Tankless coils unwound: using a tankless coil for domestic hot water for washing and bathing.
Here we explain the function, use, capacity, inspection, and repair of Tankless Coils on heating boilers: a guide to tankless coils for domestic hot water supply: capacity, safety, clogging, adjustment, cleaning, & Repair Guide
This article series answers most questions about Heating System Boiler Controls on central heating systems to aid in troubleshooting, inspection, diagnosis, and repairs. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Tankless coils used on heating boilers:
This device, basically a coil of finned copper tubing which is inserted into the heating boiler, is used to provide domestic hot water to some buildings.
[Click to enlarge any image]
Watch out for leaks at piping fittings or more seriously the coil mounting plate which bolts the coil to the boiler (leaks at this location can destroy a steel boiler).
Watch out also for missing a mixing/tempering valve which mixes cold in with the outgoing hot water to avoid scalding temperatures at nearby taps. Some building jurisdictions require a separate temperature/pressure relief valve on hot water piping at the boiler.
The photo shows a pile of tankless coils found in a building basement next to the heating boiler.
We suspected that high mineral content in the building's water supply was causing frequent coil clogging.
The heating boiler, hot water or steam, will include a temperature limit control switch dedicated to maintaining temperature in the heater's interior for purpose of heating the coils of the tankless coil.
As the illustration at left shows, domestic hot water is heated by passing cold water through a finned copper coil which is in turn immersed in hot water inside of a heating boiler.
Drawing of a tankless coil for heating water shown here, courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
[Click to enlarge any image]
The temperature and effective quantity of domestic hot water received at a fixture in the building for washing and bathing is set, affected, or controlled by these things:
Considering these factors, you can understand that converting a large old cast iron home heating boiler with a tankless coil to a new small high-efficiency steel heating boiler that also includes a tankless coil may result in a new heating system which is more efficient and economical, but it may provide less total domestic hot water than the old system.
2020/03/24 Al said:
What is the normal btu input that a tankless coil can accept?
Thank you for the interesting question, Al. Let's put some rough calculations behind my explanation (above) of why a tankless coil system on a conventional heating boiler will run out of hot water.
A typical residential heating boiler will have itself an input BTUh between say 70,000 and 200,000 BTUs/hour. That's the rate that the oil burner is pumping heat INTO the boiler.
The rate that heat is transferred out of that hot boiler water and into the building's potable water as that potable water passes through the tankless coil is a different (unknown) number that depends on factors we cited above on this page, or below in summary:
That analysis is possible but is so complex and so theoretical as to be unlikely to describe an arbitrarily-selected home heating boiler using a tankless coil.
For that reason tankless coil and boiler manufacturers typically rate the tankless coil's ability to provide hot water as some temperature rise (increase in temperature between incoming and outgoing water - say 40 °F) for a **limited period of time** (say 5 minutes!).
The reason for that time limit is that the oil burner is sized to put heat into a boiler designed for heating the home.
In that application the temperature rise across the boiler (cold zone water entering the boiler and hot zone water leaving it) may be rather small (less than 20F) while in contrast there is an enormous temperature difference between the cold water entering the coil (40F in winter) and the desired output temperature (120F) - that's an 80 deg rise.
The burner can keep up with the boiler's need for heating the home but it cannot keep up with the rate at which a tankless coil can suck heat out of the boiler. That's why the tankless coil on a conventional hydronic boiler can never ever deliver "endless" hot water.
At 5 gpm, to heat water up from an incoming 40 °F to 120 °F we need to raise the water temperature by 80 degrees, so we will need
Factor in the boiler's efficiency in burning heating oil. The boiler is not running at 100% efficiency.
The INPUT BTUh is always more than the boiler's OUTPUT BTUh - the rate at which heat is actually delivered. A typical output BTUh is maybe 80% of the input rate.
The above is a rough back-of-the-envelope calculation - an approximation, but we can see that
Bottom line answer to your question: the tankless coil can accept as much heat as the boiler water temperature can provide, but the coil will always cool off a conventional residential heating boiler faster than the burner can keep up.
Sanity-check on the above calculation.
Advantage Engineering offers their own cute formula that is simpler than my calculations above:
Their calculator has mashed together all of the details that I preferred to give and explain above.
Using their calculator and plugging in 5 gpm, 40 °F starting temperature and 120 °F ending temperature gives 200,000 BTU/hr - which is so close to my calculation that I think we're both in the right ballpark.
Advantage Engineering, Inc. 525 East Stop 18 Road Greenwood, IN 46143 USA, Tel: 317-887-0729 - retrieved 2020/03/24, original source: https://www.advantageengineering.com/fyi/288/advantageFYI288.php
Here is a photo of a more traditional single-function heating boiler limit controls. In this example the limit switch is being used on a tankless coil, and in the enlarged version of the photo you'll see that the temperature limit on the control is set to about 140 °F.
When a heating boiler uses a tankless coil to produce domestic hot water, a third single-function control may be installed for that purpose.
In this photo a Honeywell limit control switch is being used to monitor hot water temperature at the tankless coil which is in turn mounted on a steam boiler of an older home in Portland, Maine.
You can see the black-handled mixing valve in the lower right of this photo.
Cold water from the building is entering the tankless coil via the bottom pipe (green corrosion) and hot water, heated by the coil is leaving at the upper part of the tankless coil, where it turns downwards to enter the left side of the mixing valve.
Additional cold water is permitted to enter the bottom of the mixing valve, and tempered (non-scalding) hot water then leaves at the right side of the mixing
More details about this single function limit switch are
Anti-scald valve used with water heater limit switch: In this photograph a single function limit switch is in use on a water heater, not on a heating boiler.
Here too you will notice that there is also a mixing valve installed to prevent scalding - the gray-handled device to the right of the control (and leaking we might add).
The use of a mixing valve or anti-scald valve permits us to set the Honeywell 6006 limit control switch to a higher number, keeping the water in the heater at a higher temperature.
The mixing valve in this photo adds cold to the outgoing hot water to avoid scalding, and at the same time we have more total domestic hot water for washing and bathing than if we omitted this pair of controls.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-10-29 by (mod) - do we need a relief valve on a tankless coil for hot water on a boiler?
Thanks so much for continuing the discussion, kudos for being a careful observer, and thanks also for pointing out where clarification of our information is needed; I have now updated the original photo that was found at page top and that you included again in a screen shot.
You're quite right that there's a TPR valve at lower left in the photo, and even crazier, if you follow the pipes you'll see that this particular relief valve is on the COLD side of the piping system where as far as I can tell it's doing nothing useful whatsoever. This particular anti scald valve is at the tankless coil mounted into a steam boiler, using the steam boiler's internal very hot water to produce domestic hot water.
I'll include below a close-up of that Watts anti-scald valve showing the identification of its ports as HOT (out from the coil), COLD in from building supply, and MIX (the tempered water being sent as "hot" to the building plumbing fixtures.
I made use of one of my photos of an actual installation without pointing out or commenting on that particular relief valve so it's good to have a chance to clarify that now.
The presence of that relief valve does not hurt anything (as long as it's not itself leaking) but it's not doing anything useful that I can see in this installation.
On 2020-10-29 by Josh
Thank you for the response. The main reason I.was asking is because I saw in a couple pictures you have posted on this site that the tankless coil piping has a pressure relief, and every where I looked I could not figure out why. I don't have one and wondered if I needed one. I attached an image from this page and I see what looks like a pressure relief on the cold side. Thank again
On 2020-10-07 - by (mod) -
Josh
You may have seen a Tempering device or anti scald or mixing valve at a tankless coil used for producing hot water. But you will not commonly find a pressure relief valve on the tankless coil piping. That's because there is no significant volume of hot water in the tankless coil such as would be needed to produce a BLE VE explosion
On 2020-10-07 by Josh
What relief valve should I use on my indirect coil? I see in the diagram on this website it is on the hot side but I do not see mention of the pressure rating,etc. Also I have seen pictures of some installations on this website with a pressure relief on the cold side. Help would be appreciated
On 2020-06-28 by (mod) - fixing broken tankless coil mounting bolt
Mac
To have room for a detailed answer please find your question and my reply now near the end of
TANKLESS COIL / HOT WATER COIL LEAKS how to recognize, evaluate, and repair boiler leaks on or around the tankless coil.
On 2020-06-28 by mac
twisted off middle bolt front of New Yorker furnace domestic water coil to replace a gasket. What to do?
On 2020-03-24 - by (mod) -
Al,
Thank you for asking a great question. Please find your question and my very detailed reply in the article above on this page.
Bottom line:
A typical residential hydronic heating boiler's total heating capacity at (80,000 BTUh) is less than half the tankless coil's ability to draw heat out of the boiler (at 201,600 BTUs/Hr).
Do let me know if that explanation leaves you with further questions.
On 2020-03-24 by Al
What is the normal btu input that a tankless coil can accept?
On 2019-12-09 - by (mod) -
No, Anon.
On 2019-12-09 by Anonymous
Is it a requirement to install a vacuum breaker on a tankless coil piping
On 2019-11-26 - by (mod) -
Tankless coils are always Limited in the quantity of hot water that can be delivered. In addition to maybe an anti scald device located near the coil that limits the temperature of the water leaving the system. In that case it's both a safety feature and also one that gives you longer run of hot water before you run out.
However sometimes if the plumbing fixture that's farthest away has the least water it may be that too much heat is being lost along the route of the hot water pipe. In that case you could try insulating the hot water piping.
On 2019-11-26 by Paul J. Cullinane
Why do I have to turn up my heat to get hot water in the shower? Oil fueled steam. Tankless
...
Continue reading at CLOGGED PIPES / TANKLESS COIL DE-SCALE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see TANKLESS COIL FAQs - questions & answers posted originally on this page and offering more help diagnosing tankless coil troubles.
Or see these
TANKLESS COILS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about tankless coils used to produce domestic hot water: clogging, leaks, water quantity, water temperature, scale formation and cleaning
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.