InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

VENTILATION in BUILDINGS

ACOUSTICAL SEALANT CHOICES
AGE of a BUILDING - how to determine
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR POLLUTANTS, COMMON INDOOR
AIR SEALING STRATEGIES
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
AIRBORNE MOLD COUNT NUMBER GUIDE
ALLERGEN TESTS for buildings
ANIMAL ALLERGENS
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ARCHITECTURE & BUILDING COMPONENT ID
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BEST CONSTRUCTION PRACTICES GUIDE
Best Interior Finish Practices

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION
BRICK LINED WALLS
BRICK VENEER WALL AIR LEAKS
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CASEWORK, CABINETS, SHELVING INSTALLATION
CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CEILINGS, PLASTER, LOOSE HAZARDS
CEILING TILES - Asbestos-Containing
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CHINESE DRYWALL HAZARDS
CLOGGED DRAIN DIAGNOSIS & REPAIR
COMBUSTION AIR for TIGHT buildings
COOLING LOAD REDUCTION by ROOF VENTS
CONDENSATION or SWEATING PIPES, TANKS
CONDENSATION on WINDOWS & SKYLIGHTS

CRAWL SPACES

DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DOORS, INTERIOR
DRYER VENTING

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
ENERGY SAVINGS in buildings

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD
FIREPLACES & HEARTHS
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold
FLOOR TYPES & DEFECTS

FORMALDEHYDE HAZARDS

FOUNDATION BULGE or LEAN MEASUREMENTS
FOOTING & FOUNDATION DRAINS
FOUNDATION CRACKS & DAMAGE GUIDE
FOUNDATION WATERPROOFING
FRENCH DRAINS

FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING
GREENHOUSE / SUNSPACE GLARE

HEAT LOSS RATE CALCULATIONS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOT WATER HEATERS
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR HAZARDS TABLE
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS

MOLD in FOAM INSULATION, RESISTANCE
MOLD: A COMPLETE GUIDE TO MOLD
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEARANCE INSPECTIONS
MOLD COUNT NUMBER GUIDE
MOLD CONSULTANTS / INSPECTORS
MOLD CULTURE TEST KIT VALIDITY
MOLD DETECTION & INSPECTION GUIDE
MOLD or INDOOR AIR EMERGENCY RESPONSE
MOLD EXPERT, WHEN TO HIRE
MOLD FAQ's
MOLD LEVEL IN AIR, VALIDITY
MOLD ODORS, MUSTY SMELLS
MOLD PREVENTION GUIDE
MOLD RELATED ILLNESS GUIDE
MOLD SAFETY WARNINGS
MOLD SPRAYS, SEALANTS, PAINTS
MOLD STANDARDS
MOLD TEST KITS
MOLD TESTING METHOD VALIDITY

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASCAL CALCULATIONS
PLASTER & BEAVERBOARD & DRYWALL
PLASTER BULGES & PILLOWS
PLASTER LATH, METAL
PLASTER, LOOSE FALL HAZARDS
PLASTER TYPE IDENTIFICATION

RADIANT BARRIERS
RADIANT HEAT

SAFETY HAZARDS & INSPECTIONS
SEARS KIT HOUSES
SHEATHING, FOIL FACED - VENTS
SOFFIT VENTILATION

SOUND CONTROL in buildings

STAINS on & in BUILDINGS, CAUSES & CURES
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS & FINISHES, INTERIOR
STAINS on INDOOR SURFACES: PHOTO GUIDE

STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STONE VENEER WALLS
STRAW BALE CONSTRUCTION
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES

STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

Thermal Expansion Cracking of Brick
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
THERMAL IMAGING, THERMOGRAPHY
THERMAL IMAGING MOLD SCANS
THERMAL MASS in BUILDINGS
THERMAL TRACKING Indicates Heat Loss

VAPOR BARRIERS & AIR SEALING at BAND JOISTS
VAPOR BARRIERS & HOUSEWRAP
VAPOR CONDENSATION & BUILDING SHEATHING

VENTILATION in BUILDINGS
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATHROOM VENTILATION
  Blocked Soffit Intake Vents
  CATHEDRAL CEILING VENTILATION
  CLOTHES DRYER VENTING
  COOLING LOAD REDUCTION by ROOF VENTS
  CRAWL SPACE VENTING & Dryout Procedures
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  MOISTURE CONTROL in BUILDINGS
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  SOFFIT VENTILATION
  VENTILATION, BALANCED HEAT COST SAVINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES
    Guide to Sizing House Ventilation
  Whole House Ventilation Table
    Installation of Whole House Ventilation
  VENTILATION, EXHAUST ONLY
  Single-Port Exhaust Venting
  Multiport Exhaust Venting
    Ventilating Heat-Pump Systems
  VENTILATION, SUPPLY-ONLY
    Forced-Air Supply Ventilation
    Multiport Supply Ventilation
  VENTILATION, BALANCED
    Heat Recovery Ventilation
    Energy Recovery Ventilators
VINYL CHLORIDE HEALTH INFO
VINYL SIDING
VINYL Siding or PLASTIC Window ODORS
Volatile Organic Compounds VOCs

WALL CONSTRUCTION BARRIER vs CAVITY
WATER ENTRY in buildings

WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves
WOOD FLOOR DAMAGE

More Information

Whole house ventilation system (C) Daniel Friedman Whole House Ventilation Design Guide
     

  • Key strategies for whole house ventilation & Fresh Air Intake
  • How to choose the size & type of whole house ventilation system
  • Table comparing different house ventilation systems
  • Removing or keeping out indoor contaminants
  • Best methods for cleaning & filtering indoor air
  • Questions & Answers about how to buy, install, use & maintain a whole house ventilation system & ventilation system impacts on indoor air quality
  • References

Click to Show or Hide Related Topics

  • AIR LEAK DETECTION TOOLS - home
  • AIR POLLUTANTS, COMMON INDOOR
  • ATTIC LEAKS, CONDENSATION & MOLD
  • AIR CHANGE RATE ACH HEAT SAVINGS
  • ATTIC CONDENSATION CAUSE & CURE
  • BATHROOM VENTILATION
  • BLOCKED SOFFIT INTAKE VENTS
  • BLOWER DOORS & AIR INFILTRATION
  • BLOWER FAN CONTINUOUS OPERATION
  • CATHEDRAL CEILING VENTILATION
  • COMBUSTION AIR for TIGHT buildings
  • COOLING LOAD REDUCTION by ROOF VENTS
  • CRAWL SPACE DRYOUT PROCEDURES
  • DRYER VENTING
  • FLAT ROOF MOISTURE & CONDENSATION
  • HEAT LOSS in BUILDINGS - home
  • HEAT RECOVERY VENTILATORS
  • HOT ROOF DESIGNS: Un-Vented Roof Solutions
  • HUMIDITY LEVEL TARGET
  • ICE DAM PREVENTION
  • INDOOR AIR QUALITY & HOUSE TIGHTNESS
  • INDOOR AIR QUALITY IMPROVEMENT GUIDE
  • INSULATION LOCATION - WHERE TO PUT IT
  • MOISTURE CONTROL in BUILDINGS - home
  • ODOR DIAGNOSIS CHECKLIST, PROCEDURE
  • VENTILATION in BUILDINGS - home
  • ROOF VENTILATION SPECIFICATIONS
  • Roof Venting: Eaves Intake if no Overhang
  • Roof Venting: Soffit Intake Vent-Continuous
  • Roof Venting: Un-Vented Hot Roof Solutions
  • ROOF VENTING ENERGY SAVING DETAILS
  • ROOF VENTING NEEDED?
  • SKYLIGHT VENTILATION DETAILS
  • SOFFIT VENTILATION
  • VENTILATION, BALANCED
  • VENTILATION, BALANCED HEAT COST SAVINGS
  • VENTILATION DESIGN PROBLEMS & SOLUTIONS
  • VENTILATION, WHOLE HOUSE STRATEGIES
  • VENTILATION, EXHAUST ONLY
  • VENTILATION, SUPPLY-ONLY
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Whole house ventilation systems: This article explains how to design, buy, and use a whole house ventilation system to improve indoor air quality in homes.

This article includes excerpts or adaptations from Best Practices Guide to Residential Construction, by Steven Bliss, courtesy of Wiley & Sons. But many indoor contaminants are simply too small to see, or are not particles at all but rather gases or chemicals. See ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY for our full list of environmental hazard identification and remedy related to buildings. See VENTILATION in BUILDINGS for our full list of building ventilation articles.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Whole House Ventilation Strategies for Improving Indoor Air Quality

There are a number of strategies for providing whole-house ventilation, which vary in cost, complexity, and effectiveness. All strategies, however, can be categorized as either exhaust-only, supply-only, or balanced (Below we provide Table 7-1 - Whole House Ventilation Strategies).

Guide to Sizing House Ventilation Systems - How Many CFM of Vent Fan Capacity are Needed?

As detailed in Best Practices Guide to Residential Construction:

ASHRAE Standard 62-1989 recommends a minimum ventilation rate in houses of 15 cfm per person, or .35 air changes per hour (ACH), whichever is greater. Based on the ACH method, a three-bedroom house of 1,500 sq ft with 8 ft ceilings would require:

(1,500 x 8) x .85 x .35 / 60 = 60 cfm

Multiplying the volume by .85 accounts for partitions and exterior wall thickness.

Using the per person method and assuming two people in the master bedroom and one in each other bedroom, the rate is also 60 cfm.

The revised ASHRAE standard 62.2, released in 2003, uses the formula of 7.5 cfm per person (based on the number of bedrooms plus one) plus an factor of .01 cfm for each square foot of house area. For example, based on the new ASHRAE standard, the same three-bedroom, 1,500-square-foot house would require:

(7.5 x 4) / (1,500 x .01) = 45 cfm.

As these calculations show, a low ventilation rate is adequate if run on a continuous basis. A higher continuous rate would be advisable for a home with higher-than-average moisture levels or pollutant sources such as smoking. Intermittent ventilation can also work as long as the total daily ventilation rate is equivalent, but is most effective when the system is timed to operate when people are home breathing air and generating pollutants.

A two-speed or variable-speed fan provides flexibility, allowing the ventilation rate to be raised when needed, for example when painting a room or during a party. More important than the precise number of cubic feet per minute, however, is a well-designed system that is quiet, reliable, and low- maintenance, ensuring it will actually be used.

TABLE 7-1 Whole House Ventilation Strategies

Table of whole house ventilation strategies (C) J Wiley, Steven Bliss

Installation Tips for Whole House Ventilation Systems

Whole-house ventilation systems should be installed by people familiar with the equipment. Since they normally operate at 100 to 200 cfm rather than the much larger fans found in air handlers, they are less forgiving of errors. Numerous field studies have found heat-recovery ventilators performing poorly due to installation errors and poor maintenance.

For good performance with whole-house ventilation systems, follow these general guidelines:

  • Size the whole house ventilation system correctly. Oversizing will increase heating and cooling costs.
  • Choose quiet, efficient fans in the house ventilation equipment
  • Keep HVAC or ventilation duct runs as short and straight as possible.
  • Locate fresh air intakes away from pollution sources such as cars, pesticides, and outlets from HVAC equipment or exhaust fans.
  • Seal all ducts and insulate where required. Examples: Insulate intake ducts that run though a hot attic or exhaust ducts that pass through a cold, unheated space.
  • Integrate spot ventilation in bathrooms or provide separately.
  • Use separate spot ventilation in kitchens due to grease.
  • Place supply registers high on walls and away from beds, sofas, chairs, and other places likely to cause occupant discomfort.
  • Keep controls as simple and automatic as possible.
  • Educate homeowners about the system and maintenance requirements.

-- Adapted with permission from Best Practices Guide to Residential Construction.


Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Questions & answers or comments about how to buy, install, use & maintain a whole house ventilation system & ventilation system impacts on indoor air quality.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • Steve Bliss's Building Advisor at buildingadvisor.com helps homeowners & contractors plan & complete successful building & remodeling projects: buying land, site work, building design, cost estimating, materials & components, & project management through complete construction. Email: info@buildingadvisor.com
    Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com
  • Historic Preservation Technology: A Primer, Robert A. Young, Wiley (March 21, 2008) ISBN-10: 0471788368 ISBN-13: 978-0471788362

Air Leaks, Moisture Problems, Vapor Barriers & Ventilation in buildings - References, Products

  • Basement Moisture Control, U.S. Department of Energy
  • Building Pathology, Deterioration, Diagnostics, and Intervention, Samuel Y. Harris, P.E., AIA, Esq., ISBN 0-471-33172-4, John Wiley & Sons, 2001 [General building science-DF] ISBN-10: 0471331724 ISBN-13: 978-0471331728
  • Building Pathology: Principles and Practice, David Watt, Wiley-Blackwell; 2 edition (March 7, 2008) ISBN-10: 1405161035 ISBN-13: 978-1405161039
  • Crawl Space Moisture Control, U.S. Department of Energy
  • Energy Recover Ventilation Systems for buildings, U.S. Department of Energy
  • Energy Savings Methods: Whole House Systems Approach, U.S. Department of Energy
  • Log Homes: Minimizing Air Leakage in Log Homes, U.S. Department of Energy
  • Log Homes: Controlling Moisture in Log Homes, U.S. Department of Energy
  • Log Homes: Log Home Design, U.S. Department of Energy
  • Moisture Control in buildings, U.S. Department of Energy
  • Moisture Control in Walls, U.S. Department of Energy
  • Quality Standards for the Professional Remodeling Industry, National Association of Home Builders Remodelers Council, NAHB Research Foundation, 1987.
  • Quality Standards for the Professional Remodeler, N.U. Ahmed, # Home Builder Pr (February 1991), ISBN-10: 0867183594, ISBN-13: 978-0867183597
  • Natural Ventilation for buildings, U.S. Department of Energy
  • R-Value of Wood, U.S. Department of Energy
  • Spot Ventilation for houses, U.S. Department of Energy
  • Slab on Grade Foundation Moisture and Air Leakage, U.S. Department of Energy
  • Straw Bale Home Design, U.S. Department of Energy
  • "Vapor Barriers or Vapor Diffusion Retarders", U.S. DOE: how vapor barriers work, types of vapor diffusion barriers, installing vapor barrier
  • Ventilation for energy efficient buildings, Purpose, Strategies, etc.,
  • Weather-Resistive Barriers, how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • Whole House Ventilation Systems, U.S. Department of Energy
  • Whole-House Balanced Ventilation Systems, U.S. Department of Energy
  • Whole-House Exhaust Ventilation Systems, U.S. Department of Energy
  • Whole-House Supply Ventilation Systems, U.S. Department of Energy

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com