FAQs about using framing tables for decks, porches & other wood construction: joist & beam spans & sizes.
This article series gives recommended or allowable joist & beam spans and explains typical spans for deck joists, deck beams, and deck flooring, giving both standard span tables and a quick "rule of thumb" that works pretty well.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions & answers about finding & using wood framing span tables for decks, porches, other common building floor structures were posted originally at FRAMING TABLES, SPANS - be sure to consult the tables and rules of thumb given there.
On 2019-03-02 by (mod) - using 3/4" porch floor boards over joists with what spacing?
Mike
Standard deck framing for joists of various depths (you don't give the depth nor span of your porch floor joists) are in the article above.
Just specifying "12" OC joist spacing is not enough to even make a wild guess at spans allowed.
I agree that building codes are probably not going to specify joist spacing for 3/4" thick boards (of unspecified width) directly placed onto the joists.
Common porch flooring is not 3/4" thick but rather is 7/8" in these widths:
Tongue-and-groove profile – 3-1/8" x 7/8" x 10', 12' and 16'
Solid profile – 3-1/8" x 7/8" x 12'
Those are commonly installed on joists that are 16" o.c.
So your 12" o.c. with the thinner flooring may be ok.
Comparing a porch floor with 3/4" boards to a deck with heavier flooring:
Typically actual deck boards are 5/4 thick lumber and requires 16" o.c. joists. If you were building a deck (not a porch) using 2x lumber (like 2x6s) that flooring can be installed over joists that are up to 24" o.c.
Indoors where 3/4" thick flooring is installed in modern construction it's placed over at least a layer of 3/4" subfloor. So when you're going to a non-standard construction plan for an indoor floor you probably need to find suggestions either from your deck board supplier/manufacturer or from a local engineer or architect.
Keep in mind that the joist tables above are for the deck structure and don't address whether or not your flooring will be saggy or bouncy as it spans the joist themselves.
More tables that you might want to check out are at FRAMING AGE, SIZE, SPACING, TYPES inspectapedia.com/structure/Framing_Size_Spacing.php
On 2019-03-01 by Mike - 12" o.c. joist spacing and 3/4" white oak boards
I’m using 3/4” White Oak for a porch deck. I’m planning on 12” OC for the joist spacing but can’t find anything in the code that states that is correct.
Mike
On 2018-09-26 by (mod) - what size lumber should I use for a 10 foot span
Bob
Please check the joist span tables in the article FRAMING TABLES, SPANS.
There you will see that the span distance that you're allowed depends on the wood species, the joist dimensions, and the joist spacing.
On 2018-09-17 by Rob
What size of lumber should I use for decking that has no joists but will span 10 feet?
On 2018-06-23 by (mod) - rule of thumb for using 2x6's
Thanks for the thank you Red. We work hard to provide authoritative data so we're grateful when a reader finds it useful.
In Steve Bliss’ tables above Table 4-7 gives beam sizes (click to enlarge) and Table 4-8 gives joist spans.
A typical 2x6 SYP (the most common you’ll find at a Home Depot store or Lowes)
according to the table in FRAMING TABLES, SPANS when spaced 16” o.c. can span 9’9”
Our “rule of thumb” discussed earlier on this page and applied to a 2x6 would have given
(6-2)x2 = 8 ft. allowable span,
which would have been within the actual joist span table and would have been “safe”.
Questions, content criticism, content contributions, photos (of your deck) are entirely welcome.
- Editor
On 2018-06-23 by Redhead
Just wanted to say thank you for posting the 2x6 etc. deck span chart. I am building a deck at just 6 inches (beams are 4"x6"x12' with 3 supports on each beam) above ground level and have an 8 foot span and 2 foot overhang past the main beams.
It is good to know that I could go as wide as 9 feet at the span without compromising the strength overall. That would be quite a drop if I got it wrong, kidding ;o)
On 2018-02-28 by (mod) - deck's supporting joists should be no more than 24" o.c. for nominal 2" thick SYP deck boards
Bob,
Bottom line: your deck's supporting joists should be no more than 24" o.c. for nominal 2" thick SYP deck boards and the joist depth needed depends on the joist spans and beam placements.
I would not frame a deck with joists at more than 24" o.c.
So your "floor board span" is never more than 24" joist - to - joist.
ANSWER:
Using
5/4" thick SPF (Spruce Pine Fir) PT (pressure treated lumber) deck flooring, the 2x deck joists should be 16" o.c. and the joist depth required depends on the joist span.
2" thick SPF, Hem-Fir, northern white cedar, redwood, or western red cedar, or southern pine deck flooring, the 2x deck joists may be spaced 24" o.c.
Incidentally, other readers, nominal 2x8 SPF pressure treated lumber is really only 1 1/2" thick
On 2018-02-27 by Bob R - max span for 2x8 PTs when used as decking boards?
What is the max span for 2x8 PTs when used as decking boards?
On 2017-06-28 by Petrosorr
I have a situation I'm looking for advice on. I own a 1928 house in Seattle that was constructed 20' wide with a 6x6 beam spanning the joists in the center of the basement.
The beam sits on 6' tall 6x6 posts (it's a low ceiling), staggered 8' OC.
A chimney at one end of the house interrupts the beam, with the final section spanning 8' beneath the living room.
I would like to replace this final 8' span with two 6x6 beams on either side of the chimney. Since the chimney is two feet back from where the current post supports the beam, the two new beams would be spanning 10'-6" instead of 8'.
I can't very well use a larger beam as the head height is already quite low. I've read around that 6x6 Doug Fir isn't advisable as a beam, but the current beam has been in place for 90 years and I would imagine two of them would split the weight.
Can anyone advise for or against two 6x6 beams spanning 10'-6"?
On 2016-12-03 by Max McKnight
Using 2x6 joist, do they need to be supported on 8'3". Maybe I didn't,read correctly the chart. Tanks
On 2016-07-26 by (mod) - can I use 32" on center joist spacing
No, I wouldn't
On 2016-07-26 by Tara
If I have 1.25" thick deck boards can I use 32" on center joist spacing
On 2016-07- by Ted
looking for joist span info for hem fir used in a tree house
On 2016-06-20 by (mod) -
In the article FRAMING TABLES, SPANS see Table of Maximum Beam Spans for Exterior Decks
On 2016-06-20 by Doyle Terrell
As a deck cover. Considering a snow load of up to two feet, what size beam do l need?
Camino
I need to span 16 ft. With a beam that will carry 2"x6" rafters which will be sheeted with opaque corrugated fiberglass to serve as. a
On 2016-04-25 by Mike csiro
I want to change out rotted 4x4 post with 6x6 post. Deck is 12 20 with triple 2x8 band. How far apart can I place the 6x6 posts.
...
Continue reading at DECK LAYOUT if you need to know how to lay out and square up the deck plan to set exact pier & post locations, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
FRAMING TABLES, SPANS FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Or see
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about allowable spans for deck, floor, or porch framing. .
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.