This article discusses kitchen vent fans:
Kitchen vent fan types, ventilation rate, installation specifications, and noise ratings.
We also discuss downdraft fans and kitchen fan noise issues. Our page top photograph illustrates a high capacity vertical rise range hood in a New York home. This is the most-effective kitchen exhaust ventilation design, but attention to fire safety is required with this and all exhaust fan systems.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Kitchens and bathrooms are key sources of indoor moisture and other pollutants. Kitchens produce particulates and atomized grease from cooking, and with a gas range, they also produce combustion by-products including nitrogen dioxide and carbon monoxide.
Also see INDOOR AIR QUALITY IMPROVEMENT GUIDE.
Our photos illustrate a traditional through-wall kitchen exhaust vent fan installed ca 1970 [DF]. The outdoor termination for this kitchen exhaust fan requires occasional caulking, and periodically the entire fan assembly is removed and cleaned to remove accumulated grease.
A magnetically-attached cover is sometimes installed over traditional through-wall kitchen exhaust fans to avoid drafts or heat loss in cold weather.
Kitchen cooktops produce large amounts of water vapor, atomized grease, particulates, and cooking odors. In addition, gas cooktops produce combustion by-products, including carbon dioxide, nitrogen dioxide, nitrous oxide, and carbon monoxide.
Also see BACKDRAFTING HEATING EQUIPMENT.
The most effective way to remove the moisture and contaminants from a cooktop is with an overhead range hood vented to the outdoors.
Unvented range hoods offer no protection against moisture and combustion gases and provide only minimal protection against grease, smoke, and odors trapped by the filter.
This article includes excerpts or adaptations from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) , by Steven Bliss, courtesy of Wiley & Sons. Photographs are by Daniel Friedman.
Research at the University of Minnesota has shown that many range hoods are too small, too high, or not oriented properly to do their job well.
According to the study, the most effective range hoods are at least as wide as the cooktop and rectangular rather than angled in front.
For best performance, standard hoods should be mounted no more than 24 inches above the cooking surface and project out at least 20 inches from the wall (see Figure 6-57).
[Click any image or table to see an enlarged version with additional detail, commentary & source citation.]
Some high-capacity ventilators are designed to work from 24 to 30 inches above the cooking surface,
but the stronger fans increase the risk of backdrafting other combustion appliances.
Hoods integrated with microwaves typically project out
only 13 to 15 inches and miss most of the contaminants generated by the front burners.
[Click to enlarge any image]
The minimum ventilation rate for kitchens required by the 2003 International Residential Code is 100 cfm intermittent or 25 cfm continuous (if part of a whole-house ventilation system).
Most industry experts recommend that overhead range hoods have a minimum capacity of 150 cfm and recommend higher capacity fans for open grilling, high-BTU commercial-style ranges, and other cooking styles that generate greater than average steam or smoke (see Table 6-14).
[Click any image or table to see an enlarged version with additional detail, commentary & source citation.]
A rule of thumb for high-output ranges is 1 cfm of ventilation per 100 BTU’s of output. With high-powered fans, multi speed controls are best so the fan speed (and noise) can be lowered when full power is not required.
As a general guideline, a residential exhaust fan that is left on constantly and that runs at 400 CFM or below, should operate at a noise level of 3 sones or less.
An under-sized kitchen range exhaust hood will increase the exhaust fan noise.
A kitchen exhaust hood should be at least as wide as the range top it serves. A good kitchen exhaust range hood installation places the hood opening no more than two feet above the cooktop surface, or 27" above the surface of an island-type cooking area.
The kitchen exhaust hood should extend 20" past the front edge of the cooking surface.
See FAN NOISES in BUILDINGS where we list sources of fan noises and provide details about sone ratings; also see our discussion of fan noise ratings in sones, discussed
at BATHROOM VENT FAN SIZING & NOISE RATINGS
Exhaust Fan Sone Ratings: noise level ratings |
||
Fan | Sones | CFM |
Broan QS 130SS Under-Cabinet Hood 30" | 1.5 | 220 |
Broan 512M Through-Wall 6" | 3.5 | 70 |
Broan 505 Vertical Discharge 8" | 6.5 | 180 |
Broan 507 Utility 8" | 7.0 | 250 |
This is a very incomplete list as the number of kitchen exhaust vent fans is enormous. We list fan brands and models for which the fan sones rating was given at typical retail outlets like Amazon
Island hoods are typically installed at least 27 inches above the cook surface so they do not interfere with sight lines.
Because they are farther from the cooktop and subject to passing air currents, they require more powerful fans than standard wall-mounted hoods.
HVI recommendations for wall-mounted and island hoods are shown in Table 6-14 above.
As Mr. Bliss noted above,
The most effective way to remove the moisture and contaminants from a cooktop is with an overhead range hood vented to the outdoors.
The interesting kitchen vent fan exhaust system shown at left was installed (we estimate) in this New York home in the 1930's. A combination of wood and metal site-built ductwork runs horizontally across an attic floor to a high-capacity exhaust fan located in the attic (green). The attic-mounted fan connects to a vertical roof exhaust port using asbestos fabric to avoid vibration damage problems.
I [DJF] was more concerned about the possible fire hazards in this long-in-place ductwork combined with a high capacity attic fan than with any possible asbestos worry.
Grease accumulating in a cool horizontal kitchen exhaust fan duct is a fire hazard, as might be a fan in this location without any fire detection control or shut-off device. Just sayin' ...
Because they lack a canopy to catch contaminants and must overcome natural convection, downdraft fans are less effective than overhead range hoods. Typically sized at 400 to 600 cfm or more, they do a reasonable job of venting barbecues and grills, but are less effective with pots and pans taller than about 3 inches.
Downdraft fans are either flush-mounted at counter level or pop up about 8 inches at the back of the range.
Look for the unit with the lowest noise rating that meets the ventilation requirements. Some hoods are rated as low as 2.5 sones, although most range from 4 to 7 sones at full power (one sone roughly equals the sound of one quiet refrigerator).
Like bathroom fans, the airflow from kitchen exhaust fans is generally rated at a static pressure of 0.1 in. (see “Ductwork,” page 262).
This is roughly equivalent to 30 feet of smooth 7-inch round or 3 1/4x10 in. metal duct venting a 200 cfm fan.
For good performance, the total equivalent duct length, not counting the wall or roof cap, should not exceed about 30 feet. Equivalent duct lengths for common fittings are shown in Table 6-15.
[Click any image or table to see an enlarged version with additional detail, commentary & source citation.]
Watch out: most sources we reviewed specifically warn against using flexible metal duct and of course dryer duct for kitchen exhuast vents, both of which are fire hazards.
With large-capacity exhaust fans of 200 cfm or greater, there is a risk of causing backdrafting of a fireplace or atmospherically vented boiler, furnace, or water heater.
The potential for backdrafting can be tested by a heating system technician and should be conducted with all household exhaust fans running to simulate the worst-case scenario. A simple preliminary test can be done by holding a stick of incense next to the draft diverter or dilution port of each combustion appliance with the furnace fan on and off.
If the smoke spills into the room for more than 30 seconds, then dedicated makeup air is most likely required. Modest amounts of makeup air can be delivered through a passive duct with an automatic damper, but significant depressurization may require an active supply fan.
The makeup air supply should be delivered into the kitchen or a nearby room not blocked by a door.
For more information see BACKDRAFTING HEATING EQUIPMENT.
This article series discusses current best design practices for kitchens and bathrooms, including layout, clearances, work space, and accessible kitchen and bathroom layout, clearances, turning space, grab bars, controls, etc.
We include advice on choosing and installing kitchen countertops, cabinets, and kitchen or bathroom flooring, sinks, and other plumbing fixtures and fixture controls such as faucets. A list of kitchen and bath product manufactures and sources is included just below.
Also see MICROWAVE OVEN VENT INSTALL
(Mar 13, 2014) Jim said:
If downdraft fans are not that effective -- and a hood over an island takes up a bunch of space -- why not just skip the ventilation completely?
Is ventilation required in a kitchen?
Jim,
There are two separate questions: the desirability of ventilation + code requirements for it and the energy efficiency & design requirements for ventilation.
For the former, national model codes and state, provincial or local codes indeed require kitchen ventilation, though "exhaust" and "ventilation" are mingled and sometimes a bit confounded. Here is an excerpt from M.D. Ewert's discussion of the Oregon building code on kitchen ventilation:
The requirements for ventilation in the ORSC can be found in Section R303.2, which states that
... all habitable rooms are to be provided with an aggregate glazing area of 8 percent of the floor area, with a minimal openable area of 4 percent of the floor area being ventilated.
The purpose of the glazing and the portion that is openable is to provide both natural light and natural ventilation.
Since a kitchen is considered a habitable room, it would require (at a minimum) a window, door, or other openings which opens directly to the outdoors, with an aggregate opening of at least 4% of the floor area. Sect ion R303.2 also allows the use of adjoining rooms to be used when determining this ventilation requirement
For the latter, ANSI/ASHRAE/IES Standard 90.1-2010 sets energy efficiency requirements for kitchen exhaust hoods and is discussed by a US DOE article on kitchen ventilation - www.energycodes.gov
[Click to enlarge any image]
(Jan 30, 2016) Anonymous said:
As an accidental reluctant and inescapably entrapped lifelong do-it-all-myself-"err", I stray easily amongst this wealth of solutions for issues that I seek to address. My immediate quest is to find any information for kitchen range fan wall cap exhaust termination clearance from a double-hung window. While there are many other variables to consider, I feel that I lack that important detail.
I haven't seen that number either, and will research it further. Meanwhile 3-10 feet is most likely a safe number.
Handyman said: 2019/11/14
Given that there some range hoods do not even vent outside, I doubt that there is a minimum distance that code will require of you to vent away from windows. You are not venting noxious gases, just nuisance gases. Use your common sense judgment.
None of these kitchen range exhaust fan installation guides mention clearance distances from windows, though it would be smart to keep 2-3 feet away to avoid sending odors and exhaust back through an open window that otherwise is nearby.
Typical range exhaust vent instructions do address
And some such as the Miele exhaust vent instructions www.mieleusa.com/pmedia/ZGA/TX3587/9968630-000-06_9968630-06.pdf mention the safety hazard that ensues if the exhaust vent air supply is limited so as to risk stealing combustion air from nearby gas fired appliances (risking dangerous carbon monoxide poisoning)
Excerpts:
WARNING: Danger of toxic fumes. Gas cooking appliances release carbon monoxide that can be harmful or fatal if inhaled.
To reduce the risk of fire and to properly exhaust air, the exhaust gases extracted by the hood should be vented outside of the building only. Do not vent exhaust air into spaces within walls or ceilings or in attics, crawl spaces or garages.
To reduce the risk of fire, only use metal ductwork. Please read and follow the "IMPORTANT SAFETY INSTRUCTIONS" to reduce the risk of personal injury. Follow all local building codes when installing the hood. (Miele)
And Zephyr notes
NEVER exhaust air or terminate duct work into spaces between walls, crawl
spaces, ceiling, attics or garages.
All exhaust must be ducted to the outside, unless using the recirculating option.
Use single wall rigid Metal ductwork only. Fasten all connections with sheet metal screws and tape all joints w/ certifi ed Silver Tape or Duct Tape. (Zephyr)
Commercial kitchen exhaust vents have different requirements
Section 304, Business Group B
Section 305, Educational Group E
Section 306, Factory Group F
Section 307, High-Hazard Group H
Section 308, Institutional Group I (this includes hospitals)
Section 309, Mercantile Group M
Section 310, Residential Group, or R, R-1, R-2, R-3, R-4
Section 311, Storage Group S
Section 312, Utility and Miscellaneous Group U
-- Portions of this article were adapted with permission from Steve Bliss, Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) .
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-08-02 - by (mod) -
Fair question, Steven but as odor sensitivity is so individual and variable I'm not able to give a certain answer to what you may smell when cooking. I agree that your set up is a bit higher than usual over the stove- an arrangement I actually prefer for it gives more working space. I'd trust the manufacturer.
As a general rule of thumb, Rangecraft recommends that a range hood fan should move a minimum of 100 CFM of air for every 12 inches of stove width.
At 1000 CFM (your range exhuast vent fan capacity BEFORE considering duct restrictions) that's 1000/100 = 10 x 12 or 120 " of stove width - plenty of capacity.
On 2020-08-02 by Steven Taylor
**CORRECTION**to my previous question - The hood is 24" not 18" - Thanks
Hood = Z-Line/1000CFM - 30" x 18" - 8" ducting - Installed 36" above stovetop...I'm concerned that the hood is too high although the manufacturer says it's OK. With a hood this size, should I be able to smell any cooking odors while the fan is running?
On 2020-06-02 - by (mod) -
Maybe, Steve, depending on the materials, routing, number of bends, length, of the existing vent, and thus depending on whether or not the combined vent is sufficiently free-flowing and fire-resistant.
Check the instructions in the specific brand and model of your range exhaust vent.
On 2020-06-02 by steve s
Can I "Y" my new range vent pipe into the existing kitchen exhaust fan piping in the attic (which is vented through the roof?)
On 2020-03-29 - by (mod) -
Jim
Thanks for an interesting question: Will a range exhaust vent work properly and safely if terminated at the ridge vent.
I cannot say with 100% certainty without reading the manufacturer's installation instructions for your particular range vent (tell me the brand and model and we can look for that)
But
in general it is dangerous and perhaps also a code violation to do what you described.
Any obstruction that reduces the vent's exhaust to the exterior risks not only inadequate venting but a future grease fire setting the building afire. In my opinion there is no ridge vent that is designed to pass or support the flow from a kitchen range hood exhaust.
Also it's likely that some of the exhaust is simply venting into the attic.
The exhaust should be vented to the outside.
On 2020-03-28 by jim
i live on the top floor of a 4-plexs with vaulted ceilings. tile roof with about a 1'.6" vented ridge. range hood exhaust vent. vents inside the vented ridge is this ok or do we need to add a vent to roof?
On 2020-03-28 by Anonymous
i live on the top floor of a 4-plexs with vaulted ceilings. tile roof with about a 1'.6" vented ridge. range hood exhaust vent. vents inside the vented ridge. is this ok ?
On 2018-08-28 - by (mod) -
Sounds reasonable to me, Ann.
On 2018-08-28 by Anonymous
Thanks for your reply. I looked at codes for Maryland, where I live, and your posting for VA above as well, and didn't see it. It sounds like if I keep the fan and area clean of grease, it will be alright. I'll go with your cleaning advice, thanks!
...
Continue reading at VENTILATION CODES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see KITCHEN VENTILATION DESIGN FAQs - questions & answers about kitchen exhaust fans posted originally at the end of this page.
Or see these
KITCHEN VENTILATION DESIGN at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about kitchen ventilation system design, installation, choices, and best practices
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.