Aluminum electrical wiring field failure photographs:
Color photos and descriptive captions from CPSC Meeting 9/28/95.
In this document aluminum wire twist-on connector failures and repair procedures are described, including aluminum wire repair methods which work and methods which do not work and are unsafe. Color photos of aluminum wire repair procedures, and photos of failed connectors are included.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
This document series describes hazards with existing aluminum wiring repair products, explains the aluminum wiring failure mechanism, and reviews recommended retrofit procedures including use of readily-available materials.
This information was presented to the US Consumer Product Safety Commission by Dr. J. Aronstein, 9/28/95. The minutes of that meeting were obtained under the Freedom of Information Act and posted by Daniel Friedman January 1996.
[Click to enlarge any image]
10. Field failures are also seen. These were from an aluminum-wired senior housing complex in the DC area.
A large number of these twist-on connector splices were found with various degrees of heat damage in an on-site inspection in which CPSC participated. (Photo courtesy of Tom Donahue)
11. The earliest visible sign of overheating is often softening and melting of the wire insulation, as in this field failure.
12. This field failure shorted to ground when the thermoplastic insulating shell softened due to overheating in the connector-spring area. Short circuits, due to insulation deterioration on the
connector or wire, add to the fire hazard posed by the failure of aluminum-wired twist-on connections.
13. This field failure is from Canada, where they had a substantial number of aluminum-to-copper twist-on splice failures in electric baseboard heater installations.
14. This field failure was in service 9 years. Failure of the aluminum-wired twist-on splices occurs in a relatively short time for a component of the permanent built-in wiring of a home.
15. Note the burn-back of the wire insulation and the characteristic discoloration pattern on the connector shell of this field failure. (Photo courtesy of Eleanor Posey)
16. This last field failure again shows the typical overheating band. A number of field failures have been shown to emphasize that they are not rare. Both UL and CPSC investigated field performance
and uncovered a substantial number of failures, with the worst-case failures resulting in structural fire and fatalities.
...
Continue reading at ALUMINUM WIRE to WIRE CONTACT or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
ALUMINUM WIRING FIELD FAILURES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about field failures of aluminum wiring connections and repair connections.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.