium carbonate, or propoylene glycol and water. But almost any airborne aerosol or particulate product is potentially irritating and could raise issues.

Above I've made sure that our links to Regin Smoke Pencil information includes links to the MSDS (Material Safety Data Sheet) for these products. Take a look for yourself.

...

Ask a Question or Search InspectApedia

Questions & answers or comments about choosing, buying, & using smoke pens, smoke pencils and related HVAC and building air movement test tools.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • [1] Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steve Bliss's Building Advisor at buildingadvisor.com helps homeowners & contractors plan & complete successful building & remodeling projects: buying land, site work, building design, cost estimating, materials & components, & project management through complete construction. Email: info@buildingadvisor.com
    Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com
  • [3] GAS EXPOSURE EFFECTS, TOXIC Toxic Gas Exposure Hazards and Test Protocols including links to our toxic gas exposure screening and gas testing protocols.
  • [4] Ice Dam Leaks in building attics and roof cavities, how to inspect for evidence of leaks, identify causes, and correct bad attic ventilation, improper roof venting, and these causes of attic mold or roof structure damage
  • [5] Maintenance of Fire Protection Systems and Equipment, the New Australian Standard, What does it Mean for Owners, Occupiers, and Service Providers, White Paper, Australian Standard AS1851:2005, original source: http://www.firesys.com.au/AS1851WhitePaper.pdf, Fire Protection Association, Australia, Steven Kip, Warrington Fire Research
  • [6] Björnax AB, Stråssa Företagsby, 71177 Stråssa Sweden, Tel: +46 (0)581 431 50, Fax: +46 (0)581 432 06, Website: http://www.bjornax.se
  • [7] National Draeger, PO Box 120, Pittsburgh PA 15230 - 412-787-8383, - 866-905-9793
    Website: http://www.buydraegersafety.com/
  • [8] Nextteq LLC., 8406 Benjamin Rd. Suite J.,, Tampa FL 33634 USA, 877-312-2333, 877-312-2444 website: www.nextteq.com email: info@nextteq.com.
    Nextteq MSDS for the Nextteq Irritant Smoke Tube Kit (using Gastec Irritant Smoke Tubes P/N 9500), using Stannic Chloride (CAS No. 7646-78-8, UN No. 1827), air flow indicator tube, irritant smoke generator
  • [9] Fire System Services, Unit 1, 16 Glasgow Street, Wingfield, South Australia 5013, Mail to: P.O. Box 16, Prospect SA 5082, Tel: +61 8 8445 6300, Website: http://www.firesys.com.au/, Fire System Services distributes a wide range of smoke emitters used for monitoring air movement patterns or testing smoke detectors (and other fire protection or fire extinguisher related equipment) including the Miniax, Ventilax, Brandax, Datax, white smoke emitter candles discussed above, and coloured smoke emitters such as their AAX18, AX60, and Brandax KSO.
  • [10] The Chimney Balloon LLC, 2123 N Pontiac Drive, Janesville, WI 53545, Tel: (608) 467-0229 M-F 9am - 5:00pm (CST), distributes smoke pencils at www.smokepencil.com
  • [11] Regin Products for Heating, Air Conditioning, & Special Effects, Regin HVAC Products, Inc. 315 Riggs Street, Unit 1 Oxford, CT 06478 USA, Tel: (203) 881-2600 or (800) 394-2739, web search 11/30/2011, original source: http://www.regin.com Comment from the company's website:
    REGIN HVAC Products are exclusive distributor of smoke cartridges manufactured by company BJORNAX AB in Sweden, one of the worlds largest manufacturer of smoke products for technical purposes, and with the increasing emphasis on environmental and safety issues, their products are finding an ever-widening range of applications such as: Leak testing of duct-work, pipelines, heat-exchanges, tanks etc. Study make up and exhaust air systems, smoke stacks, chimneys etc. Air balancing from grills, draft in fume hoods, negative air pressure testing, equipment testing, HEPA filter testing, smoke alarms, fire drills, film and photography and much more.
    • [12]
    • MSDS for Regins' Smoke Bottles smoke generator, Smoke Bottle RFA, S101, Air-Check, 4811C, 11/01/2007
    • MSDS for Bjornax AB's Splintax smoke pen, generator for airflow studies and leakage tests, 2007/07/30, Smoke Pen, Smoke Stick, Smoke Wick products.
    • MSDS for Bjornax AB's Powder Puffer silica "smoke" generator, produced by Bjornax AB, 11/01/07, Powder Puffer S201
    • MSDS for Regin's - Bjornax AB's Splintax smoke-match for airflow studies and leakage tests, 2007/07/30,
    • MSDS for Regin's Smoke Emitter test material, using PotassiumChlorate & Ammonium Chloride, 11/05/07, Smoke Emitters sold as S102, S103, S104, S105, S107
  • [13] Sampling for gases in air such as VOC's, MVOC's, toxic chemicals, and combustion products.
    Unfortunately no single test or tool can detect all possible building contaminants. We use methods and equipment which can test for common contaminants. If the identity of a specific contaminant is known in advance we can also test for a very large number of specific contaminant gases in buildings.
    We use gas sampling equipment provided by the two most reliable companies in the world, Draeger-Safety's detector-tubes and Drager accuro� bellows pump, the Gastec� cylinder pump and detector-tube system produced by Gastec or Sensidyne, and we also use Sensidyne's Gilian air pump. For broad screening for combustibles and a number of other toxic gases and for leak tracing we also use Amprobe's Tif8850. All of these instruments, their applications, and sensitivities (minimum detectable limits) for specific gases are described in our Gas Sampling Plan online document.
  • [14] Zefon Corporation, 1-800-282-0073, website: http://www.zefon.com, distributes a wide range of gas testing equipment including Gastec detector tubes.
  • [15] HSI Fire & Safety Group LLC, 107 Garlisch Drive, Elk Grove Village IL 60007-1322, 847-427-8340, Manufactured for HSI at Shield Packaging Co., Inc., 50 Oxford Dr., Dudley MA 01571-3262, Tel: 508-949-0900, 24-Hour Emergency Tel: 800-424-9300 (Chemtrec) or 24-hour emergency Tel: 703-527-3887 (Chemtrec) - Product Name: SmokeCheck™
  • [16] Superior Signal Smoke Candle, P.O. Box 96 Spotswood NJ 08884 Tel: 732-251-0800 Fax: 732-251-9442 info@superiorsignal.com, Smoke Cartridge 3C screening smoke produced by Superior Signal, PO Box 96, Spotswood NJ 08884, Tel: 201-251-0800, web search 10/5/12, original source: https://www2.itap.purdue.edu/msds/docs/7967.pdf; & http://www.superiorsignal.com/smoke-products/smoke-candles, smoke volume depends on model: Superior#1A - 4,000 cu.ft., Superior #2B - 8,000 cu.ft., Superior #3C & W3C - 40,000 cu.ft.,Superior Signal Smoke Candle, Smoke Cartridge 3C MSDS, screening smoke produced by Superior Signal, PO Box 96, Spotswood NJ 08884, Tel: 201-251-0800, web search 10/5/12, original source: https://www2.itap.purdue.edu/msds/docs/7967.pdf; & http://www.superiorsignal.com/smoke-products/smoke-candles, smoke volume depends on model: Superior#1A - 4,000 cu.ft., Superior #2B - 8,000 cu.ft., Superior #3C & W3C - 40,000 cu.ft.,
  • Nextteq LLC, 8406 Benjamin Rd., Suite J, Tampa, Florida 33634 USA Tel: (877)312-2333 / (813)249-5888, VeriFit® Irritant Smoke Generator (P/N 50811000-310N), & VeriFit Irritant Smoke MSDS, web search 10/5/2012, original source http://www.nextteq.com/productDetails.aspx?id=6556
  • Air Pollution Toxicology: APTI Course SI:300, Introduction to Air Pollution Toxicology, US EPA Air Pollution Training Institute, Environmental Research Center, Research Triangle Park, NC 27711, Sept. 1993, web search 08/28/2010, original source: http://yosemite.epa.gov/
  • CCSP, 2008: Analyses of the effects of global change on human health and welfare and human systems. A Report by the U.S. Climate Change Science Program and the Subcommittee on Global Change Research. [Gamble, J.L. (ed.), K.L. Ebi, F.G. Sussman, T.J. Wilbanks, (Authors)]. U.S. Environmental Protection Agency, Washington, DC, USA. Web search 08/28/2010, original source: http://nepis.epa.gov/
  • Gas Exposure Hazard Levels: for Toxic Gas Exposure to Ammonia, Arsine, Arsenic, Bromine, Carbon Dioxide, Carbon Monoxide, Hydride, Ozone - allowable exposure levels and hazard levels
  • Carbon Dioxide Gas Toxicity hazard level, poisoning symptoms, & testing
  • Health Effects of Carbon Dioxide - see "National Advisory Committee for Acute Exposure Guideline Levels (AEGLs) for Hazardous Substances; Proposed AEGL Values, Federal Register Document", http://www.epa.gov/EPA-TOX/2002/February/Day-15/t3774.htm note that these are proposed guidelines
  • Carbon Dioxide CO2: Geologic Sequestration Health Effects: "Vulnerability Evaluation Framework for Geologic Sequestration of Carbon Dioxide [on file as /hazmat/CO2_EPA_VEF-Tech_Doc_072408.pdf ] - ", US EPA, EPA430-R-08-009, July 2008, web search August 2010,original source: http://www.epa.gov/climatechange/emissions/downloads/VEF-Technical_Document_072408.pdf
  • Carbon Dioxide CO2: Geologic Sequestration, U.S EPA, web search 08/28/2010, original source:
    http://www.epa.gov/climatechange/emissions/co2_gs_tech.html
    • GTSP, 2006: Carbon Dioxide Capture and Geologic Storage: A Core Element of a A Global
      Energy Technology Strategy to Address Climate Change (PDF, 37 pp., 6.05 MB, About PDF).
      April 2006, JJ Dooley et al. Global Energy Technology Strategy Program (GSTP)
    • IPCC, 2005: Special Report on Carbon Dioxide Capture and Storage, Special Report of the
      Intergovernmental Panel on Climate Change [Metz, Bert, Davidson, Ogunlade,
      de Coninck, Heleen, Loos, Manuela, and Meyer, Leo (Eds.)]. Cambridge University Press, The
      Edinburgh Building Shaftesbury Road, Cambridge CB2 2RU England
  • Carbon Monoxide Gas Toxicity hazard levels, poisoning symptoms, & testing
  • Fluorine, Its Compounds, and Air Pollution,: a Bibliography with Abstracts, US Environmental Protection Agency, Office of Air Quality Planning and Standards, Research Triangle Park, North Carolina 27711, December 1976. Web search 08/28/2010, original source: http://nepis.epa.gov.
    NOTE: because the EPA's original source of this document in PDF format is damaged we have created a text image file, converted to a new PDF for readability.
  • Formaldehyde: US EPA. UFFI (Urea Formaldehyde Foam Insulation) was previously considered a hazard (formaldehyde outgassing). Subsequent research virtually closed concern regarding this material; however formaldehyde appears to remain a health concern for sensitive individuals.
  • Greenhouse Gas Overview: Carbon Dioxide: U.S. EPA, web search 08/28/2010, original source:
    http://www.epa.gov/climatechange/emissions/co2.html
  • Nitrogen Oxides: Air Quality Criteria for Oxides of Nitrogen, Vol III of III, US EPA, EPA600/8-91/049cF, August 1993, web search 08/28/2010, original source: http://nepis.epa.gov [Large PDF 25MB]
    Key chapters in this document evaluate the latest scientific data on (a) health effects of NOx measured ill laboratory animals and exposed human populatIOns and (b) effects of NOx on agricultural crops, forests, and ecosystems, as well as (c) NOx effects on visibility and non biological materials. Other chapters describe the nature, sources, distribution, measurement, and concentratiOns of NOx m the environment These chapters were prepared and peer revived by experts from various state and Federal government offices, academia, and private industry for use by EPA to support decision makIng regarding potentIal risks to public health and the enVIronment Although the document IS not intended to be an exhaustIve literature reVIew, It IS intended to cover all the pertinent literature through early 1993
  • Ozone Warnings - New Use of Ozone as a "mold" remedy is ineffective and may be dangerous.
  • Sampling for gases in air such as VOC's, MVOC's, toxic chemicals, and combustion products.
    Unfortunately no single test or tool can detect all possible building contaminants. We use methods and equipment which can test for common contaminants. If the identity of a specific contaminant is known in advance we can also test for a very large number of specific contaminant gases in buildings.
    We use gas sampling equipment provided by the two most reliable companies in the world, Draeger-Safety's detector-tubes and Drager accuro� bellows pump, the Gastec� cylinder pump and detector-tube system produced by Gastec or Sensidyne, and we also use Sensidyne's Gilian air pump. For broad screening for combustibles and a number of other toxic gases and for leak tracing we also use Amprobe's Tif8850. All of these instruments, their applications, and sensitivities (minimum detectable limits) for specific gases are described in our Gas Sampling Plan online document.
  • Sulfur dioxide & other Oxides: Air Quality Criteria for Particulate Matter and Sulfur Oxides, Vol. III, US EPA, Environmental Criteria and Assessment Office, Research Triangle Park NC 27711, Dec. 1982, EPA-600/8/2-029c. Web search 08/26/2010, original source: http://nepis.epa.gov [large PDF]
  • Radon Gas U.S. EPA Radon level maps, web search 2005, original source: http://www.epa.gov/iaq/radon/zonemap/zmapp33.htm
  • "Table Z-1 Limits for Air Contaminants, 1910.1000 Table Z-1" OSHA standard for air contaminant limits (http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9992) - includes for CO2, Carbon dioxide.........| CAS No. 124-38-9 | 5000 ppm | 9000 mg/m3 limits for carbon dioxide as an air contaminant.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.

  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • ...
HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com