InspectAPedia®   -   Search InspectApedia

Stair gauge in position on a wood scrap (C) Daniel FriedmanFraming Square Tables, Uses, Instructions
Layouts, Measurements & Cuts Using a Framing Square & Its Tables
Roof rise, run, rafter cuts, braces, or stair stringer layout using a framing square

  • POST a QUESTION or COMMENT about types of roofing materials, installation, inspection, diagnosis, repair, maintenance, & warranties

How to use a framing square.

A framing square is a lot more than a simple square-cut saw guide. This simple device is crammed with tables, data and tricks that allow a carpenter to lay out roof rafters, stairs, or other building features.

A carpenter's framing square includes tables stamped right into the tool itself. This article explains how to make quick use of a framing square and its imprinted data to get some basic roof measurement data like roof pitch or slope, rafter lengths, and end cuts, stair stringer cuts, lengths of braces and other construction measurements.

Roof measurement methods: these articles explain various methods for measuring all roof data: roof slope or pitch, rise, run, area, and other features. This article series gives clear examples just about every possible way to figure out any or all roof dimensions and measurements expressing the roof area, width, length, slope, rise, run, and unit rise in inches per foot.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Guide to Using a Carpenter's Square / Framing Square

Theoretical stair design (C) Daniel FriedmanThe standard two-foot framing square, also referred to as a "carpenter's square" and historically as a "steel square" is an L-shaped tool that is used to mark angles for cuts used in building framing, particularly roof rafters, stair stringers, and many other cuts or angles other than 90°.

On both the long and short arms of the framing square are marked various framing tables giving rafter lengths, roof slopes and the proper angle of cuts for various roofing connections such as a rafter end abutting the ridge board, the birds' mouth cut at the rafter segment that rests atop a wall plate, hip and valley rafter cuts and other information.

Here we explain just how to use a framing square and its etched-on tables to figure out roof slope & rafter lengths, rafter cuts, brace lengths & cuts, stair stringer layout & cuts and other construction & framing layouts & saw cuts.

We start by defining the parts of the square, then we list each of the tables found on the carpenter's square and we explain what the table is for.

That list includes links to detailed procedures for using each of the tables on the square.

Special tables give the number of joists, studs, or rafters in a floor, ceiling, wall or roof of given dimension. Another clever table allows you to accurately frame complex structures such as an octagon

Other tables include conversions of inches of rise/run to slope in degrees, conversion of fractions of an inch (1/32, 1/16, 1/8 etc. ) to decimal fractions, conversion of inches to decimal fractions of a foot, numbers of joists, studs, rafters, and even pilot hole size recommendations for wood screws.

Our sketch above illustrates just one of many uses of the carpenter's square: to lay-out a stair stringer, steps and step rise.

[Click to enlarge any image]

Definition of the Parts of a Framing Square: blade, tongue, heel, front, back

Parts of a framing square (C) Daniel Friedman

The parts and faces of the framing square labelled in the framing square photograph above, and are referred to as follows:

  1. The framing square BLADE or body:

     this is the wider and longer arm of the "L", normally 2" in width and 24" long.

    The "fatter" and "longer" length of the framing square is its blade.

    [Click to enlarge any image]
  2. The framing square TONGUE:

     this is the shorter and more narrow arm of the "L", normally 1 1/2 " in width and 16" long.

    The "skinny" and "shorter" length of the framing square is its tongue.
  3. The framing square HEEL:

    is the point where the two arms of the framing square meet.

    In our framing square photo above the framing square heel is indicated by the yellow arrow.

    Below we take a closer look at the heel face and the back of the heel of the framing square.
  1. The framing square FRONT or face

     is the side of the square you will see if you look at the square while holding its longer arm, the tongue, horizontally with the shorter arm, the tongue to your right and pointing down.

    When held in this position, the wider longer blade or body arm is pointing to my left and shows me a table of common rafter lengths per foot of run, hip or valley rafter lengths per foot run. Below our photo shows the front or face view of a framing square.

    The face of the framing square, by custom, is the side imprinted with the manufacturer's name and perhaps a patent identification. More useful, on the face of the framing square blade you'll find rafter framing tables.

Framing square face showing blade at top and tongue at right (C) Daniel Friedman

  1. The framing square BACK

     is the side of the framing square that you will see if you look at the square while holding its longer arm, the tongue horizontally with the shorter arm, the tongue, to your left and pointing down, as cute little Fala is demonstrating in the framing square back photo below.

    Fala's little red tongue is licking the TONGUE of the framing square BACK.

    When held in this position the wider longer blade or body arm is pointing to the right.

Photo of the back side of a framing square, tongue on left (C) Daniel Friedman

A Closer Look at the Framing Square Heel

Below our photo shows the front or face side of the heel of a framing square. You'll see that the manufacturer's name (Empire) and the framing square model number (e1190) appear on the framing square's heel face.

Framing square heel face (C) Daniel Friedman

Watch out: the measurement scales along various edges of the framing square are not all in the same units.

We will discuss the inch-divisions shown on the heel face of the framing square in just a bit further along in this article

at FRAMING SQUARE DIVISION WARNINGS 8ths 10ths 12ths & 16ths.

List of the Tables Found on a Framing Square

Framing square face showing blade at top and tongue at right (C) Daniel FriedmanHere we'll list all of the tables found on a decent quality framing square, then we'll explain how each of them is used.

6 Rafter Tables Found on the FRONT of a Framing Square BLADE

Seen from the top edge of the framing square blade then moving downwards, on the front of the blade when you hold the framing square with the tongue or shorter arm to your right and pointing down you'll see inches marked in 16ths on the blade top edge, then the tables we give below, and finally inches marked in 8ths on the bottom edge of the blade.

All of the tables listed above are explained in detail at FRAMING SQUARE RAFTER LENGTHS - explaining each of the 6 tables on the framing square's blade front

Rafter tables on a framing square (C) Daniel Friedman

Above: an example of one of the rafter length data columns explained in the article cited just above.

Octagon Table Found on the FRONT of a Framing Square TONGUE

The octagon scale on a framing square is numberd in multiples of 5 (C) Daniel Friedman

When you hold the framing square with the tongue or shorter arm to your right and pointing down, on the outer edge of the framing square tongue are inches marked in 8ths, then the table I cite below, and finally inches marked in 16ths on the inner edge of the tongue.

Details about reading and using the octagon table on a framing square are found at

FRAMING SQUARE OCTAGON TABLE in multiples of 5 (located in the middle of the tongue)

6 Tables Found on the BACK of a Framing Square BLADE

Tables on the back of the framing square blade (C) Daniel Friedman at InspectApedia.com

These tables are on the framing square back, on its long arm or "blade"

Brace Triangle Table on the Framing BACK of the Framing Square TONGUE

This table is also called the "Diagonal Scale" table.

Brace length table on the back of a framing square tongue (C) Daniel Friedman

This table shows us the length of the brace arms needed for diagonal braces used, for example, to stabilize & support posts used in timber frame construction, or in bracing the posts of a deck or porch.

The framing square Brace Triangle Table , also referred to as the Brace Rule - is discussed in detail

at FRAMING SQUARE BRACE TABLE

Other Framing Square Tutorials

Board feet calculatio & framing square example using the Essex Table (C) Daniel Friedman at InspectApedia.com

How to Use the Tables on the BACK of a Framing Square

The Number of Joists, Studs, Rafters N Run Ft-In Table on a Framing Square Blade Back

Number of joists, studs, or rafters N run (C) Daniel Friedman

Found beginning under the 2-inch column on the back of a framing square blade and extending to below the 8-inch column of data is a table titled

NO OF
JOIST
STUD &
RAFTER
N RUN
FT-IN

This table gives the number of framing members N in a floor, ceiling, wall or roof of width (or "run") W.

Complete details about this table and how to use it are found at

FRAMING SQUARE N JOISTS RAFTERS N RUN FT-IN

Convert Inches to Decimal Fractions of a Foot using the Framing Square

Found under the 9-11 inch columns on the framing square blade back, this framing square table converts inch measurements into decimal fractions of a foot.

Table converting inches to decimal fractions of a foot (C) Daniel Friedman

For example:

Change of Inches of Rise per Foot into Degrees of Slope on a Framing Square Blade Back

Found under the 12-16 inch columns on the framing square blade back, this table helps you convert inches of rise to slope expressed in degrees.

Framing square table converts inches of rise to degrees of slope (C) Daniel Friedman

For example:

See ROOF SLOPE TABLE, TYPES, WALKABILITY for a detailed table of roof slopes in rise & degrees as well as comments about roof slope walkability

Table of Wood Screw Pilot Hole Sizes on the Framing Square Blade Back

Table of wood screw sizes pilot holes (C) Daniel Friedman

Found under the17-19 inch columns on the framing square blade back, Empire includes a table of recommended pilot hole diameter for wood screws of various sizes.

For example, in the table shown above, if you are using a #10 wood screw the pilot hole should be 0.109"

Convert Inch Fractions (32nds, 16ths, 8ths, 4ths) to Decimal Fractions on the Framing Square

Table of inch fractions converted to decimal fractions on a framing square (C) Daniel Friedman

Found under the 19-23 inch columns on the framing square blade back, near the right end of the back of our framing square blade this table converts common inch-fractions from 1/32" to 15/16" into decimal fractions.

A savvy carpenter will use this table given on the right end of the back side of the framing square body to find common (close enough) conversions of fractions of an inch to 8ths, 16ths, or 32ds. That table is shown just below.

Examples:

Let's use the decimal to inch conversion table above to find the length of our brace hypotenuse in the 33 33 46.67 example given above.

We want to convert 46.67" to something in eights or sixteenths of an inch. Look into the table and find the decimal fraction closest to .67.

I see that the entry for 5/8" = .625" and the next bigger entry is for 11/16" = .687". Without a lot of thought I think figure that .687 is the closest number to my target of .67" so I'll measure my cut to 46 11/16". Let's see just how close this table gets us to spot-on by calculating the numbers instead of using the table above.

Whip out your cellphone, turn on its calculator and multiply the number of sixteenths in an inch (that's 16 of course) by .67 (the fraction of an inch given in the table) and you'll get 10.72 sixteenths.

That tells me that if I'm measuring my cut to the nearest 16th of an inch I'll measure out 46" and another 10 1/2 sixteenths inches or 46 10/16" plus a hair as we say in the trade.

And you can see that the table gave us 46 11/16" while the calculation gave us 46 10/16" plus a hair. In other words either approach gives us something between 46 5/8 (that's the same as 46 10/16) inches and 46 11/16 inches.

What's nice about these brace length numbers is that if you measure the hypotenuse length carefully to match the numbers in the brace table you can just slap your speed-square or try-square onto the length measurement point and with your square set at 45 degrees, mark your cut.

For my example, your triangular layout of the brace, measured on the outermost edge of the bracing member, will be 33" on the two short sides and 46" on the long side.

Warning About the Different Inch-Divisions on the Framing Square

Framing triangle with stair gauges attached (C) Daniel Friedman

Why do we care about identifying the "face" or the "back" of the framing square? Because the two arms and four sides of them contain different tables of saw cut information that some texts will identify by their location on the framing square.

Watch out: you can get fouled up by different subdivisions of the inch markings on the face and back of a framing square. Remember to check the divisions as the 12ths and 10ths below can lead you to make a measuring or saw cut mistake.

Some texts say "always make your measurements using the outside edges of the framing square so that you won't get fouled-up. That advice does not work. For example, the front outside edges of the framing square measure 16ths or 8ths of an inch, depending on which blade you use, but the back outside edges of a framing square are marked in 12ths.

Our photo above shows the inch divisions on the back of a framing square:

Inch divisions on the front heel of a framing square (C) Daniel Friedman

Framing square color and metal - do they matter?

Framing square (steel), and speed square (aluminum) (C) Daniel FriedmanEarly framing squares were made of hardwood and carefully trued then braced into a right angle.

Modern carpenters have used steel squares and more recently aluminum framing squares for decades.

The traditional steel framing square was black while newer framing squares are often made of aluminum. Who cares what color or metal comprise your framing square? You might.

My first framing square was made of steel and was black in color with white numbers and lines.

In the photo of my old hand tools (above), the red arrow points to this framing square while the green arrow points to an aluminum speed square whose added thickness forms a terrific saw guide.

More about these hand tools is

at DECK BUILDING & CARPENTRY TOOLS.

My old black steel framing square was easy to read in various lighting conditions, was very resistant to gouges from my rock knife when I used the square to make cuts in drywall or to make cuts in lumber as one might do to avoid chipping up wood when cross-cutting with a power saw.

This black square also got hot as hell when left flat in bright sunlight. And as the finish wore off of this tool, if I did not use it often enough it was prone to rust.

My current framing square, made by Empire Level, is made of light blue aluminum. The numbers and lines are of the same color and are quite a bit harder to read in some light conditions.

This square is also easily gouged and scarred when in use. It is a bit lighter and a bit cooler in the hot sun. I miss my old square but truth is, I had allowed the old one to get a bit rusty.

Framing square number legibility improvement tip:

As the numbers and line markings on your framing square are recessed, having been stamped into the metal of its body, you can improve the legibility of a monotonic framing square (for you carpenters that means it's all the same color), by painting the whole square surface with white latex paint.

Right after you've made a horrible white painted mess of the square's surface, wipe it off before the paint dries.

You'll see that some white paint will remain in the recessed numbers and grooves of the tool. The manufacturer could have done this too, but then they'd have to charge you more for the tool.

Using the Framing Square to Build Stairs

Theoretical stair design (C) Daniel Friedman

Separately at DECK STAIR BUILDING DETAILS we explain in detail how a framing square is used to layout rise and run on the stair stringers when building stairs.

 

Roof Framing Example 5: Location of the Bird's Mouth Cutout in the Rafter

How to use the framing square to lay out a rafter and the birds's mouth cut (C) Daniel Friedman at InspectApedia.com

This discussion now has its own page at FRAMING SQUARE for BIRDS MOUTH CUT

How to Obtain Roof Pitch or Slope by Using the Rafter Tables on a Framing Square

Roof rafter tables on a framing square (C) Daniel Friedman

This discussion got promoted to its very own web page

at FRAMING SQUARE DETERMINES ROOF SLOPE

Framing Square History, References Articles & How-To Manuals

This section has moved to

FRAMING SQUARE HOW-TO MANUALS

At the end of this article atReferences or Citations you'll find more texts and articles on using a framing square and written by other experts.


...

Continue reading at FRAMING SQUARE RAFTER LENGTHS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see FRAMING SQUARE USER'S GUIDE FAQs - Questions & answers posted originally on this page

Or see these

Building & Roof Measurement Articles

Suggested citation for this web page

FRAMING SQUARE USER'S GUIDE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING ROOFING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT