Bad water pressure regulator:
How to diagnose and fix or replace a bad water pressure regulator. This article describes Diagnosing a Bad Water Pressure Regulator - how to diagnose the loss of water pressure and the need for a replacement water pressure regulator. The process of water pressure problem diagnosis and the costs of the repair are explained.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Water pressure regulators are devices that protect building plumbing systems from excessive water pressure damage by reducing incoming high water main pressure (that can be more than 150 psi in some communities) to a safe level (typically 50 psi) in the building.
[Click to enlarge any image]
Our photo (left) shows typical incoming municipal water piping at a building. From left to right we see a main water shut off valve, a water meter (wires lead to an outdoor water meter reading device), a water pressure regulator, and water piping rising into the building. The articles listed just below discuss how to adjust a water pressure regulator:
An alternative to installing or changing a water pressure regulator when building water pressure is occasionally 80 psi or higher is the installation of an expansion tank to temporarily absorb that pressure increase.
Proper use of an expansion tank can help avoid unnecessary opening of the pressure/temperature relief valve on a hot water heating tank or a hot water heating boiler.
The water pressure regulator can be adjusted to improve building water pressure and thus flow, by loosening a lock nut on the regulator and screwing the adjustment screw up or down a few turns.
Our photo (left) shows the water pressure regulator (photo bottom) and the regulator screw and lock-nut.
Be careful not to set the building water pressure too high, as you'll cause leaks.
For details on adjusting a municipal water pressure regulator
see WATER PRESSURE REGULATOR ADJUSTMENT
Watch out: don't set the water pressure reducing valve higher than necessary. Doing so wastes water and as we discuss
at WATER PRESSURE TOO HIGH: DANGERS, setting water pressure too high can cause both plumbing problems and actual serious safety hazards at buildings.
As we discuss in more detail at WATER PRESSURE VARIATION CAUSES, there are several causes of variation in building water pressure:
Key things to check when water pressure and flow are inadequate in a building served by municipal water supply are
Bad water pressure regulator or bad pressure regulator adjustment: (poor municipal water pressure)
if the building is connected to a municipal water supply there may be a water pressure regulator installed, usually close to the water meter or where the water supply pipe enters the building. Photos of water pressure regulators and diagnosis and adjustment advice are
at WATER PRESSURE REDUCER / REGULATOR.
If the water pressure control was set too low to start with
or if there is a problem with the water pressure regulator, you may see an improvement in water pressure by diagnosing and adjusting or repairing this control.
If the loss of water pressure was sudden,
it's not likely to be a problem the pressure regulator except in the less common cases of a blockage or failure in the regulator itself.
In this photo our flashlight lights up a (rather amateurish looking) water pressure regulator installed on a municipal water supply.
You can see that a previous connection to the water meter was cut, left shut off (see that shutoff valve at the left hand vertical pipe - what happens if someone opens that valve?), and new fittings were installed to conduct incoming water to the building water supply piping.
The use of smaller diameter flexible copper tubing might restrict the incoming water flow, but the presence of a pressure regulator at all suggests that the incoming pressure may have been excessive. (Too high water pressure leads to fixture leaks.)
Details about how to adjust the building water pressure regulator or pressure reducing valve are found
at WATER PRESSURE REGULATOR ADJUSTMENT. Excerpts are below.
We have already mentioned checking and adjusting the pressure control for the water pump on a private well system - just above. But what if the home does not have it's own well - what if the building is connected to a municipal water supply?
A water pressure regulator may be installed. See the illustration at the top of this article .
A device, usually a few inches across and often shaped a bit like a bell, may be found installed at the water meter. The water meter is often installed where water pipes enter the building and the pressure regulator will be installed just after the water meter on the same pipe. You may see a screw secured by a lock-nut on the top of the meter or there may be another screw or knob that will permit the water pressure regulator to be adjusted to set the water pressure up or down in the building.
Which way to turn the water pressure regulator screw? On most pressure regulators, after loosening the lock-nut around the adjusting screw, turning the screw in will increase the water pressure. Don't overdo-it. Just a turn or two should make a difference. Keep track of the number of turns so that you can go back to where you started if necessary.
Sometimes the municipal water supply may itself be temporarily shut down or running at reduced flow. Check with your local water department or neighbors.
Increasing the building water pressure by adjusting the pressure regulator (or a pump pressure control switch) will not fix a poor water delivery rate from the source (municipal water main or local private water pump), but if the pressure was set too low to start with you may see an improvement by this adjustment. If your loss of water pressure or flow was sudden, it's not likely to be a problem with the pressure regulator except in the less common cases of a blockage or failure in the regulator itself.
Watch out: don't set the water pressure reducing valve higher than necessary. Doing so wastes water and as we discuss
at WATER PRESSURE TOO HIGH: DANGERS, setting water pressure too high can cause both plumbing problems and actual serious safety hazards at buildings.
For details about diagnosing poor well water pressure and flow, start
at WELL WATER PRESSURE DIAGNOSIS or go directly to the individual items listed just below.
...
Continue reading at WATER PRESSURE REDUCER / REGULATOR or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see WATER PRESSURE REGULATOR FAILURE FAQs - questions & answers about bad pressure regulators posted originally on this page.
Or see these
WATER PRESSURE REGULATOR BAD at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.